HomeMy WebLinkAboutNC0064726_Compliance Evaluation Inspection_20160321 PAT MCCRORY
`•
DONALD R. VAN DER VAART
Water Resources
' _M/lRONNcNTALDUALITY S. JAY ZIMMERMAN
March 21, 2016
Town of East Bend
Attn: Larry W.Adams, Mayor
108 West Main Street
East Bend, NC 27018
RECEIV1DWR
SUBJECT: Compliance Evaluation Inspection
East Bend Industrial Park Wastewater Treatment Plant MAREDINCDEa2 4 c01
NPDES Permit: NC0064726
Water Quality
Yadkin County permitting Section
Dear Mr. Adams:
Ron Boone of the Winston Salem Regional Office (WSRO) of the North Carolina Division of Water
Resources (DWR or the Division) conducted a compliance evaluation inspection of the East Bend Industrial Park
Wastewater Treatment Plant on March 17, 2016. The assistance and cooperation of Mark Matthews, Operator in
Responsible Charge (ORC), was greatly appreciated. An inspection report is attached for your records and the
inspection findings are summarized below.
The East Bend Industrial Park Wastewater Treatment Plant is located at the south end of Salem Trail, in
East Bend, Yadkin County, North Carolina, at approximate coordinates 36.211336°, -80.494283°. The Town of East
Bend is authorized to operate this 0.01 million-gallon-per-day (MGD) wastewater treatment plant, which consists of
extended aeration,settling, sludge holding, UV disinfection, and backup chlorination and dechlorination,and discharge
treated effluent from outfall 001 of said treatment works into an unnamed tributary to the Yadkin River, this section of
which is currently classified as Class WS-IV waters and is located in the Yadkin Pee-Dee River Basin.
SITE REVIEW
Mr. Boone reviewed the entire plant with Mr. Matthews. Everything was in good condition and well
maintained. Mr. Boone noted no discrepancies.
DOCUMENTATION REVIEW
Mr. Matthews had all required paperwork on hand. This includes discharge monitoring reports, laboratory
reports, chains of custody, operation and maintenance logs, operator visitation logs, etc. The only discrepancy Mr.
Boone noted was that the Town does not currently have a valid certification for the field lab parameters of pH,
temperature, and dissolved oxygen. This must be addressed immediately and the appropriate field lab certification
acquired by the Town.You may initiate this process by contacting the Division's Laboratory Certification Branch. Please
call Gary Francies at 828-296-4677 or Jason Smith at 828-296-4679. You may also go to their website at:
https:lldeq.nc.ciovlaboutldivisions!water-resourceslwater-resources-datalwater-sciences-home-
paqellaboratortl-certification-branchlfleld-lab-certification
The website tells you step by step how to acquire the required field laboratory certification. Please complete this as
soon as possible. Technically, all lab data acquired without the required field lab certification is non-reportable.
Therefore, in effect, you're not even taking those samples.
State of North Carolina 1 Environmental Quality!Water Resources
450 West Hanes Mill Road.Suite 300 1 Winston-Salem,North Carolina 27105
336--6 981i0
There were no other discrepancies noted. Mr. Matthews is doing a good job operating and maintaining the
plant. Please keep up the good work in ensuring the plant is properly operated and maintained and meeting all the
terms and conditions of the permit. Please remember that violations of the permit are subject to enforcement actions
not to exceed$25,000 per day, per violation.
If you have any questions regarding the inspection or this letter, please do not hesitate to contact Mr. Boone
or me at 336-776-9800. Thank you for your cooperation in this matter.
Sincerely,
6 Y.
;{! sem:' `
Sherri V. Knight, P.E.
Regional Supervisor
Water Quality Regional Operations
Division of Water Resources
Attachments:
1. BIMS Inspection Report
CC: Central Files
NPDES Unit
WSROISWP Files
Town of East Bend
Attn: Mark Matthews, Operator in Responsible Charge
108 West Main Street
East Bend, NC 27018
United States Environmental Protection Agency Form Approved.
EPA Washington,D C 20460 OMB No.2040-0057
Water Compliance Inspection Report Approval expires 8-31-98
Section A:National Data System Coding(i.e.,PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN I 2 1.51 3 I NC0064726 111 12 I 16/03/17 117 18u, 19 Li 201
211111 11 1111111111111111111111111 11111111111 r6
Inspection Work Days Facility Self-Monitoring Evaluation Rating 61 QA Reserved----------------
671 I 70I 1 71 I ' 72 I N I 731 1 174 75i 1 1 1 1 1 1 180
Section B:Facility Data
Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date
POTW name and NPDES permit Number) 10:30AM 16/03/17 14/06/01
East Bend Industrial Park WWTP
Exit Time/Date Permit Expiration Date
NC Hwy 67E
11:30AM 16/03/17 18/12/31
East Bend NC 27018
Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data
111
Mark C Matthews/ORC/336-403-2171/
Name,Address of Responsible Official/Title/Phone and Fax Number
Contacted
Mark Matthews,108 W Main St East Bend NC 27018//336-699-4481/ I
No
Section C:Areas Evaluated During Inspection(Check only those areas evaluated)
II Permit II Flow Measurement I Operations&Maintenance II Records/Reports
• Self-Monitoring Program • Sludge Handling Disposal I♦ Facility Site Review • Effluent/Receiving Waters
is Laboratory
Section D:Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s)and Signature(s)of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Ron Boone WSRO WQ//336-776-9690/
rte_
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
/1�.�
EPA Form 3560-3(Rev 9-94)Previous editions are obsolete.
Page# 1
NPDES yr/mo/day Inspection Type 1
31 NC0064726 I1 1 121 16/03/17 117 18 I
Section D:Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
Please refer to the attached inspection summary letter.
Page# 2
Permit: NC0064726 Owner-Facility: East Bend Industrial Park WWTP
Inspection Date: 03/17/2016 Inspection Type: Compliance Evaluation
Operations& Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • El 0 0
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable • 0 0 0
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: None
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ • ❑
application?
Is the facility as described in the permit? IN ❑ ❑ ❑
#Are there any special conditions for the permit? 0 • 0 ❑
Is access to the plant site restricted to the general public? • ❑ 0 0
Is the inspector granted access to all areas for inspection? • ❑ ❑ ❑
Comment: None
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit? • ❑ 0 El
Is all required information readily available, complete and current? • ❑ ❑ 0
Are all records maintained for 3 years(lab. reg. required 5 years)? • ❑ ❑ ❑
Are analytical results consistent with data reported on DMRs? • ❑ 0 0
Is the chain-of-custody complete? • El ❑ ❑
Dates, times and location of sampling U
Name of individual performing the sampling •
Results of analysis and calibration •
Dates of analysis U
Name of person performing analyses U
Transported COCs •
Are DMRs complete:do they include all permit parameters? • ❑ 0 0
Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ 11 ❑
(If the facility is=or>5 MGD permitted flow) Do they operate 24/7 with a certified operator ❑ 11 ❑ ❑
on each shift?
Is the ORC visitation log available and current? • ❑ ❑ ❑
Is the ORC certified at grade equal to or higher than the facility classification? • ❑ ❑ ❑
Is the backup operator certified at one grade less or greater than the facility classification'? • El ❑ ❑
Is a copy of the current NPDES permit available on site? • ❑ El ❑
Page# 3
Permit: NC0064726 Owner-Facility: East Bend Industrial Park VWVTP
Inspection Date: 03/17/2016 Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Facility has copy of previous year's Annual Report on file for review'? ❑ 0 • 0
Comment: None
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained? • 000
Are the receiving water free of foam other than trace amounts and other debris? • 000
If effluent (diffuser pipes are required) are they operating properly'? 00 • O
Comment: None
Flow Measurement-Effluent Yes No NA NE
#Is flow meter used for reporting? M ❑ ❑ ❑
Is flow meter calibrated annually? • 000
Is the flow meter operational'? • 000
(If units are separated) Does the chart recorder match the flow meter? • 000
Comment: None
Aerobic Digester Yes No NA NE
Is the capacity adequate'? • 000
Is the mixing adequate'? • 000
Is the site free of excessive foaming in the tank? • 000
#Is the odor acceptable'? 11000
#Is tankage available for properly waste sludge? • 000
Comment: None
Bar Screens Yes No NA NE
Type of bar screen
a.Manual •
b.Mechanical 0
Are the bars adequately screening debris? • 000
Is the screen free of excessive debris? • 000
Is disposal of screening in compliance? 11000
Is the unit in good condition'? U 000
Comment: None
Page# 4
Permit: NC0064726 Owner-Facility: East Bend Industrial Park WWTP
Inspection Date: 03/17/2016 Inspection Type: Compliance Evaluation
Equalization Basins Yes No NA NE
Is the basin aerated? • ❑ 0 0
Is the basin free of bypass lines or structures to the natural environment? • 0 0 0
Is the basin free of excessive grease'? II ❑ ❑ ❑
Are all pumps present'? • ❑ 0 ❑
Are all pumps operable? • ❑ 0 0
Are float controls operable? • ❑ ❑ 0
Are audible and visual alarms operable? • ❑ 0 0
#Is basin size/volume adequate? • ❑ ❑ ❑
Comment: None
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater? • ❑ 0 0
Is the site free of excessive buildup of solids in center well of circular clarifier? ❑ ❑ U 0
Are weirs level? • 0 ❑ 0
Is the site free of weir blockage? • 0 0 ❑
Is the site free of evidence of short-circuiting? • ❑ ❑ 0
Is scum removal adequate? • ❑ ❑ ❑
Is the site free of excessive floating sludge? • ❑ ❑ ❑
Is the drive unit operational? ❑ ❑ • ❑
Is the return rate acceptable(low turbulence)? • ❑ ❑ ❑
Is the overflow clear of excessive solids/pin floc? • ❑ ❑ 0
Is the sludge blanket level acceptable?(Approximately''/.of the sidewall depth) ❑ ❑ ❑ IN
Comment: None
Aeration Basins Yes No NA NE
Mode of operation Ext.Air
Type of aeration system Diffused
Is the basin free of dead spots? • ❑ ❑ ❑
Are surface aerators and mixers operational? ❑ El U ❑
Are the diffusers operational? • ❑ ❑ ❑
Is the foam the proper color for the treatment process? • ❑ 0 ❑
Does the foam cover less than 25%of the basin's surface? • ❑ ❑ ❑
Is the DO level acceptable? • ❑ ❑ ❑
Page# 5
Permit: NC0064726 Owner-Facility: East Bend Industrial Park WWTP
Inspection Date: 03/17/2016 Inspection Type: Compliance Evaluation
Aeration Basins Yes No NA NE
Is the DO level acceptable?(1.0 to 3.0 mg/I) • 0 0 0
Comment: None
Disinfection - UV Yes No NA NE
Are extra UV bulbs available on site? • 0 ❑ 0
Are UV bulbs clean'? • 0 0 ❑
Is UV intensity adequate? • ❑ ❑ ❑
Is transmittance at or above designed level? U ❑ ❑ ❑
Is there a backup system on site'? • ❑ 0 0
Is effluent clear and free of solids? • ❑ 0 0
Comment: None
Pumps-RAS-WAS Yes No NA NE
Are pumps in place? • ❑ 0 0
Are pumps operational'? II ❑ 0 0
Are there adequate spare parts and supplies on site? • ❑ 0 0
Comment: None
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory? ❑ • ❑ ❑
Are all other parameters(excluding field parameters)performed by a certified lab? • ❑ ❑ ❑
#Is the facility using a contract lab'? • 0 0 0
#Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees 0 ❑ ❑ •
Celsius)?
Incubator(Fecal Coliform)set to 44.5 degrees Celsius+/-0.2 degrees'? ❑ ❑ ❑ 11
Incubator(BOD)set to 20.0 degrees Celsius+/-1.0 degrees'? ❑ ❑ ❑ 11
Comment: Town does not have field laborartory certification.
Influent Sampling Yes No NA NE
#Is composite sampling flow proportional'? ❑ El U ❑
Is sample collected above side streams? • ❑ ❑ ❑
Is proper volume collected'? • ❑ ❑ ❑
Is the tubing clean'? 0 ❑ • ❑
Page# 6
Permit: NC0064726 Owner-Facility: East Bend Industrial Park WWTP
Inspection Date: 03/17/2016 Inspection Type: Compliance Evaluation
Influent Sampling Yes No NA NE
#Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees 000 •
Celsius)?
Is sampling performed according to the permit'? • 000
Comment: None
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? 00110
Is sample collected below all treatment units? • 000
Is proper volume collected? • 000
Is the tubing clean? 00 • O
#Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees 000 •
Celsius)?
Is the facility sampling performed as required by the permit(frequency, sampling type • 000
representative)?
Comment: None
Upstream ! Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit(frequency, sampling type, and M ❑ ❑ ❑
sampling location)?
Comment: None
Page# 7