HomeMy WebLinkAboutNCG550288_Compliance Evaluation Inspection_20120529 477,A
NCDENR
North Carolina Department of Environment and Natural Resources
Division of Water Quality
Beverly Eaves Perdue Charles Wakild, P.E. Dee Freeman
Governor Director Secretary
May 29, 2012 tom:;
Mr. James M. Harrell
281 Tyre Dodson Road JUN 0 52012
Reidsville, North Carolina 27320 CEH ,,,4,L F;, �.,
DwQ;s0u
SUBJECT: Compliance Evaluation inspection
Single Family Residence Wastewater Treatment System
NPDES General Wastewater Permit NCG550000
Certificate of Coverage #-NCG550288a
Rockingham County
Dear Mr. Harrell:
Steve Mauney of the Winston-Salem Regional Office of the NC Division of Water Quality
(DWQ or the Division) conducted a compliance evaluation inspection (CEI) at the subject facility on
May 16, 2012. We were able to locate the chlorinator and the discharge point. An inspection
checklist is attached for your records and the inspection findings are summarized below.
Mr. Mauney detected no problems with the system. Please continue to have the septic tank
pumped every three to five years when the cabin is being used regularly as required by the permit
and please also check your chlorinator at least once per month to ensure it has enough chlorine and
that it hasn't clogged up. You should also ensure your chlorine tablets are rated for wastewater
treatment, not for use with swimming pools (this is normally indicated on the container). Wastewater
rated tablets can be acquired from one of the supply sources on the attached list or other local
suppliers. No flow was detected from the effluent pipe during the inspection. Annual sampling of the
effluent discharge should be conducted as required by the permit if a discharge occurs. You should
also document your operation/maintenance of the system and keep all records for a period of three
years as you have been doing and maintain records for the annual samples. Your efforts to maintain
the system properly are appreciated.
The Certificate of Coverage (NCG550288) was renewed in 2007 and will expire July 31, 2012.
Please be aware that the Division sends out invoices for the annual fee. Of course, the invoices must
be paid (annual fee currently $60/yr). It is understood that a new Certificate of Coverage will be sent
out in a few months.
North Carolina Division of Water Quality,Winston-Salem Regional Office
Location:585 Waughtown St.Winston-Salem,North Carolina 27107 One
Phone:336-771-5000\FAX:336-771-4630\Customer Service:1-877-623-6748 North Carolina
Internet:www.ncwaterquality.org Naturally
An Equal Opportunity\Affirmative Action Employer
Mr.James Harrell
NCG550288
Page 2 of 2
Thank you for your cooperation in this matter. Your continued attention to the use of chlorine
tablets and routine septic tank pumping could prevent compliance problems in the future. Should you
have any questions please feel free to contact Mr. Mauney or me at (336) 771-5000.
Sincerely,
,,,04/1/
W. Corey Basinger, Regional Supervisor
Surface Water Protection Section
Division of Water Quality
Attachments:
1. BIMS Inspection Checklist
2. NCG550000 Technical Bulletin
3. Sources for Chlorine Tablets
cc: �U.' —WS' I.
United States Environmental Protection Agency Form Approved.
E PA Washington,D.C.20460 OMB No.2040-0057
Water Compliance Inspection Report Approval expires 8 31 98
Section A: National Data System Coding(i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 I N 1 2 1 51 'I NCG550288 111 121 12/05/16 1 17 181 C I 19I S I 201 11
Remarks
211 I I I I I I I I I I I I I I I I I 1 I I I I I I I I I I I I I I I I I I I I I I I I I I 1 166
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA Reserved
671 169 701 51 711 I 721 N 1 73I 1 174 75I , 1 1 1 1 1 1 80
Section B: Facility Data
Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date
POTW name and NPDES permit Number)
01:15 PM 12/05/16 07/08/06
281 Tyre Dodson Road
281 Tyre Dodson Rd Exit Time/Date Permit Expiration Date
Wentworth NC 27375 01:45 PM 12/05/16 12/07/31
Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data
///
Name,Address of Responsible Official/Title/Phone and Fax Number
Contacted
James M Harrell,281 Tyre Dodson Rd Reidsville NC 27320//336-342-0907/3363498615 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit II Operations&Maintenance II Records/Reports •Facility Site Review
III Effluent/Receiving Waters
Section D: Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s)and Signature(s)of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Max S Mauney WSRO WQ//336-771-5000/ 9
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3(Rev 9-94)Previous editions are obsolete.
Page# 1
NPDES yr/mo/day Inspection Type 1
3 I NCG550288 111 12I 12/05/16 I 17 18 CI
Section D: Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
Page# 2
Permit: NCG550288 Owner-Facility: 281 Tyre Dodson Road
Inspection Date: 05/16/2012 Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? ■ ❑ ❑
fl
Does the facility analyze process control parameters,for ex: MLSS, MCRT,Settleable Solids, pH, DO,Sludge ONO ':
Judge,and other that are applicable?
Comment: No tests have been conducted as no discharge has been observed in
recent years. The use of the cabin is minimal except for ocassional cookouts (ie. cabin
used 3 nights in recent years). The cabin is down near the stream in the side yard of
the Harrell residence. The cabin has one bedroom and bathroom, a kitchen sink and a
pump tank and force main back to the septic tank-sandfilter system.
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new application? n n U n
Is the facility as described in the permit? ■ ❑ ❑
El
#Are there any special conditions for the permit? ❑ i
Is access to the plant site restricted to the general public? ■ ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? ■ ❑
11
Comment: The septic tank and subsurface sand filter are not accessible to the general
public. A staff report from 1988 indicates the sand filter is 261sq. feet to comply with the
minimum 2 bedroom design requirements.
Septic Tank Yes No NA NE
(If pumps are used) Is an audible and visual alarm operational? ❑ ❑ • ❑
Is septic tank pumped on a schedule? ■ ❑ ❑ ❑
Are pumps or syphons operating properly? fl ❑ U ❑
Are high and low water alarms operating properly? ❑ n • ❑
Comment: Mr. Harrell indicated the tank was pumped 3 years ago (2009) during
additional construction activity at their primary residence. The Harrell residence has 2 lift
pumps with a subsurface leach field up along the upper edge of their property. The
Harrell residence was constructed near the location of the former cabin owned by Tyre
Dodson. The current cabin is appx 200 feet from the Harrell residence and adjacent to
the creek.
Disinfection-Tablet Yes No NA NE
Are tablet chlorinators operational? ❑ ■ ❑ ❑
Are the tablets the proper size and type? ❑ ❑ • ❑
Number of tubes in use? 2
Is the level of chlorine residual acceptable? ❑ fl ■
11
Page# 3
Permit: NCG550288 Owner-Facility: 281 Tyre Dodson Road
Inspection Date: 05/16/2012 Inspection Type: Compliance Evaluation
Disinfection-Tablet Yes No NA NE
Is the contact chamber free of growth,or sludge buildup? n n n •
Is there chlorine residual prior to de-chlorination? n n • n
Comment: The cabin is not occupied and the sewer system is only used infrequently
by anyone. There did not appear to be any chlorine in the tubes but this deficiency is
mitigated by the fact there was no discharge from the system.
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained? ■ ❑ n 0
Are the receiving water free of foam other than trace amounts and other debris? ■ n ❑ ❑
If effluent (diffuser pipes are required) are they operating properly? I-1 ❑ • n
Comment: The effluent pipe extends appx. 90-120 feet from the chlorinator to the
bank of the receiving stream. The pipe was dry with soil partially blocking the outlet from
the pipe.
Page# 4