HomeMy WebLinkAboutNCG550258_Authorization to Construct_19850624 4.0
a53g •
:LC
r q,J 5o2
�5
T.i v'�Vnrv. wnJ•
State of North Carolina
Department of Natural Resources and Community Development
512 North Salisbury Street•Raleigh, North Carolina 27611
June 24, 1985
James G. Martin, Governor S.Thomas Rhodes, Secretary
Mr. Christopher Norris
1924 Bivins Road
Durham, North Carolina 27712
SUBJECT: Permit No. NC0058220
Authorization to Construct
Norris Residence
Single Family Residence
Wastewater Treatment Family
Durham County
Dear Mr. Norris:
A letter of request for Authorization to Construct was received March 8,
1985, by the Division and final plans and specifications for the subject project
have been reviewed and found to be satisfactory. Authorization is hereby granted
for the construction of a 600 GPD wastewater treatment facility consisting of
a 1,200 gallon capacity septic tank, a 270 square foot surface sand filter with
distribution box, a 27 gallon chlorine contact tank with tablet type chlorinator
and a five (5) step cascade aerator to serve the 4-bedroom Norris Residence
located at Winders Lane in Durham County.
This Authorization to Construct is issued in accordance with Part III para-
graph C of NPDES Permit No. NC0058220 issued May 6, 1985, and shall be subject
to revocation unless the wastewater treatment facilities are constructed in
accordance with the conditions and limitations specified in Permit No. NC0058220.
The sludge generated from these treatment facilitis must be diposed of
in accordance with G.S. 143-215.1 and in a manner approvable by the North Carolina
Division of Environmental Management.
The Raleigh Regional Office, telephone No. 919/733-2314 shall be notified
at least twenty-four (24) hours in advance of the backfilling of the installed
subsurface filter system so that an in-place inspection can be made of said
system prior to backfilling. Such notification to the Regional Supervisor shall
be made during the normal office hours from 8:00 A.M. until 5:00 P.M. on Monday
through Friday, excluding State Holidays.
In even the facilities fail to perform satisfactorily in meeting:i,ts NPDES
permit effluent limits, the Permittee shall take such immediate corrective action
as may be required by this Division, including the construction of additional
wastewater treatment and disposal facilities.
Contd.
P.O.Box 27687,Raleigh,North Carolina 27611-7687 Telephone 919-733-4984
An Equal Opportunity/Affirmative Action Employer
-. Per-raft No. NC0058220
Page Two
The sand media of the subsurface filter must comply with the Division's sand
specifications and must be analyzed and approved by this Division either by direct
sampling or by acquisition of filter sand from a dealer who is currently certified
by the Division as an acceptable source.
Septic tank must be pumped once a year and the filters must be rehabilitated
as needed but should be inspected no less than once every three (3) years of operation.
One (1) set of approved plans and specifications is being forwarded to you.
If you have any questions or need additional information, please contact Mr. Donald
Safrit, telephone No. 919/733-5083, ext. 104.
Sincerelypussir
ORie,tiNAL RA,MSEY
DENNtS of
R. Paul Wilms
Director
cc: Durham County Health Department
Duance K. Stewart and Assocites, Inc.
Mr. Dennis R, Ramsey