April 18, 2022
Permittee:
The NPDES Compliance inspection consisted of the following:
Findings during the pre-inspection file review were as follows:
1.
DWR last inspected this facility for NPDES compliance on March 8, 2018.2.
No violations have been reported since the last inspection.3.
Findings during the inspection were as follows:
On Thursday, March 24, 2022, Jason Robinson of the NC Division of Water Resource's Raleigh Regional
Office (RRO) conducted an inspection of the MPLX - Selma Terminal at 2555 W Oak St in Selma. The
purpose of this inspection was to ensure compliance with the subject NPDES Permit. During the
inspection, the presence and cooperation by Bob Jarabeck, Roger Lamberth (ORC) and Felix Jimenz
(bORC) was appreciated.
• Review of the NPDES permit
• Review of the Owner/facility information
• Review of monitoring data
• Review of log book.
• On-site inspection of the treatment facility
The most recent permit that covers the discharge from this facility became effective on July 1, 2018
and expires on March 31, 2023. Please submit a renewal application within 180 days of expiration of
the permit.
Subject: Compliance Evaluation Inspection
MPLX - Selma Terminal
NPDES Permit No. NC0027006
Johnston County
ROY COOPER
Gove! 'W?
ELIZABETH S. BISER
RICHARD E. ROGERS. JR.
Directar
1 £
NORTH CAROLINA
Environmental Quality
Michael Gray
Environmental Compliance Manager/East
migray@marathonpetroleum.com
539 S Main St
Findlay, OH 45840
DocuSign Envelope ID: B9206BFC-C6C7-4B6F-AOI
4.
The facility utilizes a Field Task Maintenance System (FTMS), a program with a checklist of tasks.5.
6.
7.
Section A.(l.) of the permit requires the permittee to monitor discharges at Outfall #001 and submit
monthly Electronic Reporting of Discharge Monitoring Reports (eDMRs):
Staff reviewed the Permit Contact Report generated by NCDWR's Basinwide Information
Management System (BIMS). Several updates were made to the facility contacts.
The treatment facility consists of two oil/water separators (both off-site recycle), an aerated storage
pond with discharge control valve (motor-operated, normally closed) and a v-notch weir and ultra
sonic flow meter.
• Separator #2: Rainwater that collects in the containment area from the Above Ground Storage
Tanks and parking area are routed through oil/water separator #2, along with the water from
Separator #1.
• Aerated Storage Pond: The combined flows from the oil-water separators discharge into the
aerated pond. The pond is constantly aerated. Flow from the pond is measured with an
ultrasonic flow meter as water flows over a v-notch weird to a valve controlled basin. Discharge
occurs when the valve is open. Flow is measured by an ISCO 3010 ultrasonic flow meter. The
meter is calibrated once a year by Clear Water Calibration and was last calibrated on November
11, 2021. The aerator was working during the time of the inspection, and the pond appeared
• Samples are collected at the discharge of the aerated pond.
• Samples are collected and kept on ice and transported to Pace Laboratories by Pace staff or
their courier. Most parameters are analyzed at Pace's Asheville location (Certified Lab #40)
and Huntersville location (Certified Lab #12). Samples for Whole Effluent Toxicity (WET) test
are done at Pace Analytical National Testing Center. Please confirm the Lab Certification #
for this facility. According to the DWR Aquatic Toxicology Branch (ATB), this facility is #9
(not #041, which appears to be the number for the old lab before it was changed to Pace).
• A cursory review was done of bench sheets, chain of custodies and laboratory results since
the last inspection. Lab data was found to be complete with no issues.
• Laboratory results from April and October 2021 were compared to the facility's submitted
eDMRs, and no discrepancies were observed.
• Based on the Division's Basinwide Information System (BIMS), facility staff, and the inspectors
cursory review of laboratory data, no limit/monitoring violations have been reported or
occurred since the last inspection.
• The annual WET (Whole Effluent Toxicity) testing and the semi-annual EPA Method 625
testing were last done on July 14, 2021.
• Flow is measured using an ultrasonic flow meter.
• The inspector confirmed that monitoring data was kept on-site for at least three years.
• The permittee is reminded to include the "Certified Lab #s" on the eDMR reports.
• Separator #1: Stormwater runoff and associated wash water from the loading rack pup manifold,
rack manifold, additive pump off, truck pump off containment area and the vapor recovery unit
containment area flow into oil/water separator #1. This oil/water separator is a 10,0000-gallon
Enquip separator with a design capacity of 400 gallons/minute and is double-walled with an
interstitial probe. A hydrocarbon sensor is in the water compartment to sound an alarm if oil
enters the water compartment. Water that leaves Separator #1 flows to Separator #2.
'^^E24932BBFC
* DocuSigA Envelope ID: B9206BFC-C6C7-4 B8-95E24932BBFC
clean and no sheens were observed.
8. The NPDES Permit authorizes the discharge from the facility to an unnamed tributary of Mill Creek, a
waterbody currently classified WS-IV; NSW within the Neuse River Basin. The discharge point is in the
wooded area outside the fence of the facility, and was not observed.
Attachments
• Compliance Inspection Report
Cc: Raleigh Regional Office and Laserfiche
rjiarabeck@marathonpetroleum.com
rwlamberth@marathonpetroleum.com
asbrown@marathonpetroleum.com
migray@marathonpetroleum.com
Thank you again for your cooperation. If you have any questions regarding the attached reports or any of
the findings, please contact Jason Robinson at Jason.Robinson@ncdenr.gov .
Sincerely,
,------DocuSigned by
., . -B29I6E6AB32144- _Vanessa Manuei, Absisiarii negiuridi Supervisor
Water Quality Regional Operations Section
Raleigh Regional Office
Division of Water Resources, NCDEQ
DocuSign Envelope ID: 219540F4-3016-41E6-9652 FBC1483F
ERA
Section A: National Data System Coding (i.e., PCS)
yr/mo/dayNPDES
3 NC0027006 22/03/24 S
I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I p'>6211
72 i8067
Section B: Facility Data
Entry Time/Date Permit Effective Date
18/05/0101:30PM 22/03/24
Selma Terminal
Exit Time/Date
2555 W Oak St
22/03/2403:00PMSelma NC 275769198
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Roger Lamberth,2555 W Oak St Selma NC Selma NC 27576//919-427-6512/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
9 Operations & Maintenar Records/Reports
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date
DWR/RRO WQ/919-791-4200/4/18/2022
Agency/Office/Phone and Fax Numbers Date
4/18/2022
1Page#
Inspection Work Days
I I
r7j11
| Permit | Flow Measurement
| Effluent/Receiving Wate | Laboratory
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
///
Roger Wayne Lamberth/ORC/919-427-6512/
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Permit Expiration Date
23/03/31
Inspector
19
United States Environmental Protection Agency
Washington. D.C. 20460
Water Compliance Inspection Report
Signature of Management Q A Reviewer
-------DocuSigned by.
_ ------------f;. AUluxlL
-------B2916E6A832144F.
EPa Form 3560-3 (Rev 9-94) Previous editions are obsolete.
N
QA
12L
Fac Type
20U
Facility Self-Monitoring Evaluation Rating
70 u
-----------------------Reserved--------------------
73L±J74 75l I I I I I I I
Jason T Robinson _oocuSl9ned
-----8F93314C1 £8 t4A9 .
Inspection Type
18[cl
Transaction Code
1 In I 2 |5 |
Bl
71u
• DocuSigh Envelope ID: 219540F4-3016-41E -A9A3FBC1483F
1(Cont.)
3l
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Findings during the pre-inspection file review were as follows:
DWR last inspected this facility for NPDES compliance on March 8, 2018.2.
3. No violations have been reported since the last inspection.
Findings during the inspection were as follows:
The facility utilizes a Field Task Maintenance System (FTMS), a program with a checklist of tasks.5.
2
J11
• Separator #2: Rainwater that collects in the containment area from the Above Ground Storage
Page#
NPDES
NC0027006
yr/mo/day
22/03/24
6. Section A.(1.) of the permit requires the permittee to monitor discharges at Outfall #001 and
submit monthly Electronic Reporting of Discharge Monitoring Reports (eDMRs):
• Samples are collected at the discharge of the aerated pond.
• Samples are collected and kept on ice and transported to Pace Laboratories by Pace staff or
their courier. Most parameters are analyzed at Pace's Asheville location (Certified Lab #40) and
Huntersville location (Certified Lab #12). Samples for Whole Effluent Toxicity (WET) test are done at
Pace Analytical National Testing Center. Please confirm the Lab Certification # for this facility.
According to the DWR Aquatic Toxicology Branch (ATB), this facility is #9 (not #041, which appears to
be the number for the old lab before it was changed to Pace).
• A cursory review was done of bench sheets, chain of custodies and laboratory results since the
last inspection. Lab data was found to be complete with no issues.
• Laboratory results from April and October 2021 were compared to the facility’s submitted eDMRs,
and no discrepancies were observed.
• Based on the Division’s Basinwide Information System (BIMS), facility staff, and the inspectors
cursory review of laboratory data, no limit/monitoring violations have been reported or occurred since
the last inspection.
• The annual WET (Whole Effluent Toxicity) testing and the semi-annual EPA Method 625 testing
were last done on July 14, 2021.
• Flow is measured using an ultrasonic flow meter.
• The inspector confirmed that monitoring data was kept on-site for at least three years.
• The permittee is reminded to include the “Certified Lab #s” on the eDMR reports.
• Separator #1: Stormwater runoff and associated wash water from the loading rack pup manifold,
rack manifold, additive pump off, truck pump off containment area and the vapor recovery unit
containment area flow into oil/water separator#!. This oil/water separator is a 10,0000-gallon Enquip
separator with a design capacity of 400 gallons/minute and is double-walled with an interstitial probe.
A hydrocarbon sensor is in the water compartment to sound an alarm if oil enters the water
compartment. Water that leaves Separator #1 flows to Separator #2.
7. The treatment facility consists of two oil/water separators (both off-site recycle), an aerated
storage pond with discharge control valve (motor-operated, normally closed) and a v-notch weir and
ultra-sonic flow meter.
J1712l
1. The most recent permit that covers the discharge from this facility became effective on July 1,
2018 and expires on March 31,2023. Please submit a renewal application within 180 days of
expiration of the permit.
Inspection Type
18[c]
4. Staff reviewed the Permit Contact Report generated by NCDWR’s Basinwide Information
Management System (BIMS). Several updates were made to the facility contacts.
DocuSign Envelope ID: 219540F4-3016-41E6-9652 FBC1483F
3Page#
• Aerated Storage Pond: The combined flows from the oil-water separators discharge into the
aerated pond. The pond is constantly aerated. Flow from the pond is measured with an ultrasonic
flow meter as water flows over a v-notch weird to a valve controlled basin. Discharge occurs when
the valve is open. Flow is measured by an ISCO 3010 ultrasonic flow meter. The meter is calibrated
once a year by Clear Water Calibration and was last calibrated on November 11,2021. The aerator
was working during the time of the inspection, and the pond appeared clean and no sheens were
observed.
8. The NPDES Permit authorizes the discharge from the facility to an unnamed tributary of Mill
Creek, a waterbody currently classified WS-IV; NSW within the Neuse River Basin. The discharge
point is in the wooded area outside the fence of the facility, and was not observed.
Permit: NC0027006 Owner - Facility: Selma Terminal
Inspection Date: 03/24/2022 Inspection Type: Compliance Evaluation
Tanks and parking area are routed through oil/water separator #2, along with the water from
Separator #1.
•DocuSign Envelope ID: 219540F4-3016-41E -A9A3FBC1483F
Permit Yes No NA NE
■
Comment: z
Record Keeping Yes No NA NE
Comment: Add certified lab #s to eDMRs
Operations & Maintenance Yes No NA NE
■ Is the plant generally clean with acceptable housekeeping?
4Page#
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain-of-custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Permit: NC0027006
Inspection Date: 03/24/2022
■
■
■
■
■
■
■
Owner - Facility: Selma Terminal
Inspection Type: Compliance Evaluation
■
■
■
■
■
■
■
■
■
DocuSign Envelope ID: 219540F4-3016-41E6-965 FBC1483F
Operations & Maintenance Yes No NA NE
■
Comment:
Flow Measurement - Influent Yes No NA NE
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment:
5Page#
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
■
■
■
■
Permit: NC0027006
Inspection Date: 03/24/2022
Owner - Facility: Selma Terminal
Inspection Type: Compliance Evaluation