HomeMy WebLinkAboutNC0027006_Historical information_20111231 (3)/7/
May 16, 2011
Subject:
Dear Mr. Rhode:
1.
2.
3.
4.
Ray Rhode, Terminal Manager
Marathon Petroleum Company LP
2555 West Oak Street
Selma, North Carolina 27576
Beverly Eaves Perdue
Governor
The BIMS computer currently lists the classification of the subject facility as a Physical Chemical
1 (PC-1) facility. You are currently listed as the Operator in Responsible Charge (ORC) Physical
Chemical - 1 (PC-1). You stated that Terry Swick, PC-1 certified, is listed as your back-up ORC.
A permit name change from Marathon Petroleum Company LLC - Selma to Marathon
Petroleum Company LP was approved October 05, 2010. The permit will expire on March 31,
2013. Permit renewal must be received 180 days prior to permit expiration date.
The treatment facility consists of two oil/water separators in series with an aerated storage pond.
The ethanol truck off-loading facility that was installed in 2008 has been converted to a rail off
loading facility. Stormwater runoff and associated wash water from the loading rack pump
manifold, rack manifold, additive pump off, truck pump off containment area and the vapor
recovery unit containment area flow into oil/water separator #1. This oil/water separator is a
10,000-gallon Enquip separator with a design capacity of 400 gallons/minute and is double
walled with an interstitial probe. A hydrocarbon sensor is located in the water compartment to
sound an alarm if oil enters the water compartment. Rainwater that collects in the containment
area for the Above Ground Storage Tanks (AST’s) and parking area are routed through oil/water
separator #2. The combined flows from the oil/water separators discharge into the aerated
pond. Flow from the pond is measured with an ultrasonic flow meter as water flows over a v-
notch weir to a valve-controlled basin. Discharge occurs when the valve is open. At the time of
inspection, one aerator was not in operation. A new motor and aerator housing is on site and
will be installed within the month. Water in the pond appeared clear with no sheen detected.
There was no discharge.
Raleigh Regional Office
1628 Mail Service Center
3800 Barrett Drive
Phone (919) 791-4200
FAX (919) 788-7159
Dee Freeman
Secretary
Compliance Evaluation Inspection
Marathon Petroleum Company L.P. Selma Terminal
NPDES Permit NC0027006
Johnston County
NCDENR
North Carolina Department of Environment and Natural Resources
Division of Water Quality
Coleen H. Sullins
Director
Customer Service
877-623-6748
NorthCarolinaNaturally
I, Mitch Hayes, performed the subject inspection on May 09, 2011. Your assistance with this
inspection was greatly appreciated. Please find attached with this letter the Basin Wide Information
Management System (BIMS) checklist. Below is a list of findings and recommendations developed from
the inspection.
Surface Water Protection
Raleigh, NC 27699-1628
Raleigh, NC 27609
An Equal Opportunity/Affirmative Action Employer - 50% Recycled/10% Post Consumer Paper
Discharge Monitoring Reports (DMR’s) for the period April 2007 through January 2011 were
reviewed for compliance with permit limit and monitoring requirements. There are no violations
listed for the period.
North Carolina Division of Water Quality
Internet: www ncwaterquality org
Location'
5.
6.The ultra sonic flow meter was last calibrated August 05, 2010 by Johnson Controls.
Cc: Permit files, Central files
I would like to thank you for your assistance with this inspection. If you have any questions about this
report or the inspection, please contact me at 919.791.4261.
Marathon Petroleum LP CEI
Page 2
Commercial lab results, chain of custody records, and bench sheets were compared with data
submitted on the DMR for January 2011. No discrepancies were noted. All toxicity results were
recorded as 'Pass”. All permit parameters, except toxicity, are analyzed by Test America in
Nashville, TN. Advent Environ in Brentwood TN analyzes toxicity.
Mitch Hayes
Environmental Specialist
Sincerely,
EPA
NPDES
12lNCC027006
Entry Time/Date Permit Effective Date
08/05/0111/05/0901:05 PMSelma Terminal
Exit Time/Date Permit Expiration Date2555 W Oak St
Selma NC 275769198 13/03/3111/05/0902:00 PM
Other Facility Data
Raymond Oliver Rhode//919-965 3201 /
Raymond Oliver Rhode/ORC/919- 965-3201/
Name, Address of Responsible Official/Title/Phone and Fax Number
William Greg Moore,539 S Main St Findlay OH 45840//419 421 3774/
Permit Records/Reports Self-Monitoring Program
Facility Site Review
(See attachment summary)
Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date
RRO WQ//919-791 4200/
Sh
I
Page #1
3l
Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
United States Environmental Protection Agency
Washington, D C. 20460
yr/mo/day
11/05/09
Contacted
No
QA
72|nJ
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Date
///^y/z '
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
J11
Facility Self-Monitoring Evaluation Rating
70 EJ
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
fl Flow Measurement
Fac Type
20U
Mitchell S Hayes
latur^of Management Q A Reviewer , / Agency/Office/Phone and Fax Numbers
EPA Form 356X-3 (Rev 9-94) Previous editions are obsolete
Inspection Type
18U
Inspector
19EJ
73LU
Inspection Work Days
671| 69
Water Compliance Inspection Report
Section A National Data System Coding (i.e., PCS)
Bl71 u_
_____________________________________________________Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
J17
Remarks
21l I I I I I I I I I I I I I I I I I I I I I III I I I I I I I I I I I I I I I I I I I I I I66
y / 3, 3LO I I
-------------Reserved------------------------
74 75| I I I I I I I80
<2 X
Transaction Code
1 |_N| 2 [2]
Permit Yes No NA NE
O ■ 0
■ O O
# Are there any special conditions for the permit?■ o o
Is access to the plant site restricted to the general public?■ 0
■ 000
Permit expires 03.31.2013
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit?■ non
Is all required information readily available, complete and current?■ ODD
Are all records maintained for 3 years (lab. reg. required 5 years)?■ DOO
Are analytical results consistent with data reported on DMRs?■ n n o
Is the chain-of-custody complete?■ O
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters'?■ 000
Has the facility submitted its annual compliance report to users and DWQ? □■0
0010
■ ODD
Is the ORC certified at grade equal to or higher than the facility classification?■ O 0
Is the backup operator certified at one grade less or greater than the facility classification?■ ODD
Is a copy of the current NPDES permit available on site?■ 000
Facility has copy of previous year's Annual Report on file for review?n o ■ o
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained?■ ODD
Page #3
Comment: .
TN. Advent Environ
(If the present permit expires in 6 months or less). Has the permittee submitted a new application?
Is the facility as described in the permit?
Permit: NC0027006
Inspection Date: 05/09/2011
Owner - Facility: Selma Terminal
Inspection Type: Compliance Evaluation
(If the facility is - or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator on each shift?
Is the ORC visitation log available and current?
Is the inspector granted access to all areas for inspection?
Comment:
All parameters except toxicity are analyzed by Test America in Nashville
i.T.'Tcn in Brentwood TN analyzes toxicity.