HomeMy WebLinkAboutNCG550238_Compliance Evaluation Inspection_20170403 ROY COOPER
" - ="` Governor
S. JAY ZIMMERMA-N
Director
Water Resources
ENVIRONMENTAL QUALITY
April 3, 2017
RECEIVEDINCDEQIDWR
MR.DENNIS HOBBS
5444 IRONWOOD LANE APR 0 5 2017
RALEIGH,NORTH CAROLINA 27613 WaP
iiy
atil Ss�eg®rl
Subject: Compliance Evaluation Inspection
Hobbs SFR NPDES Wastewater System
COC No.NCG550238
Wake County
Dear Mr. Hobbs:
On March 23, 2017 Cory Larsen,PE from Wake County Department of Environmental Services
visited your single-family residence (SFR) wastewater treatment system to evaluate compliance
with the above permit to discharge wastewater. The checked boxes below show what conditions
were noted at your facility (also refer to the attached inspection report):
Treatment tablets are wrong kind: You are responsible for always having chlorine
tablets in place. They must be the kind for wastewater treatment(active ingredient 70%
calcium hypochlorite) and not for swimming pools.
Pumping the septic tank: Your septic tank requires immediate pump out and should
be pumped out every 3 to 5 years going forward. A pumping company can check the
status periodically and determine when pumping is required.
® Failure to analyze the effluent: The effluent that is discharged from your system
must be analyzed once each year. See Part I(A) of your permit about his requirement. A
list of NC certified laboratories that provide this service can be found at DEQ's
Laboratory Certification Branch webpage. Please locate your outfall pipe, make
arrangements for sampling to be carried out within the next 3 months,.and submit results
to this office within 3 weeks after the sampling has been done.
If you have questions or comments about this inspection or the requirements to take corrective
action, please contact Cory Larsen, PE at 919-480-9998 or me at 919-791-4200.
Division of Water Resources,Raleigh Regional Office,Water Quality Operations Section http://portal.ncdenr.org/web/wq/aps
1628 Mail Service Center,Raleigh,NC 27699-1628 Phone:(919)791-4200
Location: 3800 Barrett Drive,Raleigh,NC 27609 Fax:(919)788-7159
NCG550238
March 27,2017
Page I 2
0 mc ely,
apiiy - .
Danny Smi(h, Supervisor
Water Quality Regional Operations
Raleigh Regional Office
., .
cc: Wake County Department of Environmental Services File
1 _4.01:502le
1
United States Environmental Protection Agency
Form Approved.
E PA Washington,D.C.20460 OMB No.2040-0057
Water Compliance Inspection Report Approval expires 8-31-98
Section A:National Data System Coding(i.e.,PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN I 2 3 1 NCG550238 111 12 1 17/03/23 117 18 19 I c 201 I
211I I I lul I I I I I I I I I I I I I I I I I I I I 1 1 1 1 1 1 1 1 111 1 1 1 1 1 r6
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 • QA Reserved -
671 701 Li I 71 I 72 �, 731 I 174 751 I I 1 1 1 1 180
Section B:Facility Data
LJ
Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date
POTW name and NPDES permit Number) 09:30AM 17/03/23 13/08/01
5444 Ironwood Lane
5444 Ironwood Ln • Exit Time/Date Permit Expiration Date
Raleigh NC 27609 10:45AM 17/03/23 18/07/31
Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data
///
Name,Address of Responsible Official/Title/Phone and Fax Number
Contacted
C Dennis Hobbs,5444 Ironwood Ln Raleigh NC 276 0 9//9 1 9-7 8 7-3 3 1 4/
• No
Section C:Areas Evaluated During Inspection(Check only those areas evaluated)
NI Permit 1.1 Operations&Maintenance El Effluent/Receiving Waters
Section D:Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s)and Signature(s)of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Cory Larsen RRO WQ//919-856-7443/
(gnat e of Manageme Q A eviewer Agency/Office/Phone and Fax Numbers Date
k_YA/i9) (91i V/-1709
EPA Form 35 -3(Rev 9-94)Previous editions are obsolete.
Page# 1
ti
NP DES yr/mo/day Inspection Type (Cont.) 1
31 NCG550238 Ill 121 17/03/23 17 18 Li
Section D:Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
Wake County Department of Environmental Services staff, on behalf of the Division of Water
Resources, performed a compliance evaluation inspection of the subject Single-Family Residence
Wastewater Discharge System on March 23, 2017. The following observations were made during the
inspection:
1. The septic tank must be pumped immediately to prevent a discharge of untreated waste from the
tank riser lid. It was last performed in 2011.
2. No visible signs of malfunction (breakout, seepage, etc)were observed in the area of the
subsurface sand filter.
3. The chlorinator was stocked with pool type disinfection tablets and should be switched out for
calcium hypochlorite wastewater disinfection tablets.
4. Effluent was observed in the chlorine contact chamber but it was well below the invert elevation of
the outlet pipe,thus no active discharge.
5. Effluent monitoring has not been performed recently but based on previous inspection records the
system does not regularly discharge effluent.
Page# 2
Permit: NCG550238 Owner-Facility: 5444 Ironwood Lane
Inspection Date: 03/23/2017 Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • 0 0 0
Does the facility analyze process control parameters,for ex: MLSS, MCRT,Settleable ❑ ❑ • 0
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new 0 0 • 0
application?
Is the facility as described in the permit? 0 0 • 0
#Are there any special conditions for the permit? 0 0 •
Is access to the plant site restricted to the general public? • 0 0 0
Is the inspector granted access to all areas for inspection? • ❑ 0 0
Comment: Certificate of Coverage is current.
Effluent Pipe • Yes No NA NE
Is right of way to the outfall properly maintained? • 0 0 0
Are the receiving water free of foam other than trace amounts and other debris? 0 0 IN 0
If effluent (diffuser pipes are required) are they operating properly? 0 0
II 1=1
Comment: Outlet pipe could not be located-must clear leaf litter. •
Septic Tank Yes No NA NE
(If pumps are used)Is an audible and visual alarm operational? 0 0 • 0
Is septic tank pumped on a schedule? ❑ • 0 0
Are pumps or syphons operating properly? 0 0 • 0
Are high and low water alarms operating properly? 0 0 • 0
Comment: Septic tank last pumped in 2011 and in immediate need of pumping to prevent discharge out
of riser.
Sand Filters (Low rate) Yes No NA NE
(If pumps are used) Is an audible and visible alarm Present and operational? 0 0 • 0
Is the distribution box level and watertight? 0 0 I 0
Is sand filter free of ponding? • 0 0 0
Is the sand filter effluent re-circulated at a valid ratio? 0 ❑ III 0
#Is the sand filter surface free of algae or excessive vegetation? 0 0 0 U
Page# 3
1
Permit: NCG550238 Owner-Facility: 5444 Ironwood Lane
Inspection Date: 03/23/2017 Inspection Type: Compliance Evaluation
Sand Filters (Low rate) Yes No NA NE
#Is the sand filter effluent re-circulated at a valid ratio?(Approximately 3 to 1) ❑ ❑ • ❑
Comment: No visible signs of seepage downslope of filter area.
Disinfection-Tablet Yes No NA NE
Are tablet chlorinators operational? • ❑ ❑ ❑
Are the tablets the proper size and type? ❑ • ❑ ❑
Number of tubes in use? 2
Is the level of chlorine residual acceptable? ❑ ❑ ❑ •
Is the contact chamber free of growth, or sludge buildup? MI ❑ ❑ ❑
Is there chlorine residual prior to de-chlorination? ❑ ❑ • ❑
Comment: Chlorinator tubes were both stocked with tablets and checked to ensure contact with
effluent.They were pool tablets, not wastewater disinfection tablets however.
Page# 4