Loading...
HomeMy WebLinkAboutNC0026051_Historical information_20051231Michael F. Easley, Governor February 14, 2005 SUBJECT: Wastewater/Groundwater Laboratory Certification Dear Mr. Battle: Thank you for your time and cooperation. I can be contacted at (919) 733-3908 (extension 272), if you have questions. Sincerely, An Equal Opportunity/Affirmative Action Employer - 50% Recycled/10% Post Consumer Paper Review your last inspection report (Inspection date: January 30, 2004), to assure that all cited items have been corrected; otherwise, enforcement action may be recommended. We have scheduled an on-site inspection of your field operation for approximately 9:00 a.m., March 1, 2005. The scope of the inspection will include all methods marked on Attachment I of the field operations current North Carolina Wastewater /Groundwater Certificate and /or marked on the application for NC Wastewater/Groundwater Laboratory Certification. A copy of the current Attachment I is enclosed for your reference. The purpose of the inspection will be to verify documented quality control/quality assurance procedures and adequacy in meeting the requirements of 15A NCAC 2H .0800. The data review portion of the inspection will require complete data packets including all of the supporting documentation for data analysis. This requires, but is not limited to: copies of final reports, instrument run logs, bench sheets, standard preparation logs, reagent preparation logs, calibration curves and sample receipt/chain of custody forms. These data sets will be used to assess the quality of your data during the inspection. Any parameters for which there is no North Carolina data to review, general examples of samples analyzed by the certified methods will be reviewed along with any documented allowances in the laboratory's quality system to meet North Carolina program specific requirements. Please have available all field meters and calibration standards at this time. cc: James Meyer Raleigh Regional Office •Edith Henderson Laboratory Section William G. Ross Jr., Secretary North Carolina Department of Environment and Natural Resources Alan W. Klimek, P.E. Director Division of Water Quality Laboratory Section 1623 Mail Sendee Center; Raleigh, NC 27699-1623 4405 Reedy Creek Road; Raleigh, NC 27607 Phone (919) 733-3908 /FAX (919) 733-2496 / Internet: www.dwqlab.org 5108 Mr. Tyrone Battle Woodard & Curran - Triangle WWTF 5926 NC Hwy. 55 East Durham, NC 27713- dujct North Carolina Naturally 4 March 31, 2005 M&C 01471-0003 (40/60) GV. Dear Mr. Schuster: If you have any questions, please let me know. Sincerely, Enclosure cc: S:\1471 \0003\40\03315Schuster.DOC 200 MacKenan Court, Cary, North Carolina 2751 1 Tel 919.233.8091 Fax 919.233.8031 www.mckimcreed.com AA0002467 Mr. Ken Schuster NCDENR Raleigh Regional Office 1628 Mail Service Center Raleigh, NC 27699-2628 Bob Carter, Durham County Project Manager Chuck Hill, PE, Durham County Utility Division Manager Tom Belnick, NCDENR NPDES Unit Kevin Eberle, PE, McKim & Creed McKim & Creed will issue partial substantial completions as each train has been made ready to come on line. At this time, it is anticipated that only two BNR trains will be placed into service at a capacity of 8 MGD ADE. We understand that neither the Regional Office nor the NPDES Unit of NCDENR will issue any written approval or acknowledgement of the plant startup. Bry^X?- Blake, PE Senior Project Manager Per the Authorization to Construct and on behalf of Durham County, McKim & Creed is notifying you of the County's intent to place into service the new process facilities tentatively on April 6,h or 7th. Based on our conversation on March 30, 2005, please find attached the draft start-up plan dated February 17, 2005 for the new process facilities. As discussed, the County is planning to phase in one new BNR train at a time. This will allow the existing plant to stay on line as the first BNR train is stabilized. After the first train is stabilized, the second train will be brought on line. As this is being accomplished, the existing plant will start to be taken off line. Ur :KRE: Triangle Wastewater Treatment Plant Phase II Expansion ATC No. 026051A01 NPDES Permit No. NC0026051 1. 2. 3. 4. 5. 6. 7. 1C:\Documents and Settings\BBIake\Local SettingsVTemporary Internet Files\OLK3\02175Plan.doc Woodward & Curran to check and confirm that all chemical bulk storage tanks have sufficient supply of chemicals. The State (Regional Office) shall be notified when Loving starts to fill the BNR trains for leak testing as just about all plant effluent flow will be diverted to fill the BNR trains. Woodward & Curran to notify the State. The appropriate RAS/WAS pump on the south side of the new RAS/WAS pump station shall transfer flow into the new Influent Flow and RAS Distribution Box. RAS flow shall be measured by the new RAS flow meter. See Sheets C-10 and C-12. Kruger to lock out WAS Pump No. 2 and RAS Pump No. 3 in their control logic to prevent them from starting during the sludge seeding operation. The appropriate weir shall be set to allow RAS/WAS flow to enter the desired BNR Train. The other two weirs shall be raised to isolate the remaining two BNR Trains. Weirs to be set by Loving. RAS and/or WAS will be pumped via the existing RAS or .WAS pumps and an interconnection between the existing WAS waste line and the new WAS waste line. See Sheet C-8. Operation of existing RAS/WAS pumps by Woodward & Curran. TRIANGLE WWTP PHASE II START-UP PLAN FEBRUARY 17, 2005 Forward flow shall enter the desired BNR Train by pumping. Two suction lift pumps each capable of pumping 700 GPM to 2700 GPM shall be set on top of the Influent Flow and RAS Distribution Box. The discharge of the pumps shall be metered with local read The new WAS meter vault shall be valved so as to pass flow through the by-pass line around the meter vault. The WAS shall enter the new RAS/WAS wetwell by isolating and removing one of the new RAS/WAS pumps on the north side of the station. The corresponding check valve shall be blocked open to allow flow to enter the wetwell through the pump discharge piping. See Sheets C-8, C-24, and D-3A. Loving to remove RAS Pump No. 3 and block the check valve open. Loving to close the plug valve in the discharge header between RAS Pump No. 3 and No. 4. *** REVISED DRAFT *** The start-up plan is based on all process facilities being completed, leak tested, electrical checked out, SCADA checked out and ready to be placed into service. The plan is also based on transferring RAS and/or WAS from the existing clarifiers to seed the one new BNR Train. • potassium hydroxide (supplied by Woodward & Curran) • sodium aluminate (supplied by Woodward & Curran) « polymer (supplied by Woodward & Curran, see Item 16) ® methanol (supplied by Loving , see Item 1.6, Page 11501-2) • sodium hypochlorite (supplied by Woodward & Curran) The chemical bulk storage tanks shall be checked to confirm that a sufficient supply of the following chemicals are present: 8. 9. 10. 11. 12. 2S:\1471\0003\60\02175Plan doc The existing plant process train shall remain on line at all times. The existing 30” sluice gate at the grit structure effluent box shall remain open such that forward flow not pumped into the BNR basin shall continue to feed the existing aeration basins. out of GPM and total flow. Pumps to be furnished and setup by Loving. Woodward & Curran to maintain operation of the pumps. Begin seeding system with sludge approximately 24 to 48 hours prior to starting influent flow: Woodward & Curran to operate existing RAS/WAS pumps to provide seed sludge. It is desirable to have seeded the new oxidation ditch with at least 300 to 500 mg/l of MLSS from the existing system before starting influent flow. If it is possible to have more than this, so much the better, however, Kruger does not recommend adding seed sludge more than 48 hours in advance of adding influent. If possible, allow the MLSS in the existing system to increase several days prior to anticipated startup to 20 or 30 % above your normal target level. Then waste the excess sludge to the new ditch over first two to four days of seeding. The amount of sludge needed for a desirable start-up MLSS level of 300-500 mg/l may be estimated as following: For example, assuming the concentration of the RAS/WAS flow is about 8,000 mg/l approximately 170,000 gallons would be required to raise the MLSS level in the new ditch to 300 mg/l. Seeding the new ditch with RAS/WAS from the existing system should continue for several days following introduction of influent until the MLSS reaches between 1000 Where X is the target MLSS level in the new ditch and the total basin volume for the new ditch inclusive of ditch, anaerobic and anoxic zones is about 4.5 MG Volume of Seed Sludge, MG = (X mg/l) x Total Basin Volume(MG) MLSSinRASor WAS The Contractor shall leak test each BNR Train one at a time with plant effluent. The testing water can be pumped from one train to the next such that the desired BNR Train to be placed into service first receives the test water last. Leak testing is to be completed prior to transferring RAS/WAS flow into BNR. Leak testing by Loving. The mixers and weirs should be placed into local or manual control. Raise the ditch effluent weirs approximately 3 inches above lowest position and set secondary anoxic effluent weirs at lowest position. Turn on all mixers. Kruger/Loving to set weirs and place mixers into operation. After leak testing has been successfully completed, the desired BNR Train to be placed into service shall have a plant effluent water level in the anaerobic, anoxic zones and oxidation ditch that reaches the edges of rotors blades (0” rotor submergence). Rotor blade submergence can be checked physically or read from the PLC. Loving to provide the effluent water and confirm level. 13. 14. 15. 16. 17. 18. 19. 3S:\1471\0003\60\02175Plan.doc Once RAS/WAS flow from the existing clarifiers is not required, then the pumps in the new RAS/WWAS Pump Station shall be reset and valves adjusted to allow wasting of sludge from the new process. Loving to reset RAS Pump No. 3, reset check valve and discharge header valves for normal operation. Kruger to “unlock” RAS Pump No. 3 and WAS Pump No. 2 in control logic to allow normal operation. Once flow is entering the secondary clarifier, the RAS pumps should be switched on and the RAS should be adjusted to 100% of the influent flow. It is not necessary to establish a sludge blanket during startup, rather keep the RAS rate high to ensure most of the MLSS solids reside in the aeration basins where there is food and oxygen available for growth rather than the clarifier. Control of RAS pumping shall be set by Kruger in the control logic for start-up. Implement automatic level control at PLC or SCADA and set rotor submergence at 8 inches. Woodward & Curran to set automatic level control. and 1500 mg/l. At that point, it will be best to let solids accumulate through new biological growth in the system. Woodward & Curran to provide for testing of sludge to ensure the desired MLSS levels. Once the influent flow has raised the water level in the ditch so that the rotor submergence > 4”, turn on the rotors. If automatic D.O. control is functioning, the DO set point should be 2.5 mg/l. It will be decreased to 1.3 mg/l when the MLSS reaches target levels, the major criteria for achieving a stabilized system, before reducing the D.O. set point. Loving/Kruger to place rotors into operation. One of the new clarifiers shall be placed into service with the other three off-line. The clarifier will be empty and allowed to fill with forward flow from the BNR Train. Woodward & Curran shall have their chemical supplier jar testing the MLSS entering the clarifier to determine the proper polymer. McKim & Creed would anticipate the use of a cationic polymer. Once the correct polymer is identified, the polymer shall be supplied at the proper dosage to the forward flow entering the clarifier. The first clarifier shall continue to fill and allowed to stabilize establishing the sludge blanket after the BNR Train has stabilized (see Item 22). As the forward flow is increased to the first BNR Train, a second clarifier can be brought on line if needed. The two remaining off-line clarifiers shall serve as storage basins if there is an upset of the BNR Train. Flow can be diverted into the off-line clarifiers by weir adjustment at the Clarifier Distribution Box. See Sheet C-21. Woodward & Curran is to bring on-line the second clarifier as needed. Monitor MLSS in the oxidation ditch at least once per day (maybe more often) during seeding. The initial influent flow rate may be estimated as following using the aerobic F:M as the basis for controlling flow volume. Woodward & Curran to provide for monitoring of MLSS levels. Do not turn on the internal recycle pumps until it is verified that the new ditch is fully nitrifying as evidenced by low ammonia (< 1 mg/l) and a corresponding increase in nitrate (> 5 to 10 mg/l) in the BNR effluent (see Item 20). Woodward & Curran to provide testing to ensure ammonia and nitrate levels. Table 1. Recommended flow, MLSS and F:M ratio during Start-up 1.0to 1.2 600 to 700 0.14 1.5 to 1.7 0.12 2.0 to 2.2 0.10 2.3 to 2.5 0.09 3.0 to 3.2 0.09 3.5 to 4 MGD 0.09 4S:\1471 \0003\60\02175Plan.doc An aerobic F:M ratio about 0.15 to 0.2 is initially desired in order to accelerate sludge build-up during start-up. The following table shows the estimation of influent flow vs. MLSS assuming an influent BOD of about 150 mg/l on average and a ditch volume of about 3 MG. Continue seeding until MLSS reaches target levels (about 3,000-4,000 mg/l). NOTE: The aerobic F:M is estimated using the ditch volume only and does not include the volume of the anaerobic zones, the anoxic zones, or solids in the clarifier. Influent Flow, MGD 0.5 to 0.7 Influent flow, MGD = (t7: M) x 0.7 * MLSS(mg/l) x Ditch Volume(MG) Infuent BOD(mgZl) 900 to 1,100 1.400 to 1,600 1,900 to 2,200 2.400 to 2,600 3,000 to 3,300 MLSS, mg/l 300 to 400 Approximate F:M 0.17 The values in Table 1 assume the wastewater temperature is 12 to 15 °C and an influent BOD of approximately 150 mg/l. The values in this table should be considered approximate. Decrease influent flow if effluent ammonias rise above 2 mg/l or effluent BOD rises above 15 mg/l., the influent BOD increases significantly, or the MLSS tejmperature in the oxidation ditch fails below 10 to 11 °C. A recommended monitoring schedule for process startup is listed in Table 2. As an absolute minimum, the ditches should be monitored for MLSS and ammonia and the clarifier effluent composite analyzed for ammonia. Kruger assumes that plant, staff has the capability onsite to monitor ammonia and MLSS daily. Once the ditch is stabilized, the frequency of monitoring can be reduced. Table 2. Recommended Monitoring Schedule during Process Start-up Influent WAS/RAS W DC DC W DG DG DG Once/day 20. 21. 22. 5S:\1471\0003\60\02175Plan doc It may be desirable to begin wasting some sludge from the new system once the MLSS reaches about 1,500 mg/l to 2,000 mg/l or 15-20 days after seeding, whichever comes first. The volume of waste sludge can be estimated based on a SRT of 15-20 days and should be less than net growth of activated sludge in oxidation ditches to allow continued accumulation of solids. Kruger will advise during startup on when to begin wasting and how much to waste. Daily Composite Sample Daily Grab Sample Weekly (twice/week) DC W DG DG DG W DC Oxidation Ditches Secondary Clarifier Effluent DC W DC: DG: W: Twice/day DG Organic CBOD5 - total Solids TSS VSS TKN NH4-N NO3-N Operational Indicators pH Alkalinity Temperature At MLSS of about 2000 mg/l, adjust RAS flow to maintain a 1-2 ft sludge blanket depth in secondary clarifiers. The sludge blanket should be checked at approximately the same time each day in the same location in the clarifier. Woodward & Curran to make adjustment to RAS pumps and provide for checking of sludge blankets. Mixed Liquor Settled Sludge Volume (5,30,60 Min) Once nitrification is stabilized, as evidence by effluent ammonias < 1 mg/ and a rise in effluent nitrates, the internal recycle pumps can be started. The pumps should be set to return about 100 to 150% of the influent flow rate. Woodward & Curran to start internal recycle pumps. 23. 24. 25. 26. 6S:\1471\0003\60\02175Plan.doc As forward flow leaves the first clarifier, one new filter shall be placed into service. Influent sluice gates for four filters shall be shut and one sluice gate shall be open for the filter to be placed into service. See Sheet C-25. Woodward & Curran shall set the sluice gates and place the one filter into service. When the second BNR Train is placed into service and all forward flow has been diverted from the existing plant into the new BNR process trains, a second filter shall be placed into service. After approximately four weeks of operation, begin monitoring the ortho-phosphate in the selector and the total phosphate concentration in the influent about twice per week to detect onset of biological phosphorus removal. Chemical addition (sodium aluminate) will probably be required into the oxidation ditches, particularly during startup if phosphorus limits must be met. Woodward & Curran to provide for monitoring the ortho-phosphate level. After the first BNR Train has stabilized, the second BNR Train will be started up. The startup process shall be as outlined above except seed sludge shall be provided from the new clarifiers and will not be required from the existing clarifiers. The 30” sluice gate at the grit structure effluent box shall be closed allowing all forward flow to enter the two BNR Trains. This will eliminate the need for the temporary pumps (Item 5) as the forward flow will be gravity flow. Once the 30” sluice gate is closed, the existing plant can be allowed to go off-line. Once the existing plant is off-line, the effluent pump station can be shut down and the 30” sluice gate at the UV structure influent box can be closed. See Sheet C-17 of the Phase I plans. Woodward & Curran to place the existing plant off-line and close the appropriate sluice gates. BOD removal should begin to occur immediately if seeding is adequate and the influent flow is not increased too rapidly. Nitrification should also follow rapidly again if the F:M ratio does not get too high. During the first couple of days of startup, there will be a considerable dilution effect to offset any delay in onset of nitrification. Sufficient MLSS must be accumulated to see good nitrogen removal and this may require several weeks. Kruger would recommend holding off on methanol addition until solids are at target levels and effluent TN levels have stabilized. Biological phosphorus will require significantly more time and will be very much dependant on the presence of soluble BOD in the influent. If the soluble BOD is present, biological phosphorus removal should begin to take place within 6-10 weeks after initial startup and steadily improve thereafter if the system is suitably loaded. The onset of biological phosphorus removal is detected by monitoring the ortho-phosphate concentration in the last stage of the anaerobic selector. Typically, it will be 3 to 5 times the ortho-phosphate concentration in the Once the MLSS concentration is between 2,500 and 3000 mg/l and nitrification is stabilized, the RAS Bleed to the second anoxic stage may be started. The RAS bleed should be incrementally increased daily until the MLSS in the Secondary Anoxic zone is approximately 800 to 1000 mg/l higher than in the oxidation ditches. During this adjustment period lasting a few days, collect a sample of MLSS for solids measurement from the secondary anoxic zone in addition to the sample collected in the oxidation ditch. Typically the RAS bleed rate will be between 20 and 30 percent of the RAS flow rate and the target MLSS in the secondary anoxic should be about 700 to 1000 mg/l higher than in the oxidation ditch upstream. Once the RAS bleed is set, sampling in the secondary anoxic zone can be reduced to once per week. Lower the DO set point in the oxidation ditch to 1.3 mg/l. Woodward & Curran to make the RAS bleed adjustment and provide fortesting MLSS levels. 7S :\ 1471 \0003\60\02175Plan.doc influent if the release/uptake cycle is established. After approximately four weeks of operation, begin monitoring the ortho-phosphate in the selector and the total phosphate concentration in the influent about twice per week. The County has agreed for Woodward & Curran to provide a designated start-up coordinator. Woodward & Curran to inform the County of the designated person. Kruger personnel will visit the site the first few days of startup and will always be available for consult. Apt.12. 2005 3:54P No. 5936 P. I d^McKIM&CREED FACSIMILE TRANSMITTAL DESIGNATED RECIPIENT:Ken Schuster FAX NO: 571-4718 DATE: April 12, 2005 SENDER:Bryan F. Blake, PE TIME: NUMBER OF TRANSMISSION PAGES (Including this page):13 PROJECT NUMBER 01471-0003 PROJECT NAME Triangle WWTP-Phase II □ THIS IS YOUR ORIGINAL KI HARD COPY TO FOLLOW COMMENTS:• • IF NOT CORRECTLY RECEIVED OR PAGES FAULTY, PLEASE CALL SENDER AT 919/233-8091 ** REMARKS: S:\OHCOR\Reopelle\Fax\SchuSter.DOC REV.-042795 200 MacKENAN COURT SUITE 200 CARY, N.C. 27511 TEL: (919)233-8091 FAX: (919)-233-8031 ATTENTION THE INFORMATION CONTAINED IN THIS FACSIMILE MESSAGE IS PRIVILEGED AND CONFIDENTIAL INFORMATION INTENDED ONLY FOR THE USE OF THE INDIVIDUAL OR ENTITY NAMED ABOVE. IF THE READER Of THIS MESSAGE IS NOT THE INTENDED RECIPIENT. OR THE EMPLOYEE OF/OR AGENT RESPONSIBLE TO DELIVER IT TO THE INTENDED RECIPIENT, YOU ARE HEREBY NOTIFIED THAT ANY DISSEMINATION, DISTRIBUTION OR COPYING OF THIS COMMUNICATION IS STRICTLY PROHIBITED. IF YOU HAVE RECEIVED THIS COMMUNICATION IN ERROR. PLEASE NOTIFY US BY TELEPHONE AND RETURN THE ORIGINAL MESSAGE TO US AT THE ABOVE ADDRESS VIA THE US. '>OSTAU SERVICE- WE WIU.REIM5UR5E YOU FOR ANY COSTS INCURRED. COMPANY: NCDENR - Raleigh Regional Office XT 70^ P. 2 April 12,2005 M&C 01471-0003 (40/60) RE: Dear Mr. Belnick: If you need additional information, please let me know. Sincerely, McKIM & CREED, P.A. I I.Q /der Enclosures cc: $:\l4n\00C3\4O\Ml25B«lnick.d<x Bryan F. Blake, PE Senior Project Manager Bob Carter, Durham County Chuck Hill, PE, Durham County Ken Schuster, NCDENR Regional Office Kevin Eberle, McKim & Creed, P.A. Mr. Tom Belnick NCDENR NPDES Unit 1617 Mail Service Center Raleigh, NC 27699-1617 200 macKenan Court, cary, North Carolina 27511 TEL 919.233.8091 Fax 919.233.8031 www.mckifficreed.com AA0002647 Triangle Wastewater Treatment Plant Phase II Expansion ATC No. 026051A01 NPDES Permit No. NC0026051 McKim & Creed will process partial certifications for each of the two remaining BNR trains as the contractor achieves substantial completion. Please find attached the Partial Certification for the referenced project as we discussed. The Partial Certification is basically for placing into service one of the five stage biological nutrient removal trains. Train No. 2, with the other process structures as noted. This provides for 4.0 MGD ADF capacity in the new plant. Apt.1 2. 2005 3:No.5 9 36 Also attached is the current start-up plan dated April 12, 2005 for your files. It is now anticipated that the new process trains will be placed into service some time this week. Location: .ONE> > Registration No,11570 te > > > > > Ap r • 12 •_ 2_005 L3 '• 54P^k Caro^M Department EnviWment and Natural Resources Division of Water Quality r8EAL ■ Pi has been 1 wi<x the uafed in completed in substantial conformance with the Authorization to Construct and with the approve^gn' Michael F. Easley, Governor William G. Ross, Jr., Secretary Alan W. Klimek, P.E,„ Director Date APR 11^^^2005 __________________________________j Upon completion of construction and prior to operation of the modified facility. I Division with a certification from a professional engineer certifying that the permits accordance with the NPDES Permit, this Authorization to Construct, and the approve The Certification should be submitted to: f. NCDENR/DWQ, NPDES Unit, 1617 Mail Service Center, Raleigh, North Carolin^^O^- 7 a No.5 9 36 P- 3 NCDENR PARTIAL CERTIFICATION Professional Engineer’s Certification For Construction of Wastewater Treatment Facilities ATC PROJECT NUMBER: 026051API Durham-Triangle WWTP NPDES Permit No. NC0026051 ____BRYAN F. BLAKE_____________________am a duly registered Professional Engineer (please print) ill the State of North Carolina and have been authorized to observe (circle one: fall time) the construction of the subject project for the Permittee; Project: Durham/Triangle WWTP Phase JI Expansion Intersection of Hwy 55 and Alexander Drive Durham County The project consists of: Installation of a new five stage biological nutrient removal system (three treatment trains) including the following: r ..... ...._______z Three 16* x 36* x 18.5’ (79706 gallons) anaerobic selectors Th«&36’ x 67.5’ x 1825’ (331709 gallons) primary anoxic reactors Three-339’ x 36’ x 18’ (1,643,366 gallons) oxidation ditch aerobic reactors Thr-e^36’ x 45.5’ x 17’ (208,315 gallons) second stage anoxic reactors ♦ BNR system flow distribution box ONE ♦ " ONE ♦ ONE ♦ ONE ♦ ONE ♦ Three-15’ x 36’ x 16.5’ (66,656 gallons) reaeration tanks > Secondary clarifier flow distribution Four 110’ diameter x 16’ high secondary clarifiers wetwenUni aCtivated sludge wetwells with two hi8h volume (3,475 gpm) and one low volume (350 gpm) pumps per Retum-actoaiedkludge.PLG~ba$ed-fkw Gontrol pump control system Tertiary filter weir type flow distribution Five train traveling bridge tertiary sand filter with effective sand particle size of 0.55 to 0.65 nun and a unifonnity coefficient (D60/D10) less than or equal to 1.5 > Filter backwash system consisting of one 7.5 hp centrifugal pump per filter train (five pumps total) Sodium Aluminate Chemical feed system with application points located secondary clarifier influent distribution chamber and the tertiary sand filter distribution channel > Polymer feed system with application points located secondary clarifier influent distribution chamber > Sodium hypochlorite feed system with application points located at the tertiary sand filter distribution channel and the reuse water trough at the ultraviolet disinfection unit effluent > Effluent flow metering system consisting of a compound rectangular sharp crested weir and a ultrasonic level sensor > Installation of any appurtenances associated with the referenced modifications I hereby certify that I did regularly observe this project with due care and diligence and that the construction was and specifications. Signature /C No • 5 9 3 6 P. 4 1, 2. 3. 4. 5. 6. 7. 1S:\i471\0003W\04075Plan.<Joc The State (Regional Office) shall be notified when Loving starts to fill the BNR trains for leak testing as just about all plant effluent flow will be diverted to fill the BNR trains. Woodward & Curran to notify the State. RAS and/or WAS will be pumped via the existing RAS or WAS pumps and an interconnection between the existing WAS waste line and the new WAS waste line. See Sheet C-8. Operation of existing RAS/WAS pumps by Woodward & Curran. The appropriate RAS/WAS pump on the north side of the new RAS/WAS pump station shall transfer flow into the new Influent Flow and RAS Distribution Box. RAS flow shall be measured by the new RAS flow meter. See Sheets C-10 and C-12. Kruger to lock out WAS Pump No. 1 and RAS Pump No. 1 in their control logic to prevent them from starting during the sludge seeding operation. (Note: In manual operation, the pumps must be monitored and not allowed to run dry.) The appropriate weir shall be set to allow RAS/WAS flow to enter the desired BNR Train (Train No. 2). The other two weirs shall be raised to isolate the remaining two BNR Trains. Weirs to be set by Loving. Forward flow shall enter the desired BNR Train (Train No. 2) by pumping. Two suction lift pumps each capable of pumping 500 GPM to 2700 GPM shall be set on top of the potassium hydroxide (supplied by Woodward & Curran) sodium aluminate (supplied by Woodward & Curran) polymer (supplied by Woodward & Curran, see Item 16) methanol (supplied by Loving , see Item 1.6, Page 11501-2) sodium hypochlorite (supplied by Woodward & Curran) TRIANGLE WWTP PHASE II START-UP PLAN APRIL 12, 2005 The new WAS meter vault shall be valved so as to pass flow through the by-pass line around the meter vault. The WAS shall enter the new RAS/WAS wetwell by isolating and removing one of the new RAS/WAS pumps on the south side of the station. The corresponding check valve shall be blocked open to allow flow to enter the wetwell through the pump discharge piping. See Sheets C-8, C-24, and D-3A. Loving to remove RAS Pump No. 1 and block the check valve open. Loving to close the plug valve in the discharge header between RAS Pump No. 1 and No. 2 and close the 8” WAS valve in the discharge header at WAS Pump No. 2. APr.12- 2 0 05 3:54P^ The start-up plan is based on all process facilities being completed, leak tested, electrical checked out, and ready to be placed into service. The plan is also based on transferring RAS and/or WAS from the existing clarifiers to seed the one new BNR Train. Woodward & Curran to check and confirm that all chemical bulk storage tanks have sufficient supply of chemicals. The chemical bulk storage tanks shall be checked to confirm that a sufficient supply of the following chemicals are present: No • 5 93 6 P. 5 8. 9. 10. 11. 12. 13. 2S:\147-\0003\50\04076P|on.doe L The BNR train will be started and run manually without the Kruger PLC Control Panel. See the attachment “Manual Operation Train No. 2”. Volume of Seed Sludge, MG = (X mg/1) x Total Basin Volume(MG) MLSS in RAS or WAS Where X is the target MLSS level in the new ditch and the total basin volume for the new ditch inclusive of ditch, anaerobic and anoxic zones is about 4.5 MG After leak testing has been successfully completed, the desired BNR Train (Train No. 2) to be placed into service shall have a plant effluent water level in the anaerobic, anoxic zones and oxidation ditch that reaches the edges of rotors blades (0” rotor submergence). Rotor blade submergence can be checked physically or read from the PLC. Loving to provide the effluent water and confirm level. Begin seeding system with sludge approximately 24 to 48 hours prior to starting influent flow: Woodward & Curran to operate existing RAS/WAS pumps to provide seed sludge. The existing plant process train shall remain on line at all times. The existing 30" sluice gate at the grit structure effluent box shall remain open such that forward flow not pumped into the BNR basin shall continue to feed the existing aeration basins. The mixers and weirs should be placed into local or manual control. Raise the ditch effluent weirs approximately 3 inches above lowest position and set secondary anoxic effluent weirs at lowest position. Turn on all mixers. Kruger/Loving to set weirs and place mixers into operation. The amount of sludge needed for a desirable start-up MLSS level of 300-500 mg/l may be estimated as following: It Is desirable to have seeded the new oxidation ditch with at least 300 to 500 mg/l of MLSS from the existing system before starting influent flow. If it is possible to have more than this, so much the better, however, Kruger does not recommend adding seed sludge more than 48 hours in advance of adding influent. If possible, allow the MLSS in the existing system to increase several days prior to anticipated startup to 20 or 30 % above your normal target level. Then waste the excess sludge to the new ditch over first two to four days of seeding. Apt. 1 2 . 2005 3:5 5P^ Influent Flow and RAS Distribution Box. The discharge of the pumps shall be metered with local read out of GPM and total flow. Pumps to be furnished and setup by Loving. Woodward & Curran to maintain operation of the pumps. (Note: The temporary pumps are manually controlled without floats and must not be allowed to run dry.) The Contractor shall leak test each BNR Train one at a time with plant effluent. The testing water can be pumped from one train to the next such that the desired BNR Train to be placed into service first receives the test water last. Leak testing is to be completed prior to transferring RAS/WAS flow into BNR. Leak testing by Loving. P. 6No • 5936 14. 15. Forward Flow 16. 17. 3S\147l\O0OJi60\O4075Plwi.doc Table 1, Initial Chemical Dosage Recommendations (Durham Only - Not Including Cary Flow) For example, assuming the concentration of the RAS/WAS flow is about 8,000 mg/l approximately 170,000 gallons would be required to raise the MISS level in the new ditch to 300 mg/l. Seeding the new ditch with RAS/WAS from the existing system should continue for several days following introduction of influent until the MLSS reaches between 1000 and 1500 mg/l. At that point, it will be best to let solids accumulate through new biological growth in the system. Woodward & Curran to provide for testing of sludge to ensure the desired MLSS levels. Verify that chemical feed systems are functional and ready for operation (sodium aluminate, potassium hydroxide, and cationic polymer initially and methanol). Methanol will likely be required one or two weeks later, after biological nitrification has been established. Adjust initial feed rates per Table 1 based on actual influent flow rate. Start the appropriate chemical feeds simultaneously with starting influent flow to the BNR. Once RAS/WAS flow from the existing clarifiers is not required, then the pumps in the new RAS/WWAS Pump Station shall be reset and valves adjusted to allow wasting of sludge from the new process. Loving to reset RAS Pump No. 1, reset check valve and discharge header valves for normal operation. Kruger to “unlock0 RAS Pump No. 1 and WAS Pump No. 1 in control logic to allow normal operation. (Note: RAS Pump No, 1 to remain locked out until pump has been replaced.) Do not turn on the internal recycle pumps until it is verified that the new ditch is fully nitrifying as evidenced by low ammonia (< 1 mg/l) and a corresponding increase in nitrate (> 5 to 10 mg/l) in the BNR effluent (see Item 22). Woodward & Curran to provide regular testing to track ammonia and nitrate levels. Once nitrification has been established, start methanol feed at the rate indicated in Table 1 to the second anoxic zone. Chemical____________ Sodium Aluminate______ Potassium Hydroxide Emulsion Cationic Polymer Methanol 1 MOD mg/l 17.2 115.7 ___1_ 3 gal/hr 2.5 ____7 0.04 0.47 2MGD mg/l 17.2 115.7 ___1_ 3 gal/hr 5 ___14 0.08 0.94 gal/hr ___10 '__28 0.16 1.88 Apr-12- 2 0 0 5 3:5 5|^ 3MGD mg/l 17.2 115.7 ___1_ 3 4MGD mg/l 17.2 115.7 __1 3 gal/hr 7.5 __21 0.12 1.41 Once the influent flow has raised the water level in the ditch so that the rotor submergence > 4”, turn on the rotors. If automatic D O. control is functioning, the D.O. set point should be 2.5 mg/l. It will be decreased to 1.3 mg/l when the MLSS reaches target levels, the major criteria for achieving a stabilized system, before reducing the D.O. set point. Loving/Kruger to place rotors into operation. (Note: Automatic D.O. control will not be functioning at start up.) No.5 9 3 6 P. 7 18. 19. 20. 21. 4SAI 471 \0003\80W075Plan.doc Influent flow, MGD = (F: M) x 0.7 * MLSS(mgZl) x Ditch Volume(MG) Infuent B0D(mg /1) Implement automatic level control at PLC or SCADA and set rotor submergence at 8 inches. Woodward & Curran to set automatic level control. The ditch weir shall be manually adjusted at start up in accordance with the attachment. An aerobic F:M ratio about 0.15 to 0.2 is initially desired in order to accelerate sludge build-up during start-up. The following table shows the estimation of influent flow vs. MLSS assuming an influent BOD of about 150 mg/l on average and a ditch volume of about 3 MG. Continue seeding until MLSS reaches target levels (about 3,000-4,000 mg/l). NOTE: The aerobic F:M is estimated using the ditch volume only and does not include the volume of the anaerobic zones, the anoxic zones, or solids in the clarifier. Once flow is entering the secondary clarifier and HAS flow can be discharged from the clarifier, the RAS pumps should be switched on and the RAS should be adjusted to 100% of the influent flow. It is not necessary to establish a sludge blanket during startup, rather keep the RAS rate high to ensure most of the MLSS solids reside in the aeration basins where there is food and oxygen available for growth rather than the clarifier. Control of RAS pumping shall be set by Kruger in the control logic for start-up. (Note: However at start up the RAS pumps shall be manually operated. In manual operation, the pumps must be monitored and not allowed to run dry.) APr.1 2- 2 00 5 3:5 ^ One of the new clarifiers (Clarifier No. 3) shall be placed into service with the other three off-line. The clarifier will be empty and allowed to fill with forward flow from the BNR Train. Start sodium aluminate feed when forward flow is initiated to the clarifier. Woodward & Curran shall have their chemical supplier jar testing the MLSS entering the clarifier to determine the proper polymer. McKim & Creed would anticipate the use of a cationic polymer. Once the correct polymer is identified, the polymer shall be supplied at the recommended dosage to the forward flow entering the clarifier. The first clarifier shall continue to fill and allowed to stabilize establishing the sludge blanket after the BNR Train has stabilized (see Items 19 and 24). As the forward flow is increased to the first BNR Train, a second clarifier (Clarifier No. 2) can be brought on line if needed. The two remaining off-line clarifiers (Clarifier No. 1 and No. 4) shall serve as storage basins if there is an upset of the BNR Train. Flow can be diverted into the off-line clarifiers by weir adjustment at the Clarifier Distribution Box. See Sheet C- 21. Woodward & Curran is to bring on-line the second clarifier as needed. Monitor MLSS in the oxidation ditch at least once per day (maybe more often) during seeding. The initial influent flow rate may be estimated as following using the aerobic F;M as the basis for controlling flow volume. Woodward & Curran to provide for monitoring of MLSS levels. No-5 9 36 P. 8 Table 2. Recommended flow, MLSS and F:M ratio during Start-up 0.09 0.09 5S \1471\0003W7M075Plan OOC A recommended monitoring schedule for process startup is listed in Table 3. As an absolute minimum, the ditches should be monitored for MLSS and ammonia and the clarifier effluent composite analyzed for ammonia. Kruger assumes that plant staff has the capability onsite to monitor ammonia and MLSS daily. Once the ditch is stabilized, the frequency of monitoring can be reduced. 0.10 0.09 Influent Flow, MOD 0.5 to 0.7 1.0 to 1,2 1.5 to 1.7 2.0 to 2.2 2.3 to 2.5 3.0 to 3 2 3.5to4MGD MLSS, mg/l 300 to 400 600 to 700 900 to 1,100 1.400 to 1,600 1,900 to 2,200 2.400 to 2,600 3,000 to 3,300 Approximate F:M 0.17 0.14 0.12 Apr• 12- 20 0 5 3:5 |^ The values in Table 2 assume the wastewater temperature is 12 to IS^C and an influent BOD of approximately 150 mg/l. The values in this table should be considered approximate. Decrease influent flow if effluent ammonias rise above 2 mg/l or effluent BOD rises above 15 mg/l., the influent BOD increases significantly, or the MLSS temperature in the oxidation ditch falls below 10 to 11 °C. No • 5 9 36 P. 9 Table 3. Recommended Monitoring Schedule During BNR Process Start-up DC’DC DC DC W DG DG Once/day 0 DG 22. 23. 24. 25. 6S'\1471\0003«CW407&Plan.dOC It may be desirable to begin wasting some sludge from the new system once the MISS reaches about 1,500 mg/l to 2,000 mg/l or 15-20 days after seeding, whichever comes first. The volume of waste sludge can be estimated based on a SRT of 15-20 days and should be less than net growth of activated sludge in oxidation ditches to allow continued accumulation of solids. Kruger will advise during startup on when to begin wasting and how much to waste. At MLSS of about 2000 mg/l, adjust RAS flow to maintain a 1-2 ft sludge blanket depth in secondary clarifiers. The sludge blanket should be checked at approximately the same time each day in the same location in the clarifier. Woodward & Curran to make adjustment to RAS pumps and provide for checking of sludge blankets. As forward flow leaves the first clarifier, one new filter (Filter No. 1) shall be placed into service. Influent sluice gates for four filters shall be shut and one sluice gate shall be open for the filter to be placed into service. See Sheet C-25. Woodward & Curran DC’ w DC* DC’ DC* O DC’ DG DG DG DG DC DG DG DG DG DC W W w DC O DG OG Oxidation Ditches DG DG Secondary Clarifier Effluent DC DC WAS/ RAS DG DG DG DG (Raw Influent (pre screening) BNR Influent (post screening) Anaerobic Selector (3r<> stage) Twice/day DG DG DG DG DG DC DC DC DC Apr.12- 20 05 Once nitrification is stabilized, as evidence by effluent ammonias < 1 mg/ and a rise in effluent nitrates, the internal recycle pumps can be started. The pumps should be set to return about 100 to 150% of the influent flow rate. Woodward & Curran to start internal recycle pumps. Parameters Organic CBOD5-Total Solids TSS VSS_________ Nitrogen TN TKN NH4-N no3-n_____ Phosphorus TP PO4-P_______ Operational Indicators PH Alkalinity Temperature____ Mixed Liquor Settled Sludge Volume (5,30,60 Min)_________ TP In Mixer Liquor _____________________________________________________ DC: Daily composite sample DC*: Manual daily composite sample minimum of 5 samples taken to correlate with the post screening samples DG: Daily grab sample W: Weekly (twice/week) O; Occasional Apr.12. 2 0 0 5 3:No-5 9 3 6 P. 10 26. 27. 28. 7S:\1471\0003\80\0407SPIan.doe BOD removal should begin to occur immediately if seeding is adequate and the influent flow is not increased too rapidly. Nitrification should also follow rapidly again if the F:M ratio does not get too high. During the first couple of days of startup, there will be a considerable dilution effect to offset any delay in onset of nitrification. Sufficient MISS must be accumulated to see good nitrogen removal and this may require several weeks. Kruger would recommend holding off on methanol addition until solids are at target levels and effluent TN levels have stabilized. After the first BNR Train (Train No. 2) has stabilized, the second BNR Train (Train No. 1) will be started up. The startup process shall be as outlined above except seed sludge shall be provided from the new clarifiers and will not be required from the existing clarifiers. The 30" sluice gate at the grit structure effluent box shall be closed allowing all forward flow to enter the two BNR Trains. This will eliminate the need for the temporary pumps (Item 7) as the forward flow will be gravity flow. Once the 30" sluice gate is closed, the existing plant can be allowed to go off-line. Once the existing plant is off-line, the effluent pump station can be shut down and the 30” sluice gate at the UV structure influent box can be closed. See Sheet C-17 of the Phase I plans. Woodward & Curran to place the existing plant off-line and close the appropriate sluice gates. After approximately four weeks of operation, begin monitoring the ortho-phosphate in the selector and the total phosphate concentration in the influent about twice per week to detect onset of biological phosphorus removal. Chemical addition (sodium aluminate) will probably be required into the clarifiers, particularly during startup if phosphorus limits must be met. Woodward & Curran to provide for monitoring the ortho-phosphate level. shall set the sluice gates and place the one filter into service. When the second BNR Train is placed into service and all forward flow has been diverted from the existing plant into the new BNR process trains, a second filter (Filter No. 2) shall be placed into service. Once the MLSS concentration is between 2,500 and 3000 mg/l and nitrification is stabilized, the RAS Bleed to the second anoxic stage may be started. The RAS bleed should be incrementally increased daily until the MLSS in the Secondary Anoxic zone is approximately 800 to 1000 mg/l higher than in the oxidation ditches. During this adjustment period lasting a few days, collect a sample of MLSS for solids measurement from the secondary anoxic zone in addition to the sample collected in the oxidation ditch. Typically the RAS bleed rate will be between 20 and 30 percent of the RAS flow rate and the target MLSS in the secondary anoxic should be about 700 to 1000 mg/l higher than in the oxidation ditch upstream. Once the RAS bleed is set, sampling in the secondary anoxic zone can be reduced to once per week. Lower the DO set point in the oxidation ditch to 1.3 mg/l. Woodward & Curran to make the RAS bleed adjustment and provide for testing MLSS levels. Biological phosphorus will require significantly more time and will be very much dependant on the presence of soluble BOD in the influent. If the soluble BOD is present, biological phosphorus removal should begin to take place within 6-10 weeks after initial startup and steadily improve thereafter if the system is suitably loaded. The onset of biological phosphorus removal is detected by monitoring the ortho-phosphate concentration in the last stage of the anaerobic selector. Typically, it will be 3 to 5 times the ortho-phosphate concentration in the influent if the release/uptake cycle is established. After approximately four weeks of operation, No.5 93 6 P. 11 8S:\1471 \0003W3\Q4075Plan.doc begin monitoring the ortho-phosphate in the selector and the total phosphate concentration in the influent about twice per week. The County has agreed for Woodward & Curran to provide a designated start-up coordinator. Woodward & Curran to Inform the County of the designated person. Kruger personnel will visit the site the first few days of startup and will always be available for consult. Apr-12- 2 0 0 5 3 ^ P. 12No-5 936 MANUAL OPERATION TRAIN #2 Initial Manual Mode Start-up 0 8.2 8.4 8.5 8.5 8.5 8.0 8.4 8.8 9SAI 471 VOOOaWKMOZSPian.dfje 1.0 12 v 5.0 Ta To 6.0 To "o’ 7.0 44 8.0 48 "o’ 2.0 19 Z5 3.0 15 ~T 4.0 To 15 BEFORE TURN ON ROTORS, MAKE SURE ROTOR SUBMERGENCE 4” Apr.1 2. 2 0 0 5 3:^ • After leak testing, water levels in the ditch should reach the edges of rotor blades. Tum on all mixers • Drop secondary anoxic effluent weir down to the lowest position • Under manual operation mode, adjust weir position according to the flow rates listed in Table 1 The flow rates listed here are the anticipated start-up raw influent plus RAS flow. For example, assume the start-up flow rate of 2.0 MGD and RAS flow of 1.0 MGD, the total influent to the ditch would be 3.0 MGD, then the ditch effluent weir would be raised 2.0 inches from its lowest position. If the total flow rate to the ditch is more than 6.0 MGD, the effluent weir would be in the lowest position. Table 1 Rotor submergence and weir position at different flowrate Flow rate, MGD* Water head over weir, inch Initial weir elevation, inch* Approx, rotor submergence, inch ’ Including RAS flow + Measured from the lowest weir position • Add seeding sludge, and turn on re-aeration blowers. Once rotor submergence > 4”, tum on all rotors. • Pump raw influent to the BNR train when mixed liquor concentrations reach above 500 mg/1. • If necessary, re-adjust the ditch effluent weir position to maintain an optimal rotor submergence of 8.5 inches. • Adjust secondary effluent weir positions so that the water levels (read from water level sensors) in secondary anoxic zones are 3” inches lower than in the ditch. • Once fully nitrification has been established, tum on internal recycle pumps and set flow rate about 100 - 200%of influent flow rate or based on effluent quality. No ■ 59 36 P. 13 Switch from Auto Control Mode to Manual control 10$:\147 t\0003\80\04075PIan.doc Switch mixers, rotors and internal recycle pumps to manual mode. All mixers should be ON Adjust weir position according to Table 1. Please note that the weir positions are determined by the peak flow. For example, if the daily peak flow is 4 MOD and RAS is 3.0 MGD, then the weir will be drop down to the lowest position. Turn on all rotors manually or use the following equations to estimate the number of rotor in operation. Adjust secondary effluent weir positions so that the water levels (read from water level sensors) in secondary anoxic zones are 3” inches lower than in the ditch. Set the internal recycle pumps flow as 100-200% of influent flow. AOR, lbsO2/day=1.2BOD (Ibs/day) + 4.6 NH3 (Ibs/day) SOR, lbsO2/day =1.4*AOR Number of rotors required = SOR (lbsO2/hr)Z176 lbsO2/hr.rotor APr-12. 2005 3:^1 Memo End Ken Schuster and I visited the plant on April 7, 2005, arriving at 10:00 AM and meeting with Dennis A. Brown, Area Manager for Woodard & Curran, the contracted operators for the facility. This visit was in response to the letter from McKim and Creed, Bryan Blake, PE, advising of the intent to start new process facilities, as required by the Authorization to Construct. McKim and Creed submitted a start-up plan dated February 17, 2005 with their letter of March 31 advising that start-up would take place on April 6 or 7. On our arrival, we were advised that preparations were being made for start-up, but the actual start date had been put off until Monday, April 11. We toured the facility starting with the new clarifiers, one of which was filled for leak testing. All work was essentially complete with the exception of SCADA - - We were advised that the facility would be started without SCADA and run in the manual mode. The completion date for SCADA is set for late April. Most of the instrumentation was installed and operational, but communication links had not yet been established. The BNR basins were complete and filled for leak testing. Kruger was on site servicing the basin rotors and performing other start-up checks. The MCC’s were installed, main feeds pulled, but still in the process of making terminations. Local panels were still open and in need of finalizing wire runs and completing terminations. The travelling bridge filters were complete and had previously been tested. The UV system was operational. Effluent was clear and free of foam. The current plant operation showed sludge bulking in the clarifier. This is primarily due to the intentional storing of sludge to use as seed sludge during start-up. During start­ up, the existing facility and treatment units will remain on line at all times. Start-up will be at an approximate rate of 1 MOD, and should begin the week of April 11,2005. Date: To: From: Subject: April 13, 2005 File Barry Herzberg Durham Triangle WWTP Durham County NC0026051 Recon Visit April 12, 2005 M&C 01471-0003 (40/60) RE: Dear Mr. Belnick: If you need additional information, please let me know. Sincerely, McKIM & CREED, P.A. I /der Enclosures cc: S: \ 1471 \0003 \ 40 \ 04125Belnick.doc I Please find attached the Partial Certification for the referenced project as we discussed. The Partial Certification is basically for placing into service one of the five stage biological nutrient removal trains. Train No. 2, with the other process structures as noted. This provides for 4.0 MGD ADF capacity in the new plant. Bob Carter, Durham County Chuck Hill, PE, Durham County Ken Schuster, NCDENR Regional Office Kevin Eberle, McKim & Creed, P.A. 200 MacKenan Court, Cary, North Carolina 2751 1 Tel 919.233.8091 Fax 919.233.8031 www.mckimcreed.com AA0002667 Mr. Tom Belnick NCDENR NPDES Unit 1617 Mail Service Center Raleigh, NC 27699-1617 Triangle Wastewater Treatment Plant Phase II Expansion ATC No. 026051A01 NPDES Permit No. NC0026051 McKim & Creed will process partial certifications for each of the two remaining BNR trains as the contractor achieves substantial completion. Also attached is the current start-up plan dated April 12, 2005 for your files. It is now anticipated that the new process trains will be placed into service some time this week. Bryan F. Blake, PE Senior Project Manager I, Location: > > Signature Registration No.11570 Date > > > > Michael F. Easley, Governor William G. Ross, Jr., Secretary Alan W. Klimek, P.E.„ Director ATC PROJECT NUMBER: 026051A01 Durham-Triangle WWTP NPDES Permit No. NC0026051 the Sed in &. ONE ♦ ONE ♦ ONE ♦ ONE ♦ ONE ♦ > > > The project consists of: > ] NCDENR PARTIAL CERTIFICATION Professional Engineer’s Certification For Construction of Wastewater Treatment Facilities APKTT,^?, 2005 __________________________________________j Upon completion of construction and prior to operation of the modified facility, f Division with a certification from a professional engineer certifying that the permit} accordance with the NPDES Permit, this Authorization to Construct, and the approve The Certification should be submitted to: NCDENR/DWQ, NPDES Unit, 1617 Mail Service Center, Raleigh, North Carolina State of North Caroli^ Department of ^/irdjnent and Natural Resources Division of Water Quality BRYAN F. BLAKE , am a duly registered Professional Engineer (please print) in the State of North Carolina and have been authorized to observe (circle one: full time) the construction of the subject project for the Permittee: Project: Durham/Triangle WWTP Phase II Expansion Intersection of Hwy 55 and Alexander Drive Durham County (— Installation of a new five stage biological nutrient removal system (three treatment trains) including the following: ♦ BNR system flow distribution box Three 16’ x 36’ x 18.5’ (79706 gallons) anaerobic selectors Three-36’ x 67.5’ x 18.25’ (331709 gallons) primary anoxic reactors Three.339’ x 36’ x 18’ (1,643,366 gallons) oxidation ditch aerobic reactors Thr-ee-36’ x 45.5’ x 17’ (208,315 gallons) second stage anoxic reactors Three 15’ x 36’ x 16.5’ (66,656 gallons) reaeration tanks Secondary clarifier flow distribution Four 110’ diameter x 16’ high secondary clarifiers Two return activated sludge wetwells with two high volume (3,475 gpm) and one low volume (350 gpm) pumps per wetwell ReLu En-acxivated. -sludge- PLG-based-flow -proportioniU- eomrol pump-con treLsy-stem > Tertiary filter weir type flow distribution Five train traveling bridge tertiary sand filter with effective sand particle size of 0.55 to 0.65 mm and a unifonnity coefficient (D60/D10) less than or equal to 1.5 Filter backwash system consisting of one 7.5 hp centrifugal pump per filter train (five pumps total) Sodium Aluminate Chemical feed system with application points located secondary clarifier influent distribution chamber and the tertiary sand filter distribution channel Polymer feed system with application points located secondary clarifier influent distribution chamber Sodium hypochlorite feed system with application points located at the tertiary sand filter distribution channel and the reuse water trough at the ultraviolet disinfection unit effluent > Effluent flow metering system consisting of a compound rectangular sharp crested weir and a ultrasonic level sensor > Installation of any appurtenances associated with the referenced modifications I hereby certify that I did regularly observe this project with due care and diligence and that the construction was completed in substantial conformance with the Authorization to Construct and with the approve4-hl<|s and specifications^ he I&rmfl$$fyll pQivii 1. 2. 3. 4. 5. 6. 7. 1S:\1471 \0003\60\04075Plan. doc • potassium hydroxide (supplied by Woodward & Curran) • sodium aluminate (supplied by Woodward & Curran) • polymer (supplied by Woodward & Curran, see Item 16) • methanol (supplied by Loving , see Item 1.6, Page 11501-2) • sodium hypochlorite (supplied by Woodward & Curran) The appropriate RAS/WAS pump on the north side of the new RAS/WAS pump station shall transfer flow into the new Influent Flow and RAS Distribution Box. RAS flow shall be measured by the new RAS flow meter. See Sheets C-10 and C-12. Kruger to lock out WAS Pump No. 1 and RAS Pump No. 1 in their control logic to prevent them from starting during the sludge seeding operation. (Note: In manual operation, the pumps must be monitored and not allowed to run dry.) The appropriate weir shall be set to allow RAS/WAS flow to enter the desired BNR Train (Train No. 2). The other two weirs shall be raised to isolate the remaining two BNR Trains. Weirs to be set by Loving. The State (Regional Office) shall be notified when Loving starts to fill the BNR trains for leak testing as just about all plant effluent flow will be diverted to fill the BNR trains. Woodward & Curran to notify the State. Forward flow shall enter the desired BNR Train (Train No. 2) by pumping. Two suction lift pumps each capable of pumping 500 GPM to 2700 GPM shall be set on top of the Woodward & Curran to check and confirm that all chemical bulk storage tanks have sufficient supply of chemicals. RAS and/or WAS will be pumped via the existing RAS or WAS pumps and an interconnection between the existing WAS waste line and the new WAS waste line. See Sheet C-8. Operation of existing RAS/WAS pumps by Woodward & Curran. The chemical bulk storage tanks shall be checked to confirm that a sufficient supply of the following chemicals are present: TRIANGLE WWTP PHASE II START-UP PLAN APRIL 12, 2005 The start-up plan is based on all process facilities being completed, leak tested, electrical checked out, and ready to be placed into service. The plan is also based on transferring RAS and/or WAS from the existing clarifiers to seed the one new BNR Train. The new WAS meter vault shall be valved so as to pass flow through the by-pass line around the meter vault. The WAS shall enter the new RAS/WAS wetwell by isolating and removing one of the new RAS/WAS pumps on the south side of the station. The corresponding check valve shall be blocked open to allow flow to enter the wetwell through the pump discharge piping. See Sheets C-8, C-24, and D-3A. Loving to remove RAS Pump No. 1 and block the check valve open. Loving to close the plug valve in the discharge header between RAS Pump No. 1 and No. 2 and close the 8” WAS valve in the discharge header at WAS Pump No. 2. 8. 9. 10. 11. 12. 13. 2S \1471\0003\60\04075Plan doc Begin seeding system with sludge approximately 24 to 48 hours prior to starting influent flow: Woodward & Curran to operate existing RAS/WAS pumps to provide seed sludge. The BNR train will be started and run manually without the Kruger PLC Control Panel. See the attachment “Manual Operation Train No. 2”. The existing plant process train shall remain on line at all times. The existing 30” sluice gate at the grit structure effluent box shall remain open such that forward flow not pumped into the BNR basin shall continue to feed the existing aeration basins. The amount of sludge needed for a desirable start-up MLSS level of 300-500 mg/l may be estimated as following: It is desirable to have seeded the new oxidation ditch with at least 300 to 500 mg/l of MLSS from the existing system before starting influent flow. If it is possible to have more than this, so much the better, however, Kruger does not recommend adding seed sludge more than 48 hours in advance of adding influent. If possible, allow the MLSS in the existing system to increase several days prior to anticipated startup to 20 or 30 % above your normal target level. Then waste the excess sludge to the new ditch over first two to four days of seeding. Where X is the target MLSS level in the new ditch and the total basin volume for the new ditch inclusive of ditch, anaerobic and anoxic zones is about 4.5 MG Volume of Seed Sludge, MG = (X mg/l) x Total Basin Volume(MG) MLSS in RASor WAS After leak testing has been successfully completed, the desired BNR Train (Train No. 2) to be placed into service shall have a plant effluent water level in the anaerobic, anoxic zones and oxidation ditch that reaches the edges of rotors blades (0” rotor submergence). Rotor blade submergence can be checked physically or read from the PLC. Loving to provide the effluent water and confirm level. Influent Flow and RAS Distribution Box. The discharge of the pumps shall be metered with local read out of GPM and total flow. Pumps to be furnished and setup by Loving. Woodward & Curran to maintain operation of the pumps. (Note: The temporary pumps are manually controlled without floats and must not be allowed to run dry.) The Contractor shall leak test each BNR Train one at a time with plant effluent. The testing water can be pumped from one train to the next such that the desired BNR Train to be placed into service first receives the test water last. Leak testing is to be completed prior to transferring RAS/WAS flow into BNR. Leak testing by Loving. The mixers and weirs should be placed into local or manual control. Raise the ditch effluent weirs approximately 3 inches above lowest position and set secondary anoxic effluent weirs at lowest position. Turn on all mixers. Kruger/Loving to set weirs and place mixers into operation. 14. 15. 1 MGD 3 MGD 4 MGDForward Flow 2 MGD 16. 17. 3S \1471 \0003\60\04075Plan. doc Once the influent flow has raised the water level in the ditch so that the rotor submergence > 4", turn on the rotors. If automatic D.O. control is functioning, the D.O. set point should be 2.5 mg/l. It will be decreased to 1.3 mg/l when the MLSS reaches target levels, the major criteria for achieving a stabilized system, before reducing the D.O. set point. Loving/Kruger to place rotors into operation. (Note: Automatic D.O. control will not be functioning at start up.) Once RAS/WAS flow from the existing clarifiers is not required, then the pumps in the new RAS/WWAS Pump Station shall be reset and valves adjusted to allow wasting of sludge from the new process. Loving to reset RAS Pump No. 1, reset check valve and discharge header valves for normal operation. Kruger to “unlock” RAS Pump No. 1 and WAS Pump No. 1 in control logic to allow normal operation. (Note: RAS Pump No. 1 to remain locked out until pump has been replaced.) For example, assuming the concentration of the RAS/WAS flow is about 8,000 mg/l approximately 170,000 gallons would be required to raise the MLSS level in the new ditch to 300 mg/l. Seeding the new ditch with RAS/WAS from the existing system should continue for several days following introduction of influent until the MLSS reaches between 1000 and 1500 mg/l. At that point, it will be best to let solids accumulate through new biological growth in the system. Woodward & Curran to provide for testing of sludge to ensure the desired MLSS levels. Table 1. Initial Chemical Dosage Recommendations (Durham Only - Not Including Cary Flow) Chemical______________ Sodium Aluminate_______ Potassium Hydroxide____ Emulsion Cationic Polymer Methanol mg/l 17.2 115.7 ____1_ 3 mg/l 17,2 115.7 ___1_ 3 gal/hr ____5 __14 0.08 0.94 mg/l 17.2 115.7 ____1_ 3 mg/l 17.2 115.7 ____1_ 3 gal/hr 10 ___28 0.16 1.88 gal/hr __2.5 ____7 0.04 0.47 gal/hr 7.5 ___21 0.12 1.41 Verify that chemical feed systems are functional and ready for operation (sodium aluminate, potassium hydroxide, and cationic polymer initially and methanol). Methanol will likely be required one or two weeks later, after biological nitrification has been established. Adjust initial feed rates per Table 1 based on actual influent flow rate. Start the appropriate chemical feeds simultaneously with starting influent flow to the BNR. Do not turn on the internal recycle pumps until it is verified that the new ditch is fully nitrifying as evidenced by low ammonia (< 1 mg/l) and a corresponding increase in nitrate (> 5 to 10 mg/l) in the BNR effluent (see Item 22). Woodward & Curran to provide regular testing to track ammonia and nitrate levels. Once nitrification has been established, start methanol feed at the rate indicated in Table 1 to the second anoxic zone. 18. 19. 20. 21. 4S \1471\0003\60\04075Plan doc Implement automatic level control at PLC or SCADA and set rotor submergence at 8 inches. Woodward & Curran to set automatic level control. The ditch weir shall be manually adjusted at start up in accordance with the attachment. NOTE: The aerobic F:M is estimated using the ditch volume only and does not include the volume of the anaerobic zones, the anoxic zones, or solids in the clarifier. An aerobic F:M ratio about 0.15 to 0.2 is initially desired in order to accelerate sludge build-up during start-up. The following table shows the estimation of influent flow vs. MLSS assuming an influent BOD of about 150 mg/l on average and a ditch volume of about 3 MG. Continue seeding until MLSS reaches target levels (about 3,000-4,000 mg/l). Once flow is entering the secondary clarifier and RAS flow can be discharged from the clarifier, the RAS pumps should be switched on and the RAS should be adjusted to 100% of the influent flow. It is not necessary to establish a sludge blanket during startup, rather keep the RAS rate high to ensure most of the MLSS solids reside in the aeration basins where there is food and oxygen available for growth rather than the clarifier. Control of RAS pumping shall be set by Kruger in the control logic for start-up. (Note: However at start up the RAS pumps shall be manually operated. In manual operation, the pumps must be monitored and not allowed to run dry.) One of the new clarifiers (Clarifier No. 3) shall be placed into service with the other three off-line. The clarifier will be empty and allowed to fill with forward flow from the BNR Train. Start sodium aluminate feed when forward flow is initiated to the clarifier. Woodward & Curran shall have their chemical supplier jar testing the MLSS entering the clarifier to determine the proper polymer. McKim & Creed would anticipate the use of a cationic polymer. Once the correct polymer is identified, the polymer shall be supplied at the recommended dosage to the forward flow entering the clarifier. The first clarifier shall continue to fill and allowed to stabilize establishing the sludge blanket after the BNR Train has stabilized (see Items 19 and 24). As the forward flow is increased to the first BNR Train, a second clarifier (Clarifier No. 2) can be brought on line if needed. The two remaining off-line clarifiers (Clarifier No. 1 and No. 4) shall serve as storage basins if there is an upset of the BNR Train. Flow can be diverted into the off-line clarifiers by weir adjustment at the Clarifier Distribution Box. See Sheet C- 21. Woodward & Curran is to bring on-line the second clarifier as needed. Monitor MLSS in the oxidation ditch at least once per day (maybe more often) during seeding. The initial influent flow rate may be estimated as following using the aerobic F:M as the basis for controlling flow volume. Woodward & Curran to provide for monitoring of MLSS levels. Influent flow, MGD = (F: M)x Q-7 * MLSS(mg/l) x Ditch Volume(MG) Infuent BOD(mgZI) Table 2. Recommended flow, MLSS and F:M ratio during Start-up t.Oto 1.2 600 to 700 0.14 1.5 to 1.7 0.12 2.0 to 2.2 0.10 2.3 to 2.5 0.09 3.0 to 3.2 0.09 3.5 to 4 MGD 0.09 5S:\1471\0003\60\04075Plan.aoc Influent Flow, MGD 0.5 to 0.7 900 to 1,100 1.400 to 1,600 1,900 to 2,200 2.400 to 2,600 3,000 to 3,300 MLSS, mg/l 300 to 400 Approximate F:M 0.17 The values in Table 2 assume the wastewater temperature is 12 to 15°C and an influent BOD of approximately 150 mg/l. The values in this table should be considered approximate. Decrease influent flow if effluent ammonias rise above 2 mg/l or effluent BOD rises above 15 mg/l., the influent BOD increases significantly, or the MLSS temperature in the oxidation ditch falls below 10 to 11 °C. A recommended monitoring schedule for process startup is listed in Table 3. As an absolute minimum, the ditches should be monitored for MLSS and ammonia and the clarifier effluent composite analyzed for ammonia. Kruger assumes that plant staff has the capability onsite to monitor ammonia and MLSS daily. Once the ditch is stabilized, the frequency of monitoring can be reduced. Table 3. Recommended Monitoring Schedule During BNR Process Start-up DC DCDC* DC W DG DG Once/day DG0 22. 23. 24. 25. 6S \1471\0003\60\04075Plan.doc It may be desirable to begin wasting some sludge from the new system once the MLSS reaches about 1,500 mg/l to 2,000 mg/l or 15-20 days after seeding, whichever comes first. The volume of waste sludge can be estimated based on a SRT of 15-20 days and should be less than net growth of activated sludge in oxidation ditches to allow continued accumulation of solids. Kruger will advise during startup on when to begin wasting and how much to waste. (Raw Influent (pre screening) DC* DC* DC* O DC* DG DC* W DG DG DG DC DG DG DG DG W W DC O DC W DG DG Oxidation Ditches DG DG DG DG DG DG Secondary Clarifier Effluent DC DC DC DC DC DC WAS/ RAS DG DG DG DG DG: W: O: BNR Influent (post screening) Twice/day DG At MLSS of about 2000 mg/l, adjust RAS flow to maintain a 1-2 ft sludge blanket depth in secondary clarifiers. The sludge blanket should be checked at approximately the same time each day in the same location in the clarifier. Woodward & Curran to make adjustment to RAS pumps and provide for checking of sludge blankets. Anaerobic Selector (3rd stage) As forward flow leaves the first clarifier, one new filter (Filter No. 1) shall be placed into service. Influent sluice gates for four filters shall be shut and one sluice gate shall be open for the filter to be placed into service. See Sheet C-25. Woodward & Curran Parameters Organic CBOD5 - Total Solids TSS VSS_________ Nitrogen TN TKN NH4-N NO3-N________ Phosphorus TP PO4-P________ Operational Indicators PH Alkalinity Temperature_____ Mixed Liquor Settled Sludge Volume (5,30,60 Min) ______ TP in Mixer Liquor DC: Daily composite sample DC*: Manual daily composite sample minimum of 5 samples taken to correlate with the post screening samples Daily grab sample Weekly (twice/week) Occasional Once nitrification is stabilized, as evidence by effluent ammonias < 1 mg/ and a rise in effluent nitrates, the internal recycle pumps can be started. The pumps should be set to return about 100 to 150% of the influent flow rate. Woodward & Curran to start internal recycle pumps. 26. 27. 28. 7S \1471\0003\60\04075Plan doc After approximately four weeks of operation, begin monitoring the ortho-phosphate in the selector and the total phosphate concentration in the influent about twice per week to detect onset of biological phosphorus removal. Chemical addition (sodium aluminate) will probably be required into the clarifiers, particularly during startup if phosphorus limits must be met. Woodward & Curran to provide for monitoring the ortho-phosphate level. shall set the sluice gates and place the one filter into service. When the second BNR Train is placed into service and all forward flow has been diverted from the existing plant into the new BNR process trains, a second filter (Filter No. 2) shall be placed into service. After the first BNR Train (Train No. 2) has stabilized, the second BNR Train (Train No. 1) will be started up. The startup process shall be as outlined above except seed sludge shall be provided from the new clarifiers and will not be required from the existing clarifiers. The 30’’ sluice gate at the grit structure effluent box shall be closed allowing all forward flow to enter the two BNR Trains. This will eliminate the need for the temporary pumps (Item 7) as the forward flow will be gravity flow. Once the 30” sluice gate is closed, the existing plant can be allowed to go off-line. Once the existing plant is off-line, the effluent pump station can be shut down and the 30” sluice gate at the UV structure influent box can be closed. See Sheet C-17 of the Phase I plans. Woodward & Curran to place the existing plant off-line and close the appropriate sluice gates. BOD removal should begin to occur immediately if seeding is adequate and the influent flow is not increased too rapidly. Nitrification should also follow rapidly again if the F:M ratio does not get too high. During the first couple of days of startup, there will be a considerable dilution effect to offset any delay in onset of nitrification. Sufficient MLSS must be accumulated to see good nitrogen removal and this may require several weeks. Kruger would recommend holding off on methanol addition until solids are at target levels and effluent TN levels have stabilized. Biological phosphorus will require significantly more time and will be very much dependant on the presence of soluble BOD in the influent. If the soluble BOD is present, biological phosphorus removal should begin to take place within 6-10 weeks after initial startup and steadily improve thereafter if the system is suitably loaded. The onset of biological phosphorus removal is detected by monitoring the ortho-phosphate concentration in the last stage of the anaerobic selector. Typically, it will be 3 to 5 times the ortho-phosphate concentration in the influent if the release/uptake cycle is established. After approximately four weeks of operation, Once the MLSS concentration is between 2,500 and 3000 mg/l and nitrification is stabilized, the RAS Bleed to the second anoxic stage may be started. The RAS bleed should be incrementally increased daily until the MLSS in the Secondary Anoxic zone is approximately 800 to 1000 mg/l higher than in the oxidation ditches. During this adjustment period lasting a few days, collect a sample of MLSS for solids measurement from the secondary anoxic zone in addition to the sample collected in the oxidation ditch. Typically the RAS bleed rate will be between 20 and 30 percent of the RAS flow rate and the target MLSS in the secondary anoxic should be about 700 to 1000 mg/l higher than in the oxidation ditch upstream. Once the RAS bleed is set, sampling in the secondary anoxic zone can be reduced to once per week. Lower the DO set point in the oxidation ditch to 1.3 mg/l. Woodward & Curran to make the RAS bleed adjustment and provide for testing MLSS levels. 8S \1471 \0003\60\04075Plan.doc begin monitoring the ortho-phosphate in the selector and the total phosphate concentration in the influent about twice per week. The County has agreed for Woodward & Curran to provide a designated start-up coordinator. Woodward & Curran to inform the County of the designated person. Kruger personnel will visit the site the first few days of startup and will always be available for consult. MANUAL OPERATION TRAIN #2 BEFORE TURN ON ROTORS, MAKE SURE ROTOR SUBMERGENCE >4” Initial Manual Mode Start-up 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 1.2 1.9 2.5 3.0 3.5 4.0 4.4 4.8 0 032.5 2 1.5 1.0 0 8.2 8.4 8.5 8.5 8.5 8.0 8.4 8.8 9S:\1471\0003\60\04075Plan.doc After leak testing, water levels in the ditch should reach the edges of rotor blades. Turn on all mixers Drop secondary anoxic effluent weir down to the lowest position Under manual operation mode, adjust weir position according to the flow rates listed in Table 1. The flow rates listed here are the anticipated start-up raw influent plus RAS flow. For example, assume the start-up flow rate of 2.0 MGD and RAS flow of 1.0 MGD, the total influent to the ditch would be 3.0 MGD, then the ditch effluent weir would be raised 2.0 inches from its lowest position. If the total flow rate to the ditch is more than 6.0 MGD, the effluent weir would be in the lowest position. Table 1. Rotor submergence and weir position at different flowrate Flow rate, MGD* Water head over weir, inch Initial weir elevation, inch+ Approx, rotor submergence, inch * Including RAS flow + Measured from the lowest weir position Add seeding sludge, and turn on re-aeration blowers. Once rotor submergence > 4”, turn on all rotors. Pump raw influent to the BNR train when mixed liquor concentrations reach above 500 mg/l. If necessary, re-adjust the ditch effluent weir position to maintain an optimal rotor submergence of 8.5 inches. Adjust secondary effluent weir positions so that the water levels (read from water level sensors) in secondary anoxic zones are 3” inches lower than in the ditch. Once fully nitrification has been established, turn on internal recycle pumps and set flow rate about 100 - 200%of influent flow rate or based on effluent quality. Switch from Auto Control Mode to Manual control 10S\1471\0003\60\04075Plan.doc AOR, lbsO2/day=1.2BOD (Ibs/day) + 4.6 NH3 (Ibs/day) SOR, lbsO2/day =1.4*AOR Number of rotors required = SOR (lbsO2/hr)/176 lbsO2/hr.rotor Adjust secondary effluent weir positions so that the water levels (read from water level sensors) in secondary anoxic zones are 3” inches lower than in the ditch. Set the internal recycle pumps flow as 100-200% of influent flow. Switch mixers, rotors and internal recycle pumps to manual mode. All mixers should be ON Adjust weir position according to Table 1. Please note that the weir positions are determined by the peak flow. For example, if the daily peak flow is 4 MOD and RAS is 3.0 MOD, then the weir will be drop down to the lowest position. Turn on all rotors manually or use the following equations to estimate the number of rotor in operation. Memo Date:April 21,2005 To:File From:Barry Herzberg Subject: End A follow-up visit was made to this facility now that start-up of the new BNR trains is underway. Contacts on site included Charles Hill, Utility Division Manager and Bob Carter, Project Manager for Durham County, and Don Hancock, Construction Administrator for McKim and Creed. The first of the three new BNR trains was on line. Seed sludge had been taken from the existing plant clarifiers, and the process appeared to be functioning according to plan. Equipment was working satisfactorily, although the SCADA system is still not functional. Influent flow is being split so as to maintain 1.0 to 1.5 MOD to the new system with the balance going to the existing plant. Process color and odor were unremarkable. Foaming was minimal in the ditch. The Kruger equipment was operating smoothly. Secondary clarifier was clear of surface contaminants, and effluent over the weirs was clean. At the time of my visit, the traveling bridge tertiary filters had been taken off line to allow installation of a catwalk along the overflow weir in the effluent chamber downstream of the UV system. A significant amount of site work has been completed in the two weeks since my last visit. Once the first BNR train has stabilized, the second train will be put into service. The third train will remain serviceable, but will not be put into operation until necessary to meet flow demands. Target project completion date is June 5, 2005. Durham Triangle WWTP Durham County NC0026051 Recon Visit r « April 27, 2005 M&C 01471-0003 (40/60/70 RE: Dear Mr. Belnick: remaining BNR train as the It is anticipated that BNR Train No. 1 will be placed into service some time next week. If you need additional information, please let me know. Sincerely, McKIM & CREED, P.A. /der Enclosures cc: 1 Please find attached another Partial Certification for the referenced project as we discussed. This Partial Certification is for placing into service the second five stage biological nutrient removal train. Train No. 1. This provides for an additional 4.0 MGD ADE capacity in the new plant for a total of 8.0 MGD. Bob Carter, Durham County Chuck Hill, PE, Durham County Ken Schuster, NCDENR Regional Office Kevin Eberle, McKim & Creed, P.A. Ty Edmondson, III, PE, T. A. Loving Co. Mr. Tom Belnick NCDENR NPDES Unit 1617 Mail Service Center Raleigh, NC 27699-1617 Triangle Wastewater Treatment Plant Phase II Expansion ATC No. 026051A01 NPDES Permit No. NC0026051 / Bryan f. Blake, PE Senior Project Manager McKim & Creed will process a partial certification for the one contractor achieves substantial completion. S:\1471\0003\40\04275BelnickDOC 200 MACKENAN COURT, CARY, NORTH CAROLINA 2751 1 Tel 919.233.8091 Fax 919.233.8031 www.mckimcreed.com AA0002667 NCDENR Location: The project consists of: BNR Train No. 1 id with the approved plans and 11570 State of Not Department 1 and Natural Resouro Division of Water Quality Michael F. Easley, Governor William G. Ross, Jr., Secretary Alan W. Klimek, P.E.„ Director > Installation of a new five stage biological nutrient removal system (one treatment train) including the following: ■ One Anaerobic Selector with three cells each 15'-9"x36'x18' (total volume 229,000 gallons) ■ One Primary Anoxic Reactor with two cells each 67’x36'xl8’ (total volume 649,500 gallons) ■ One Oxidation Ditch Aerobic Reactor 72'x339'xl8' (total volume 3,200,000 gallons) ■ One Second Stage Anoxic Reactor with two cells each 36'x45'xl7' (total volume 412,000 gallons) ■ One-Re-Aeration Stage 15'x36'xl6.9' (total volume 68,000 gallons) ^Carolina t®Envir^nent I Resources aid mligence and that the construction was j®jct |nd with the approved plans and Professional Engineer’s Certification For Construction of Wastewater Treatment Facilities ATC PROJECT NUMBER: 026051A01 Durham-Triangle WWTP NPDES Permit No. NC0026051 I, Bryan F. Blake •, am a duly registered Professional Engineer (please print) . , in the State of North Carolina and have been authorized to observe (circle one: jXXii&kSHy, full time) the construction of the subject project for the Permittee: Project: Durham/Triangle WWTP Phase II Expansion Intersection of Hwy 55 and Alexander Drive Durham County I hereby certify that I did regularly observe thisfcroj^fwigg^afe $pc completed in substantial conformance with the jkutIwrizatLon^feCons1 specification^----y s W sisna“re Date April_27f 2005 Upon completion of construction and prior to operation of the modified facility, the Permittee shall provide the Division with a certification from a professional engineer certifying that the permitted facility has been installed m accordance with the NPDES Permit, this Authorization to Construct, and the approved plans and specif cations. The Certification should be submitted to: NCDENR/DWQ, NPDES Unit, 1617 Mail Service Center, Raleigh, North Carolina 27699-1617 f May 17, 2005 RE: Dear Mr. Belnick: If you need additional information, please let me know. Sincerely, McKIM & CREED, P.A. /der Enclosures cc: Please find attached another Partial Certification for the referenced project as we discussed. This Partial Certification is for substantial completion of the third and final five stage biological nutrient removal train, Train No. 3. This provides for an additional 4.0 MGD ADF capacity in the new plant for a total of 12.0 MGD. It is anticipated that BNR Train No. 3 will not be placed into service until such time as the additional capacity is needed. Please note that McKim & Creed has issued three partial certificates to date which cover all the process units and equipment per the Authorization to Construct except for the inplant SCADA system. A fourth and final partial certificate will be issued for this component. Bob Carter, Durham County Chuck Hill, PE, Durham County Ken Schuster, NCDENR Regional Office Kevin Eberle, McKim & Creed, P.A. Ty Edmondson, III, PE, T. A. Loving Co. Mr. Tom Belnick NCDENR NPDES Unit 1617 Mail Service Center Raleigh, NC 27699-1617 Triangle Wastewater Treatment Plant Phase II Expansion ATC No. 026051 AO 1 NPDES Permit No. NC0026051 M&C 01471-0003 (40/60/70) Bry^h F. Blake, PE Senior Project Manager S:\1471\OOO3\4O\O5175Belnick.DOC 200 MACKENAN COURT, CARY, NORTH CAROLINA 2751 1 TEL 919.233.8091 Fax 919.233.8031 www.mckimcreed.com AA0002667 r i NCDENR Location: The project consists of: BNR Train No. 3 igistration No.11570Signature Michael F. Easley, Governor William G. Ross, Jr., Secretary Alan W. Klimek, P.E.„ Director > Installation of a new five stage biological nutrient removal system (one treatment train) including the following: ■ One Anaerobic Selector with three cells each 15'-9"x36'xl8' (total volume 229,000 gallons) ■ One Primary Anoxic Reactor with two cells each 67'x36'xl8' (total volume 649,500 gallons) ■ One Oxidation Ditch Aerobic Reactor 72'x339zxl8' (total volume 3,200,000 gallons) ■ One Second Stage Anoxic Reactor with two cells each 36'x45'x17' (total volume 412,000 gallons) ■ One-Re-Aeration Stage IS'xSO'xlb.O' (total volume 68,000 gallons) State of N Ai Cardia Departmen^f ErrflBnment and Natural Resources Division of Water Quality ATC PROJECT NUMBER: 026051A01 Durham-Triangle WWTP NPDES Permit No. NC0026051 I,Bryan F, Blake _____________________, am a duly registered Professional Engineer (please print) in the State of North Carolina and have been authorized to observe (circle one-^peri®riicalhV55®ckJy, full time) the construction of the subject project for the Permittee: Project: Durham/Triangle WWTP Phase II Expansion Intersection of Hwy 55 and Alexander Drive Durham County I i I hereby certify that I did regularly olfserVe this'H^ completed in substantial conformancd^ithyihe Autho specifications. J Professional Engineer’s Certification For . Construction of Wastewater Treatment Facilities Date May 17 , 2005 _________• Upon completion of construction and prior to operation of the modified facility, the Permittee shall provide the Division 'with a certification from a professional engineer certifying that the permitted facility has been installed in accordance with the NPDES Permit, this Authorization to Construct, and the approved plans and specifications. The Certification should be submitted to: NCDENRJDWQ, NPDES Unit, 1617 Mail Service Center, Raleigh, North Carolina 27699-1617 □ B J10 witlj du&care and diligence and that the construction was rorizati&n ti/Construct and with the approved plans and Michael F. Easley, Governor ’ M . »j June 20, 2005 Floor Dear Mr. Hill: Sincerely, 50% Recycled/10% Post Consumer PaperAn Equal Opportunity/Affirmative Action Employer - The facility was operating normally at the time of the inspection, with an influent flow of approximately 5.0 MGD. There were no objectionable odors anywhere on the facility grounds. North Carolina Division of Water Quality Internet: h2o.enr.state.nc.us On June 7, 2005, Mr. Barry Herzberg of the Raleigh Regional Office conducted an annual Compliance Evaluation Inspection of the subject facility. The attached checklist reflects those areas evaluated during this inspection, and includes comments where appropriate at the end of each section. We are pleased to advise that the Durham Triangle Water Reclamation Facility is in compliance with the NPDES permit, NC0026051. Should you have any questions regarding this evaluation, please contact me at 919-571-4700 extension 238, or by e-mail to barry.herzberq@ncmail.net. Barry Herzberg 1/ Environmental Engineer Raleigh Regional Office 1628 Mail Service Center William G. Ross, Jr., Secretary North Carolina Department of Environment and Natural Resources Phone(919)571-4700 FAX (919)571-4718 Alan W. Klimek, P.E., Director Division of Water Quality Subject: Compliance Evaluation Inspection Durham Triangle Water Reclamation Facility Durham County NPDES Permit No. 0026051 Surface Water Protection Raleigh. NC 27699-1628 NorthCarolinaNaturally Customer Service 1-877-623-6748 ?puch Mr. Charles N. Hill, Jr., P.E. Utility Division Manager Durham County 120 E. Parrish Street, T1 Durham, NC 27701 JUN 2 0 2305 2J d EPA NPDES 3l NC0026051 21| I I I I I I | | | | I | I I I I I I I Illi66 Entry Time/Date Permit Effective Date 04/03/01 Triangle WWTP Exit Time/Date Permit Expiration Date5926 NC Hwy 55 E 06/04/30Durham NC 27701 Other Facility Data Gerald Tyrone Battle/ORC/919-544-8831/ Ronald Glenn Ketteman/ORC/919-544-8280/ Name, Address of Responsible Official/Title/Phone and Fax Number Effluent/Receiving Waters Section D; Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date RRO WQ///HerzbergBarry Agency/Office/Phone and Fax Numbers DateSignature of Management Q A Reviewer EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. 12L United States Environmental Protection Agency Washington, D C. 20460 yr/mo/day 05/06/07 Operations & Maintenance | Records/Reports Laboratory Contacted No QA 72 LJ Jerry F Rimmer,120 E Parrish St Durham NC 27701/Plant Manager/919-544-8280/9195448590 Facility Self-Monitoring Evaluation Rating 7° Lil Form Approved. OMB No. 2040-0057 Approval expires 8-31-98 Fac Type 20 LJ Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) /// Inspection Type 18l£jJ 11 Section C: Areas Evaluated During Inspection (Check only those areas evaluated) M Flow Measurement Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include POTW name and NPDES permit Number) J 17 Inspector 19l±| Inspection Work Days 671 .5 | 69 Remarks I I I I I I I I I I I I I I I I I I I | | | | Bl 71 U 73 LU74 m Permit m Facility Site Review Water Compliance Inspection Report Section A: National Data System Coding (i.e., PCS) —Reserved--------------------- 75| | | | | | | | 80 Transaction Code 1 Ld 2 LI 09:00 AM 05/06/07 12:30 PM 05/06/07 Permit (If the present permit expires in 6 months or less). Has the permittee submitted a new application? Is access to the plant site restricted to the general public? Comment: NA NEBar Screens b.Mechanical Are the bars adequately screening debris? Is the screen free of excessive debris? Is disposal of screening in compliance? Is the unit in good condition? Comment: There was a minor amount of debris collecting on the inside of the units rear access panel. NA NEGrit Removal Type of grit removal a.Manual b.Mechanical NA NE Comment: NA NE Is the site free of excessive buildup of solids in center well of circular clarifier? Are weirs level? Is the site free of weir blockage? Is the site free of excessive floating sludge? Is the drive unit operational? Is disposal of grit in compliance? Comment: An odor control system is operational in both the barscreen and grit removal areas. There were no objectionable odors anywhere in the immediate area. Grease Removal Secondary Clarifier Is the clarifier free of black and odorous wastewater? Is the facility as described in the permit? Are there any special conditions for the permit? Type of bar screen a.Manual Is the grit free of excessive organic matter? Is the grit free of excessive odor? Is automatic grease removal present? Is grease removal operating properly? Is the site free of evidence of short-circuiting? Is scum removal adequate? Is the sludge blanket level acceptable? Is the return rate acceptable (low turbulence)? ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ Is the inspector granted access to all areas for inspection? Comment: This facility is now operating the completed expansion to 12.0 MGD, with the following treatment components: Mechanical barscreens and grit removal, 5 stage BNR system, secondary clarifiers, tertiary sand filters and UV disinfection. Sludge is wasted to a holding lagoon for annual processing. The permit limits for 12.0 MGD operation are included in the current permit. Operations & Maintenance Is the plant generally clean with acceptable housekeeping? Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable Solids, pH, DO, Sludge Judge, and other that are applicable? Yes No Yes No Yes No Yes No NA NE Yes No Secondary Clarifier Is the overflow clear of excessive solids/pin floc? NENA Are pumps in place? Type Is chemical feed required to sustain process? NA NEFiltration (High Rate Tertiary') Type of operation: Is the filter free of growth? Is the air scour operational? Comment: NA NEDisinfection - UV Are extra UV bulbs available on site? Are UV bulbs clean? Is UV intensity adequate? Is transmittance at or above designed level? Is effluent clear? Is there a backup system on site? Is effluent clear and free of solids? Comment: NA NE Is the generator tested by interrupting primary power source? Is the generator tested under load? Is there an emergency agreement with a fuel vendor for extended run on back-up power? NENA Is the surface free of bulking ? Is the sludge blanket level acceptable? (Approximately 'A of the sidewall depth) Comment: Only one of the four clarifiers was in operation during the inspection. Sludge troughs were clean and operating normally. Rumps-RAS-WAS Is the generator fuel level monitored? Comment: There are three standby generators on site. All are operational, but were not tested during this inspection. This facility also has dual power feeds from Duke Power. Laboratory Are pumps operational? Are there adequate spare parts and supplies on site? Is nutrient removal process operating properly? Comment: Was generator tested & operational during the inspection? Do the generator(s) have adequate capacity to operate the entire wastewater site? Is total nitrogen removal required? Is total phosphorous removal required? Is the filter media present? Is the filter surface free of clogging? Is the scouring acceptable? Is the clear well free of excessive solids and filter media? ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ Comment: One pump had been removed due to failure on start-up caused by faulty wiring. Nutrient Removal Standby Power Is automatically activated standby power available? Biological ■ ■ Yes No Yes No Yes No Yes No Yes No Yes No NA NF Is proper temperature set for sample storage (kept at 1.0 to 4.4 degrees Celsius)? Incubator (Fecal Coliform) set to 44 5 degrees Celsius*/- 0.2 degrees? Record Keeping Are records kept and maintained as required by the permit? Is the chain-of-custody complete? O&M Manual ■ Dates, times and location of sampling Dates of analysis Name of person performing analyses Is the backup operator certified at one grade less or greater than the facility classification? Is a copy of the current NPDES permit available on site? Effluent Pipe Are all other parameters(excluding field parameters) performed by a certified lab? Is the facility using a contract lab? Incubator (BOD) set to 20.0 degrees Celsius +/-1.0 degrees? Comment: Is all required information readily available, complete and current? Are all records maintained for 3 years (lab. reg. required 5 years)? Are analytical results consistent with data reported on DMRs? Transported COCs Are DMRs complete: do they include all permit parameters? Has the facility submitted its annual compliance report to users and DWQ? (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator on each shift? Is the ORC visitation log available and current? Is the ORC certified at grade equal to or higher than the facility classification? Facility has copy of previous year's Annual Report on file for review? Comment: As built Engineering drawings Schedules and dates of equipment maintenance and repairs Name of individual performing the sampling Results of analysis and calibration ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ Laboratory Are field parameters performed by certified personnel or laboratory? Is right of way to the outfall properly maintained? Are the receiving water free of foam other than trace amounts and other debris? If effluent (diffuser pipes are required) are they operating properly? Comment: Very clean effluent discharge to Northeast Creek. Several large catfish and numerous smaller fishes in area. Advised plant personnel to try to determine if catfish were the flathead (invasive) species. Yes No NA NE July 7, 2005 Re: Dear Mr. Schuster: If you have any questions or need additional information, please call me at 560-7992. cc: CH/jld ■5 / Glen E. Whisler, P.E., County Engineer Adrienne Fancher, Project Manager-United Water 120 E. Parrish Street, Law Bldg., 1st Floor, Durham, N.C. 27701 (919) 560-0735 Fax (919) 560-0740 Equal Employment/Affirmative Action Employer NCDENR - Raleigh Regional Office Kenneth Schuster, P.E. Water Quality Regional Supervisor Division of Water Quality Water Quality Section 1628 Mail Service Center Raleigh, NC 27699-1628 Sincerely, Chuck Hill, P.E. Utility Division Manager Effective July 1, 2005, United Water assumed the operations and maintenance responsibilities for the TWWTP (NC0026051) and collection system (WQC00038) under a five (5) year contract with Durham County. The new Project Manager is Adrienne Fancher and she can be reached at 544-8280. Tyrone Battle will remain as IPP Coordinator and Plant ORC and will be backed up by Ron Ketteman. The collection system ORC will remain as Ron Ketteman and he will be backed up by Victor Cozart. ' ^1 ‘ I ■ ■?./ WWTP and Collection Systems Operations Change Notification for the Triangle Wastewater Treatment Plant (TWWTP) at 5926 Hwy 55 NA COUNTY OF DURHAM ENGINEERING DEPARTMENT /ii ■ ^vfCEJM&(?RSED August 17, 2005 M&C 01471-0003 (40/60/70) RE: Dear Mr. Belnick: If you need additional information, please let me know. Sincerely, McKIM & CREED, P.A. /der Enclosure cc: S:\1471\0003\40\08175Beinick.DOC Bob Carter, Durham County Chuck Hill, PE, Durham County Ken Schuster, NCDENR Regional Office Kevin Eberle, McKim & Creed, P.A. Ty Edmondson, III, PE, T. A. Loving Co. Mr. Tom Belnick NCDENR NPDES Unit 1617 Mail Service Center Raleigh, NC 27699-1617 Triangle Wastewater Treatment Plant Phase II Expansion ATC No. 026051A01 NPDES Permit No. NC0026051 200 MacKenan Court, Cary, North Carolina 2751 1 Tel 919.233.8091 Fax 91 9.233.8031 www.mckimcreed.com AA0002667 Bry/m F. Blake, PE Senior Project Manager Please note that McKim & Creed has now issued four partial certificates which cover all the process units and equipment per the Authorization to Construct. Please find attached the fourth and last Partial Certification for the referenced project as we discussed. This Partial Certification is for substantial completion of the in-plant SCADA system. NCDENR I, Location: This certification is for substantial completion of the in-plant SCADA system. itration No.11570 Date I hereby certify that I did regularly c completed in substantial conformam specifications, Signature! Michael F. Easley, Governor William G. Ross, Jr., Secretary Alan W. Klimek, P.E.„ Director Project: Durham/Triangle WWTP Phase II Expansion Intersection of Hwy 55 and Alexander Drive Durham County ATC PROJECT NUMBER: 026051A01 Durham-Triangle WWTP NPDES Permit No. NC0026051 Bryan F. Blake , am a duly registered Professional Engineer (please print) in the State of North Carolina and have been authorized to observe (circle one: periodically, weekly, full time) the construction of the subject project for the Permittee: State of NorthA^roy^ Department oHznvi™ment and Natural Resources Division of Water Quality witH du&care and diligence and that the construction was tlie^^^Qzati(Mi toJSonstruct and with the approved plans and July 2005 Upon completion of construction and prior to operation of the modified facility, the Permittee shall provide the Division with a certification from a professional engineer certifying that the permitted facility has been installed in accordance with the NPDES Permit, this Authorization to Construct, and the approved plans and specifications. The Certification should be submitted to: NCDENRJDWQ, NPDES Unit, 1617 Mail Service Center, Raleigh, North Carolina 27699-1617 7$ 2005 PROFESSIONAL ENGINEER’S CERTIFICATION FOR Construction of Wastewater Treatment Facilities cQ. . ft n K. J» . a sep : wi Michael F. Easley, Governor September 22, 2005 Subject: Dear Mr. Hill: We regret the extreme delay in providing you with these comments. Sincerely, You are reminded of the Division’s December 10, 2004, letter requires all POTWs to make various revisions to their SUOs and submit them by December 1, 2006. Please review our web­ site for details. Mr. Chuck Hill Division Head, Durham County Env. Eng. Office Durham County 120 E. Parrish St., Suite 110 Durham, NC 27701 Pretreatment Review of Sewer Use Ordinance (SUO) Program: Durham County Durham County NPDES Number NC0026051. 1617 Mail Service Center 512N. Salisbury St. Phone(919)733-5083 FAX (919)715-0059 Alan W. Klimek, P.E. Director Division of Water Quality Raleigh, NC 27699-1617 Raleigh, NC 27604 NC DWQ/PERCS Internet: h2o.enr.state.nc.us/Pretrcat/index.html Thank you for your continued support of the Pretreatment Program. If you have any questions or comments, please contact Dana Folley at (919) 733-5083 ext. 523 [email: Dana.Folley@ncmail.net] or Jeff Poupart, Supervisor of the Pretreatment, Emergency Response, and Collection Systems Unit (PERCS) at ext 527 [email: jeff.poupart@ncmail.net]. An Equal Opportunity/Affirmative Action Employer - 50% Recycled/10% Post Consumer Paper William G. Ross Jr., Secretary North Carolina Department of Environment and Natural Resources The review indicates that the SUO is adequate and the minimum requirements of 15A NCAC 2H .0900 and 40 CFR 403 are met. The SUO was adopted by the local governing body on September 1, 2003. The Pretreatment, Emergency Response and Collection Systems Unit (PERCS) of the Division of Water Quality has reviewed the Sewer Use Ordinance (SUO) for Durham County. This SUO was received by the Division on March 1, 2004, with additional information received on November 22, 2004. NorthCarolina -------------Naturally Customer Service 1-877-623-6748 pZ, co/rI j Q \ Alan W. Klimek, P.E. DRF / durhamcounty_suo_003 cc: Tyrone Battle, United Water, consultant for Durham County Central Files Chris Wu, Raleigh Regional Office Dana Folley, PERCS Unit 1 ItaXZ 1111 r Michael F. Easley, Governor ft ft Date: October 17, 2005 Subject: Notice of Incomplete Discharge Monitoring Report Dear Permittee: cc: An Equal Opportunity/Affirmative Action Employer Raleigh Regional Office Central Files Charles N. Hill, Jr. 120 East Parrish Street Durham, NC 27701 Attention: Michele Phillips Division of Water Quality Central Files 1617 Mail Service Center Raleigh, North Carolina 27699-1617 Raleigh, North Carolina 27699-1617 Raleigh. NC 27604 Phone: (919)733-7015 Fax: (919)733-0719 Alan W. Klimek, P, E. Director Division of Water Quality N. C. Division of Water Quality Internet: http://h2o.enr.state.nc.us Future DMR submittals with the same or similar problems will be unacceptable. If you have any questions about the proper completion of DMRs, please contact Michele Phillips at 919-733-5083 Ext. 225. Thank you for your assistance in this matter. 1617 Mail Service Center 512 N. Salisbury St. The purpose of this letter is to call your attention to problems with the recent submittal of the Discharge Monitoring Report (DMR) from your facility. As you may know, the data recorded on your DMR is keyed into the Division’s database. Our data entry staff has informed me of problems with your recent DMR submittal. Until these problems have been corrected, your DMR will be considered incomplete. Please see the attached form along with a copy of the problem DMR for details regarding the DMR’s deficiency. North Carolina____ Naturally Customer Service 1-877-623-6748 At7 rGO > o Incomplete or illegible DMRs affect our staffs ability to provide a timely and effective evaluation of DMR submittals. Please be aware that until the Division receives a corrected DMR, you may be considered noncompliant with your NPDES permit and 15A NCAC 02B .0506, and you may be subject to further enforcement action. Please take the necessary steps to correct the problems and submit two copies of the amended DMR within fifteen (15) days of the date of this letter to the following address: William G. Ross Jr., Secretary Nonh Carolffroepanment of Environment and Natural Resources Sincerely, W. Klimek, P.E. Notice of Incomplete Discharge Monitoring Report Q The written values are illegible. % Q The Average, Maximum, and/or the Minimum data points have been omitted. O The Units of Measure have been omitted or are incorrect U The DMR Parameter Codes have been omitted. The Division of Water Quality deems the aforementioned DMR as incomplete due to the following reason(s): (Please see the highlighted areas on the attached DMR for details.) Facility: County. DMR Month and Year Other .. C-oppcjn r\c T5 . plaj'-e. -fee UrsuZ "Qifm ~fznv| Permit Number |\^ 06 3^05-1 Michael F. Easley. Governor October 28, 2005 Subject: Dear Ms. Tian: An Equal Opportunity/Affirmative Action Employer - 50% Recycled/10% Post Consumer Paper On July 13, 1995, the Environmental Management Commission approved the Town of Cary's request for full delegation authority to issue sanitary sewer extension permits. In conjunction with that delegation, this office has been allowing the Town to issue sewer extension permits based upon a block flow approval process. Previously, the Raleigh Regional Office has granted block flow approvals for the North Cary WWTF totaling 5,000,000 GPD. As requested in your letter dated October 14, 2005, the Raleigh Regional Office hereby grants an additional block flow allocation of 500,000 GPD for the North Cary WWTF yielding a total of 5,500,000 GPD granted for that facility. The North Cary WRF has a current capacity of 10.0 MGD. North Carolina Division of Water Quality Internet h2o.enr.state.nc.us Ms. Shuyan Tian, PE Development Review Engineer Town of Cary Post Office Box 8005 Cary, N. C. 27512-8005 1) 2) 3) 4) 5) 6) Permit No. Permit Issue Date Permit Holder Name of Project Project Wastewater Flow Total Project Wastewater Flow for the Month Summary of Activities for Violations of the Permitting Process Town of Cary Sanitary Sewer Flow Allocation North Cary WRF - Block Flow Approval No. 23 Wake County Raleigh Regional Office 1028 Mail Service Center William G. Ross. Jr.. Secretary North Carolina Department of Environment and Natural Resources Phone (919)571-4700 FAX (919)571-4718 Alan W Klimek. P.E., Director Division of Water Quality Surface Water Protection Raleigh, NC 27699-1628 As permits are issued by the Town, the wastewater flow associated with those projects will be subtracted from the block flow allocation. When the issued permits have almost depleted the flow allocation, the Town will request that it be granted an additional allocation. The Raleigh Regional Office (RRO) requires that the Town submit a quarterly report for each WWTF. The reports should be received by the Raleigh Regional Office before the end of each of the months of January, April, July and October, and must provide the following information for the permits that have been issued: North Caroli nu___Naturally Customer Service 877-623-6748 /DWGC° .. Additionally, the report must provide the following information: D 4) 5) 6) Sincerely, Copies: According to our records, the addition of this block flow allocation to your remaining block flow balance will provide the Town of Cary with a total of 578,255 gpd in unpermitted block flow allocation. Our records also show a remaining paper flow capacity for your treatment facility of 1,773,280 gpd, not including the expansion of the North Cary facility to 12.0 MOD. This amount removes all the Kit Creek Pump Station service area tributary and permitted flows from the Cary North facility and redirects these flows to Durham Triangle WWTP, as stated in Glen Harrell’s letter of October 13, 2005. If you have any questions regarding this matter, please contact Barry Herzberg at 919-791-4249, or via E-Mail to barry.herzberg@ncmail.net. Ms. Shuyan Tian, P. E. Page 2 October 28, 2005 2) 3) Running Total of Flow Allocated to the Town by the Raleigh Regional Office, to Date Running Total of Flow From Permits Issued, to Date Flow Which Remains From Allocation From RRO (flow allocated but not yet depleted by issued permits) Running Total of Flow Which has Been Depleted From the Allocation by Issued Permits, but Which has not yet Become Tributary to the WWTF Total Flow (also includes flow for permits issued prior to the implementation of the block flow approval process) not yet Tributary to the WWTF Most Recent Twelve Month Flow Average of the WWTF Kenneth Schuster, P. E. Regional Water Quality Supervisor Durham Triangle file - NC0026051 Cary North file - NC0048879 Please be advised that the Raleigh Regional Office reserves the right to suspend this block flow approval process if problems occur with the operation of this program, if problems occur with the compliance status of the WWTF, or if other situations occur which might jeopardize the successful operation of this program. 1 October 27, 2005 Dear Mr. Herzberg: cc: Glen E. Whisler, P.E., County Engineer CH/kt You are cordially invited to an Open House at the Triangle Wastewater Treatment Plant, located at 5926 NC Highway 55 on November 8, 2005, 2:00 P.M. to 4:00 P.M. We look forward to showing you our newly upgraded and expanded treatment facility. 120 E. Parrish Street, Law Bldg., 1st Floor, Durham, N.C. 27701 (919) 560-0735 Fax (919) 560-0740 Equal Employment/Affirmative Action Employer 5% Sincerely, CU Chuck Hill, P.E. Utility Division Manager NCDENR - Pretreatment Unit Barry Herzberg, Environmental Engineer, I Division of Water Quality 1617 Mail Service Center Raleigh, NC 27699-1617 \ < \w If you have any questions, please contact me by telephone at 560-7992 or e-mail at chill@co.durham.nc.us. COUNTY OF DURHAM ENGINEERING DEPARTMENT 2 Dear Mr. Hill: Sincerely, ) cc: An Equal Opportunity/Affirmative Action Employer - 50% Recycled/10% Post Consumer Paper 1617 Mail Service Center 512 N. Salisbury St. Phone(919)733-7015 FAX (919)733-2496 Alan W. Klimek, P.E. Director Division of Water Quality North Carolina Division of Water Quality Internet: h2o.enr.state.nc.us Raleigh. NC 27699-1617 Raleigh, NC 27604 Mr. Chuck Hill, P.E. Durham County 120 E. Parrish Street, Suite 110 Durham, NC 27701 Customer Service 1-877-623-6748 CENTRAL FILES Raleigh Regional Office/Surface Water Protection NPDES Unit Subject: Receipt of permit renewal application NPDES Permit NC0026051 Triangle WWTP Durham County Frances Candelaria Point Source Branch Michael F. Easley, Governor I 8 ?! NorthCarolina Naturally The NPDES Unit received your permit renewal application on November 2, 2005. A member of the NPDES Unit will review your application. They will contact you if additional information is required to complete your permit renewal. You should expect to receive a draft permit approximately 30-45 days before your existing permit expires. The requirements in your existing permit will remain in effect until the permit is renewed (or the Division takes other action). il William G. Ross Jr., Secretary North Carolina Department of Environment and Natural Resources lirv' l j November 2, 2005 If you have any additional questions concerning renewal of the subject permit, please contact me at (919) 733-5083, extension 520. 2 IM 14 > I L/VUv-Z November 1, 2005 Renewal Application for Permit NC0026051 Triangle WWTPRe: Dear Mr. Weaver: 120 E. Parrish Street, Law Bldg., 1st Floor, Durham, N.C. 27701 (919) 560-0735 Fax (919) 560-0740 Equal Employment/Affirmative Action Employer Mr. Charles H. Weaver, Jr. NCDENR/Division of Water Quality Point Source Branch 1617 Mail Service Center Raleigh, NC 27699-1617 /■9.' A' '^1 > The number of clarifiers has doubled to four with an increase in the overall diameter of each and treatment capacity. Durham County respectfully submits this permit renewal application for consideration. Since the last permit issuance, we have, in essence, built a new plant. The new facility is capable of removing nitrogen and phosphorous through biological processes, and can treat an average daily flow of 12 MGD. > The Influent Pumping Station (IPS) was designed with the intent of a more efficient and less odorous removal of screenings and grit. COUNTY OF DURHAM ENGINEERING DEPARTMENT > Instead of using two extended aeration basins that could treat 6 MGD, the new facility boasts three Biological Nutrient Removal (BNR) trains that doubled our treatment capacity to 12 MGD. The new facility is geared to the removal of the nutrients Totals Nitrogen and Total Phosphorus in an effort to meet mandates prescribed by the Sta^ and EP A. Previously, we could not treat for Total Nitrogen but the BNR System j/qw7 offers that capability. The previous configuration relied heavily on chemical a precipitation for the treatment of Total Phosphorus. The BNR system allows us the / benefit of treating biologically for Total Phosphorus thus decreasing our depepde^cy on chemicals. We are pleased to report that there has been a significant reductidh in ‘ the two parameters as well as Ammonia since the start up of the system. > > > > Enclosure cc: 2 The County is proceeding with the design of sludge management facilities to produce a Class A sludge within the next few years. The current schedule has this process on line in 2008. The current lagoon will continue to be utilized and annual removals will continue until the new processes are completed. Finally, there is a serpentine chamber outfitted with multiple diffusers for post aeration before discharge to the creek. Glen E. Whisler, P.E., County Engineer Adrienne Fancher, Project Manager - United Water The walls of the aforementioned structures were built above the one hundred year flood plane. We think that this will help us maintain efficiencies during periods of excessively high flow. Three (3) emergency generators have been installed that permit 100% coverage in the event of an electrical failure. The chosen form of disinfection is Ultraviolet (UV) instead of chlorine. It allows for more consistent disinfection and is exponentially safer for the operators. There are now five sand filters instead of two. There is not only an increase in treatment capacity, but it offers a maintenance bonus. The filters can be rotated periodically and serviced more often without sacrificing run time. Sincerely, MJ Chuck Hill, P.E. Utility Division Manager The County is currently contracting with Bionomics for sludge removal. Each year, sludge is removed from the lagoon, equivalent to or exceeding the amount produced during that year, as anticipated in the Interim Biosolids Management Plan approved by the Division of Water Quality June 10, 2002 (copy attached). This contract includes dredging from the lagoon, dewatering on site, and hauling dewatered sludge to a composting facility permitted by the state for this purpose. The County is not using land application for the disposal of sludge at this time. FOR ADDITIONAL INFORMATION CONTACT THE DURHAM COUNTY ENGINEERING DEPARTMENT AT 560-0735 NOVEMBER 8, 2005 2:00PM to 4:00PM INVITATION TO AN OPEN HOUSE AT THE TRIANGLE WASTEWATER TREATMENT PLANT 5926 Highway 55 X A A 1 PF J K*STtW»T8« ■Mumwr Kami ^lAAPaVEST J- i4'h(55J HU Df / ■=t EnyleH Dr .14 Of J /A ■ \M 1 Eimst'l Ln TWWTP 17ScirtvKing Hopson P'rt i I5 ?005 MapQuftst.com, inc aI O Directions to Triangle Wastewater Treatment Plant (TWWTP) from [-40. The address of the plant is 5926 Highway 55. 2. 3. a Genlee -5 i— /- -J ~~ I O \ I I -7 Chatham U' % 54 ’2 - - "-•-■J 1. Get off 1-40 at exit 279A (heading away from downtown Durham) Turn left onto Alexander Dr. Proceed through the light at Hwy. 55 into Treatment Plant Wike I I z Clef'nont Rd I 9 2 Q .r o I CO, Parkwood o .Ctegg l o Nelson 0 •\ z> s a