HomeMy WebLinkAboutWQ0045885_Application (FTSE)_20240819a C) s iversENGINEERS PLANNERS SURVEYORS LANDSCAPE ARCH ITECTS 8 ASSOCIATES, INC SANITARY SEWER NARRATIVE Bayswater Apartments (Greenville, NQ — Proj. M 2022044 Service Area Description: This sewer system is to serve an 12+/- acres site of which 11 acres are developed for the purpose of a multi -family residential site. The proposed project consists of 5 Apartment Buildings, a Clubhouse and pool area, private access and parking, sidewalks, mail kiosk, and other features as depicted on the plans. Calculated Design Flow The calculated design flow is shown by the chart below. Daily flow rates are determined based upon the recommendations for daily design flow from 15A NCAC 02T .0714 - WasteWater Design Flow Rates; multiplied by a peaking factor of 2.5. The project calculated design daily flow is shown calculated on the following table. Project Location: 0 Bayswater Rd —Greenville, NC. The property is vacant land located adjacent to Ignite Church and Legacy at Fire Tower Apartment complex, in the Firetower Junction Subdivision, within Greenville, NC. Extent of Work: This permit is for the installation of 1.260 If of new private 8" sanitary sewer line from center line to centerline of manholes. e Units Q (9Pd) DDF (9pd) DDF (gpm) Peaking Factor QD ( ) 1-Bedroom 121 240 29040 20.17 2.S 50.42 2-Bedroom _ 71 240 I 17040 11.83 2.5 29.58 3-Bedroom 0 360 0 0.31 2.5 0.775 Acreage Clubhouse/Pool 0.5 880 440 Total Permitted DDF Wastewater Facilities Design Flow: $0.8 . Based on 15A NCAC 02T .0114 - WasteWater Desian Flow Rates - P�FESSI 0 SEAL 1 FNGI NEEiP'� Qre 10/7/2024 1 ` Brian K Edwards, PE Project Engineer of Record 107 E. Second Street, Greenville, NC 27858 • PO Box 929, Greenville, NC 27835 • Phone: 252-752-4135 • Fax: 252-752-3974 NCBELS Lic. No. F-0334 www.riversandassociates.com NCBOLA Lic. No. C-312 State of North Carolina Department of Environmental Quality Division of Water Resources FAST TRACK SEWER SYSTEM EXTENSION APPLICATION Division of Water Resources INSTRUCTIONS FOR FORM: ETA 06-21 & SUPPORTING DOCUMENTATION This application is for sewer extensions involving gravity sewers, pump stations and force mains, or any combination that has been certified by a professional engineer and the applicant that the project meets the requirements of 1 jA NCA( 0' I and the Division's Minimum Design Criteria (Gras it% Sc%oci & I'um t Statimis I gi.ce Main_) and that plans, specifications and supporting documents have been prepared in accordance with 15A :N( A(02f. 15A NCAC 02T .0300. Division policies, and good eu¢ioccrine practires. While no upfront engineering design documents are required for submittal, in accordance with 15A NCAC 02T .0305(b), design documents must be prepared prior to submittal of a fast track permit application to the Division. This would include plans, design calculations, and project specifications referenced in I,:\ NCAC 021 .0105 and the applicable minimum design criteria. These documents shall be immediately available upon request by the Division. Projects that are deemed permitted (do not require a permit from the Division) are explained in 15A \CAC 0.: Lo 303. Projects not eligible for review via the fast track process (must be submitted for full technical review): D Projects that do not meet any part of the minimum design criteria (MDC) documents; ➢ Projects that involve more than one variance from the requirements of 15A NCAC 02T; ➢ Pressure sewer systems utilizing simplex septic tank -effluent pumps (STEPS) or simplex grinder pumps; ➢ Simplex STEP or simplex grinder pumps connecting to pressurized systems (e.g. force mains); D Vacuum sewer systems. General — When submitting an application, please use the following instructions as a checklist in order to ensure all required items are submitted. Adherence to these instructions and checking the provided boxes will help produce a quicker review time and reduce the amount of requested additional information. Failure to submit all required Items will necessitate additional processing and review time, and may result in return of the application. Unless otherwise noted, the Applicant shall submit one original and one copy of the application and supporting documentation. A. One Original and One Copy (second copy maybe digital) of Application and Supporting Documents M Required unless otherwise noted. Signatures on original must be "wet ink" or secure digital signatures. Please do not submit engineering design plans with the application unless specifically requested. B. Cover Letter/Narrative Description (Required for All Application Packages): M List all items included in the application package, as well as a brief description of the requested permitting action. ➢ Be specific as to the system type, number of homes served, flow allocation required, etc. D Include the permit number/status of any other required sewer permits (downstream/upstream) ➢ If necessary for clarity, include attachments to the application form. C. Application Fee (All New and Modification Application Packages): M Submit a check or money order in the amount of $480.00, dated no more than 90 days prior to application submittal. ➢ Payable to North Carolina Department of Environmental Quality (NCDEQ) D. Fast Track Application (Required for All Application Packages, Form ETA 05-21): M Submit the completed and appropriately executed application. ➢ if necessary for clarity or due to space restrictions, attachments to the application may be made. ❑ If the Applicant Type in Item 1.2 is a corporation or company, provide documentation it is registered for business with the \orth Carolina Sea -Mary of _Slaw. ❑ If the Applicant Type in Item 1.2 is a partnership or d/b/a, enclose a copy of the certificate filed with the Register of Deeds in the county of business. M The Project Name in Item I1.1 shall be consistent with the project name on the flow acceptance letters, agreements, etc. M The Professional Engineer's Certification on Page 5 of the application shall be signed, sealed and dated by a \rnllr Carolina licensed Piolessional I_ miuco. ❑ The Applicant's Certification on Page 5 of the application shall be signed in accordance with I5A NCAC 021 olo6.Cht. Per 15A NCAC 02T .0106(c), an alternate person may be designated as the signing official if a delegation letter is provided from a person who meets the criteria in I SA NCAC 02T .0106(b). INSTRUCTIONS FOR FORM: FTA 06-21 & SUPPORTING DOCUMENTATION Page 1 of 3 E. Flow Tracking/Acceptance Form (Form: FTSE 04-16) (If Applicable): ❑ Submit the completed and executed FTSE form from the owners of the downstream sewers and treatment facility. D Multiple forms maybe required where the downstream sewer owner and wastewater treatment facility are different. ➢ The flow acceptance indicated in form FTSE must not expire prior to permit issuance and must be dated less than one year prior to the application date. D Submittal of this application and form FTSE indicates that owner has adequate capacity and will not violate Ci_S. 143-215.67t a i. D Intergovernmental agreements or other contracts will not be accepted in lieu of a project -specific FTSE. F. Site Maps (All Application Packages): ® Submit an 8.5-inch x 11-inch color copy of a USGS Topographic Map of sufficient scale to identify the entire project area, including the closest surface waters. ➢ General location of the project components (gravity sewer, pump stations, & force main) ➢ Downstream connection points and permit number (if known) for the receiving sewer ® Include an aerial location map showing general project area (such as street names or latitude/longitude) so that Division staff can easily locate it in the field. G. Existing Permit (Application Packages for Modifications to an Existing Permit): ❑ Submit a copy of the most recently issued existing permit. ❑ Include a descriptive and clear narrative identifying the previously permitted items to remain in the permit, items to be added, and/or items to be modified (the application form itself should include only include items to be added/modified). The narrative should also include whether any previously permitted items have been certified. ❑ The narrative should clearly identify the requested permitting action and accurately describe the sewers to be listed in the final permit. H. Power Reliability Plan (Required if portable reliability option utilized for Pump Station): ❑ Per li/ '_ CAC 1121 n kn5i Il 13, submit documentation of power reliability for pumping stations. ➢ This alternative is only available for average daily flows less than 15,000 gallons per day D It shall be demonstrated to the Division that the portable source is owned or contracted by the applicant and is compatible with the station. The Division will accept a letter signed by the applicant (see 15A NCAC 02T .0106(b)) or proposed contractor, stating that "the portable power generation unit or portable, independently -powered pumping units, associated appurtenances and personnel are available for distribution and operation of this pump station." D If the portable power source or pump is dedicated to multiple pump stations, an evaluation of all the pump stations' storage capacities and the rotation schedule of the portable power source or pump, including travel timeframes, shall be provided in the case of a multiple station power outage. (Required at time of certification) Certificate of Public Convenience and Necessity (All Application Packages for Privately -Owned Public Utilities): ❑ Per 15A NCAC (12.1.01 1 Nu a 1.3 provide the Certificate of Public Convenience and Necessity from the Vonh Carolina l;tilihe5 Commission demonstrating the Applicant is authorized to hold the utility franchise for the area to be served by the sewer extension, or ❑ Provide a letter from the North Carolina Utilities Commission's Rater and Sewer Division Public jiff stating an application for a franchise has been received and that the service area is contiguous to an existing franchised area or that franchise approval is expected. J. Operational Agreements (Applications from HOA/POA and Developers for lots to be sold): ❑ onic I'ro cnv Utvngs' Aasociatious ❑ Per 13A NC'AC02T .01 I iic), submit the properly executed Operational Atrcrment (FORM: HOA ). ❑ Per 15A NCAC 02T .0115(c), submit a copy of the Articles of Incorporation, Declarations and By-laws. ❑ Developersof lots to be sold ❑ Per I SA NCAC (121 .0I 3t+I, submit the properly executed operational AgLcrutm [FORM. DEV). For more information, visit the Division's collection systems u u nits INSTRUCTIONS FOR FORM: FTA 05-21 & SUPPORTING DOCUMENTATION Page 2 of 3 THE COMPLETED APPLICATION PACKAGE INCLDING ALL SUPPORTING INFORMATION AND MATERIALS, SHOULD BE SENT TO THE APPROPRIATE REGIONAL OFFICE: REGIONAL OFFICE ADDRESS Asheville Regional Office 1 2090 USHighway 70 Water Quality Section Swannanoa, North Carolina 28T7"211 (828)296-4500 (828)299-7043 Fax Fayetteville Regional Office 225 Green Street Suite 714 Water Quality Section Fayetteville, North Carolina 28301-5095 (910) 433-3300 (910) 486-0707 Fax COUNTIES SERVED Avery, Buncombe, Burke, Caldwell, Cherokee, Clay, Graham, Haywood, Henderson, Jackson, Macon, Madison, McDowell, Mitchell, Polk, Rutherford, Swain, Transylvania, Yancey Anson, Bladen, Cumberland, Harnett, Hoke, Montgomery, Moore, Robeson, Richmond, Sampson, Scotland Mooresville Regional Office Water Quality Section 610 E. Center Avenue Mooresville, North Carolina 28115 (704) 863-1699 (704)663-6040 Fax Alexander, Cabarrus, Catawba, Cleveland, Gaston, IredelI? Lincoln, Mecklenburg, Rowan, Stanty, Union Raleigh Regional Office 3800 Barrett Drive Chatham, Durham, Edgeoombe, Franklin, Water Quality Section Raleigh, North Carolina 27609 Granville, Halifax, Johnston, Lee, Nash, (919) 791-4200 Northampton, Orange, Person, Vance, Wake, (919) 571.4718 Fax Warren, Wilson Washington Reaionai Office 943 Washington Square Mall Beaufort, Bartle, Camden, Chowen, Craven, Water Quality Section Washington, North Carolina 27889 j Currituck, Dare, Gates, Greene, Hertford, Hyde, (252) 946-6481 Jones, Lenoir, Martin, Pamlico, Pasquotank, (252) 975-3716 Fax Perquimans, Pitt, Tyrrell, Washington, Wayne Wilmington Regional Office 127 Cardinal Drive Extension Brunswick, Carteret, Columbus, Duplin, New water Quality Section Wilmington, North Carolina 28405 Hanover, Onslow, Fender (910)796-7215 (910)350-2004 Fax Winston-Salem Regional Office 450 W. Hanes Mill Road — lamanoe, Alleghany, Ashe, Caswell, Davidson, Water Quality Section Suite 300 Davie, Forsyth, Guilford, Rockingham, Randolph, Winston-Salem, North Carolina 27105 Stokes, Suny, Watauga, Wilkes, Yadkin (336)776-9800 (336) 776-9797 Fax INSTRUCTIONS FOR FORM: FTA 05-21 & SUPPORTING DOCUMENTATION Page 3 of 3 \/ 0\00 4gSS State of North Carolina Department of Environmental Quality Nil R 1 Division of Water Resources FAST TRACK SEWER SYSTEM EXTENSION APPLICATION Division of Water Resources FTA 06-21 & SUPPORTING DOCUMENTATION Application Number: _ _ (to be completed by DWR) All items must be completed or the application will be returned I. APPLICANT INFORMATION: 1. Applicant's name: 221Z LLC (company, municipality, HOA utility, etc.) 2. Applicant type: ❑ Individual ❑ Corporation ® General Partnership ❑ Privately -Owned Public Utility ❑ Federal ❑ State/County ❑ Municipal ❑ Other 3. Signature authority's name: P- e . Kaarides per I SA .CAC 02'1 .01061bm Title: Manager/Partner 4. Applicant's mailing address: 1 128 Independence Boulevard. Suite 200 City:yirieina Beach State: VA Zip:23455-5555 Applicant's contact information: Phonenumber: 757 461-1000 II. PROJECT INFORMATION: Email Address: b3LClroKotarides.com 1. Project name: Ba%s++aterAparments 2. Application/Project status: ® Proposed (New Permit) ❑ Existing Permit/Project If a modification, provide the existing permit number: WQ00 and issued date: _, For modifications, also attach a detailed narrative description as described in Item G of the checklist. If new construction, but part of a master plan, provide the existing permit number: W Q00_ 3. County where project is located: Pitt 4. Approximate Coordinates (Decimal Degrees): Latitude: 35° 33' 08.6" Longitude:-77022' 14.3" 5. Parcel ID (if applicable): 4696407910, 4685497503 (or Parcel ID to closest downstream sewer) III. CONSULTANT INFORMATION: 1. Professional Engineer: Brian Edwards License Number: 043152 Finn: Rivers and Associates. Inc.. Mailing address: 107 E.. Second Sven City: Greem ille State: NC Zip: 27858- Phonen»mber: 252 752-4135 Email Address: •d++ardsrwrivenandassuciates.com IV. WASTEWATER TREATMENT FACILITY (W WTF) INFORMATION: 1. Facility Name: Greenville UtilhicsCommission Permit Number..NCO023931 Owner Name: Greenville Utilities Commission V. RECEIVING DOWNSTREAM SEWER INFORMATION: 1. PermitNtmmber(s): WQ-unknown 2. Downstream (Receiving) Sewer Information: 8 inch 19 Gravity ❑ Force Main 3. System Wide Collection System Permit Number(s) (if applicable): WQCS NC (1023931 Owner Name(s): (it Lvnvi lie I it iiities Comm issiun FORM: FTA 06-21 Page 1 of 5 Vl. GENERAL REQUIREMENTS 1. If the Applicant is a Privately -Owned Public Utility, has a Certificate of Public Convenience and Necessity been attached? ❑ Yes [-]No ® N/A 2. If the Applicant is a Developer of lots to be sold, has a Developer's Operational Agreement (FORM: DEV) been attached? ❑ Yes ❑ No ® N/A 3. If the Applicant is a Home/Property Owners' Association, has an HOA/POA Operational Agreement (FORM: HOA) and supplementary documentation as required by 15A NCAC 02T.0115(c) been attached? ❑ Yes ❑ No ®N/A 4. Origin of wastewater: (check all that apply): ® Residential (Individually Owned) ❑ Retail (stores, centers, malls) ❑ Car Wash ❑ Residential (Leased) ❑ Retail with food preparation/service ❑ Hotel and/or Motels ❑ School / preschool / day care ❑ Medical / dental / veterinary facilities ❑ Swimming Pool/Clubhouse ❑ Food and drink facilities ❑ Church ❑ Swimming Pool/Filter Backwash ❑ Businesses / offices / factories ❑ Nursing Home ❑ Other (Explain in Attachment) 5. Nature of wastewater: 100 %Domestic % Commercial _ % Industrial (See I5A NCAC 02T .0103(20)) If Industrial, is there a Pretreatment Program in effect? ❑ Yes❑ No 6. Hasa flow reduction been approved under 15A NCAC 02T .0114(fl? [-]Yes ®No ➢ If yes, provide a copy of flow reduction approval letter with this application 7. Summarize wastewater generated by project: Establishment Type (see 02T.0114(t)) Daily Design Flow 0 No. of Units Flow 1-Bedroom Apartment 75 gal/day 117 8,775 GPD 2-Bedroom Apartment 150 gal/day 71 10,650 GPD Clubhouse/Pool 880 gal/ac/day 0.5 440 GPD gal/ GPD gal/ GPD gal/ GPD Total 19,865 GPD a See 15A NCAC 02T .0114(b), (d), (e)(1) and (e)(2) for caveats to wastewater design flow rates (i.e., minimum flow per dwelling; proposed unknown non-residential development uses; public access facilities located near high public use areas; and residential property located south or east of the Atlantic Intracoastal Waterway to be used as vacation rentals as defined in G.S. 42A-4). b Per 15A NCAC 02T .0114(c), design flow rates for establishments not identified [in table 15A NCAC 02T.01141 shall be determined using available flow data, water using fixtures, occupancy or operation patterns, and other measured data. 8. Wastewater generated by project: 46 080 GPD (per 15A NCAC 02T .0114) ➢ Do not include future flows or previously permitted allocations If permitted flow is zero, please indicate why: ❑ Pump Station/Force Main or Gravity Sewer where flow will be permitted in subsequent permits that connect to this line. Please provide supplementary information indicating the approximate timeframe for permitting upstream sewers with flow. ❑ Flow has already been allocated in Permit Number: Issuance Date: ❑ Rehabilitation or replacement of existing sewers with no new flow expected ❑ Other (Explain): FORM: FTA 06-21 Page 2 of 5 VIL GRAVITY SEWER DESIGN CRITERIA (If Applicable) Se%,C,-%): 1. Summarize gravity sewer to be permitted: Size (inches) Length (feet) Material 8 1,260 PVC ::�4— ➢ Section 11 & ID of the MDC for Permitting of Gravity Sewers contains information related to design criteria ➢ Section III contains information related to minimum slopes for gravity sewer(s) ➢ Oversizing lines to meet minimum slope requirements is not allowed and a violation of the MDC VIII. PUMP STATION DESIGN CRITERIA (If Applkable)-02T .0305 & MDC- (Pump Slations/Force Mains): PROVIDE A SEPARATE COPY OF -I HIS PALL FOR L-ACH PUMP STATION INCLUDED IN TI IIs_PROJECi 1. Pump station number or name: 2. Approximate Coordinates (Decimal Degrees): Latitude: ° Longitude: - ° 3. Total number of pumps at the pump station: 3. Design flow of the pump station: millions gallons per day (firm capacity) ➢ This should reflect the total GPM for the pump station with the largest pump out of service. 4. Operational point(s) per pump(s): gallons per minute (GPM) at _ feet total dynamic head (TDH) 5. Summarize the force main to be permitted (for this Pump Station): Size (inches) ' Length (feet) MaterialIL If any portion of the force main is less than 4-inches in diameter, please identify the method of solids reduction per MDCPSFM Section 2.01C-Lb. ❑ Grinder Pump ❑ Mechanical Bar Screen ❑ Other (please specify) 6. Power reliability in accordance with I5A NCAC 02T .0305(h)41 : ❑ Standby power source or ❑ Standby pump ➢ Must have automatic activation and telemetry - 15A NCAC 02T.0305(h)(1)(B)_ ➢ Required for all pump stations with an average daily flow greater than or equal to 15,000 gallons per day ➢ Must be permanent to facility and may not be portable Or if the pump station has an average daily flow less than 15,000 gallons per day 15A NCACO2T.0305(h)(1)(C): ❑ Portable power source with manual activation, quick -connection receptacle and telemetry - or ❑ Portable pumping unit with plugged emergency pump connection and telemetry: ➢ Include documentation that the portable source is owned or contracted by the applicant and is compatible with the station. ➢ If the portable power source or pump is dedicated to multiple pump stations, an evaluation of all the pump stations' storage capacities and the rotation schedule of the portable power source or pump, including travel timeframes, shall be provided as part of this permit application in the case of a multiple station power outage. FORM: FTA 06-21 Page 3 of 5 Ix SETBACKS & SEPARATIONS —(02B.0200&ISA NCACO2T.0305(t)). 1. Does the project comply with all separations/alternatives found in 15A NCAC 02T .0305(f) R (s)? ® Yes ❑ No 15A NCAC 02T.0305(f) contains minimum lions that shall be vided for sewer systems: Setback Parameter" Separation Required Strom sewers and other utilities not listed below (vertical) 18 inches 2Water mains (vertical - water over sewer preferred, including in beached trenches) IS inches 1Water mains (horizontal) 10 feet Reclaimed water lines (vertical - reclaimed over sewer) 18 inches Reclaimed water lines (horizontal - reclaimed over sewer) 2 feet "Any private or public water supply source, including any wells, WS-I waters of Class I or Class II impounded reservoirs used as a source of drinking water, and associated wetlands. 100 feet "Waters classified WS (except WS-I or WS-V), B, SA, ORW, HQW, or SB from normal high water (or tide elevation) and wetlands associated with these waters (see item IX2) 50 feet "Any other stream, lake, impoundment, or ground water lowering and surface drainage ditches, as well as wetlands associated with these waters or classified as WL. 10 feet Any building foundation (horizontal) 5 feet Any basement (horizontal) 10 feet Top slope of embankment or cuts of 2 feet or more vertical height Drainage systems and interceptor drams — 10 feet 5 feet 10 feet Amy swimming 1wis Final earth !fie (vtzticei) Witches r if noncompliance with 02T.0305(f) or W. see Section X.1 of this application "I5A NCAC 02'L0305(c) contains alternatives where separations in u2'f.0305(f) cannot be achieved. Please check "yes" above if these alternatives are used and provide narrative information to explain. "Stream classifications ran be identified using the Division's NC' Surface t1'ater Classifications wcbpagc 2. Does this project comply with the minimum separation requirements for water mains? ®Yes ❑ No [:]N/A ➢ If no, please refer to 15A NCAC I SC.0906(f) for documentation requirements and submit a separate document, signed/scaled by an NC licensed PE, verifying the criteria outlined in that Rule. 3. Does the project comply with separation requirements for wetlands? ® Yes ❑ No ❑ N/A D Please provide supplementary information identifying the areas of non-conformance. ➢ See the Division's Jlpftsel±araiiun rcuuirrmems for situations where separation cannot be met ➢ No variance is required if the alternative design criteria specified is utilized in design and construction. 4. Is the project located in a river basin subject to any State buffer rules? ® Yes Basin name: Neuse ❑ No If yes, does the project comply with setbacks found in the river basin rules per 15.A NCAC 02 B .0'00" ® Yes ❑ No ➢ This includes Trout Buffered Streams per I SA NCAC 2B.0202 5. Does the project require coverage/authorization under a 404 Nationwide/individual permits ❑ Yes ® No or 401 Water Quality Certifications? ➢ Please provide the permit number/permitting status in the cover letter if coverage/authorization is required. 6. Does project comply with 15A NCAC 027.0105(c)(6) (additional permits/certifications)? ® Yes ❑ No Per 15:1 NCAC 02"f.0105(c1(6 ), directly related environmental permits or certification applications must be being prepared, have been applied for, or have been obtained. Issuance of this permit is contingent on issuance of dependent permits (erosion and sedimentation control plans, stormwater management plans, etc.). 7. Does this project include any sewer collection lines that are deemed "high -priority?" ❑ Yes ® No Per 15A NCAC 02'1.(NO2, "high -priority sewer" means any aerial sewer, sewer contacting surface waters, siphon, or sewers positioned parallel to streambanks that are subject to erosion that undermines or deteriorates the sewer. Siphons and sewers suspended through interference/conflict boxes require a variance approval. ➢ If yes, include an attachment with details for each line, including type (aerial line, size, material, and location). High priority lines shall be inspected by the permittee or its representative at least once every six -months and inspections documented per 15A NCAC 02T.0403(a)(5) or the permittee's individual System -Wide Collection permit. FORM: FTA 06-21 Page 4 of 5 X. CERTIFICATIONS: I. Does the submitted system comply with I5A NCAC 02T. the Minimum Design Criteria for [lie Penniuine of Pump Stations and Force Mains i latest_%ersioni. and the Gras ity Sewer Minimum Design Criteria (latest version I as applicable? ® Yes ❑ No If no, for projects requiring a single variance, complete and submit the Variance/Altemative Design Request application (VADC 10.14) and supporting documents for review to the Central Office. Approval of the request will be issued concurrerilk svilh the approval of the permit and proieets requiring a %anince apm'ovai mas he sub eel to longer review times. For proiecls requiring No or more variances or where the variance is determined bs the Division ID be a significant portion of the project. the full technical re%iew is required. 2. Professional Engineers Certification: I, Brian K. Edwards , attest that this application for Bayswater Apartments (Rofessional Engineer's name Cram Application Item III.1) (PwJM Name from Application Item II.1) has been reviewed by me and is accurate, complete and consistent with the Information supplied in the plans, specifications, engineering calculations, and all other supporting documentation to the best of my knowledge. I further attest that to the best of my knowledge the proposed design has been prepared in accordance with the applicable regulations, Minimum Design Criteria for Gravity Sewers (latest %ersion), and the Minimum Design Criteria for the Fast -Track Permiuine of Pump Stations and Force Mains I latest version i. Although other professionals may have developed certain portions of this submittal package, inclusion of these materials under my signature and seal signifies that I have reviewed this material and have judged it to be consistent with the proposed design. NOTE — In accordance with General Statutes 143-215.6A and 143-215.6B, any person who knowingly makes any false statement, representation, or certification in any application package shall be guilty of a Class 2 misdemeanor, which may include a fine not to exceed $10,000, as well as civil penalties up to $25,000 per violation. Misrepresentation of the application information, including failure to disclose any design non-compliance with the applicable Rules and design criteria, may subject the North Carolina -licensed Professional Engineer to referral to the licensing board. (21 NC AC'S65,01) North Carolina Professional Engineer's seal, signature, and date: �.: SEAL 1 6Y 711ZM 3. Applicant's Certification per 15A NCAC 02T .o106(b): 1, Pete 0. Kotarides _ . attest that this application for Bayswater Apartments (Signature Anthirity Name from Application Item I.3.) (Pmject Name from Application Item 0.1) attest that this application has been reviewed by me and is accurate and complete to the best of my knowledge. I understand that if all required parts of this application are not completed and that if all required supporting documentation and attachments are not included, this application package is subject to being returned as incomplete. I understand that any discharge of wastewater from this non -discharge system to surface waters or the lend will result in an immediate enforcement action that may include civil penalties, injunctive relief, and/or criminal prosecution. I will make no claim against the Division of Water Resources should a condition of this permit be violated I also understand that if all required parts of this application package are not completed and that if all required supporting information and attachments are not included, this application package will be returned to me as incomplete. NOTE — In accordance with General Statutes 143-215.6A and 143-215.6B any person who knowingly makes any false statement, representation, or certification in any application package shall be guilty of a Class 2 misdemeanor, which may include a fine not to exceed $10,000 as well as civil penalties up to $25,000 per violation. Signature: Date: 511 7 / 7-" 1 FORM: FTA 06-21 Page 5 rrf 5 ,X 14 Greenville .�_ Utilities October 8, 2024 Mr. Pete 0. Kotarides 2952 LLC 1128 Independence Blvd. Virginia Beach, VA 2345'_ Subject: Proposed Bayswater Apartments Pitt County Tax Parcel 89239 Intersection of Bayswater Drive & Legacy Court Public Water & Sanitary Sewer Service Availability/Capacity to Serve Dear Mr. Kotarides: This will confirm Greenville Utilities Commission's (GUC) willingness and capacity to serve the subject project with potable water and sanitary sewer. Water service is available to the project site via a 10-inch main located on the north side of Bayswater Drive and an 8-inch main located on the west side of Legacy Court. The GUC water system has adequate capacity for the proposed domestic design demand of 19,865 gallons per day. Sanitary sewer service is available to the project site via an 8-inch main located on the property at the southeast corner. The GUC sewer system has adequate capacity to accommodate the peak Flows associated with the proposed domestic design water demand of 19,865 gallons per day. The receiving facility will be Greenville Utilities Commission Wastewater Treatment Plant (NC0023931). If you should have any questions or require any additional information concerning this matter, please contact me at 252-551-3386 or at cahoonchCa)guc.com. Sincerely, LyL/ Clifton H. Cahoon, P.E. Water Resources Construction/Contracts Engineer Cc: Mr. David Springer, PE, Director of Water Resources Mr. Brian Edwards, PE, Rivers and Associates Connected To You Port Office Box 1847 1 Greenville, North Carolina 27835-1847 1 guc.com 1 252-752-7166 State of North Carolina Department of Environmental Quality Division of Water Resources Flow Tracking/Acceptance for Sewer Extension Applications (FTSE 04-16) Entity Requesting Allocation: 2952 LLC Project Name for which flow is being requested: Bayswater Apartments More than one ME may be required for a single project if the owner of the WWTP is not responsible for all pump stations along the route of theproposed wastewater flow. I. Complete this section only if you are the owner of the wastewater treatment plant. a. WWTP Facility Name: Greenville Utilities Commission b. WWTP Facility Permit #: NC0023931 All flows are in MGD c. WWTP facility's permitted flow d. Estimated obligated flow not yet tributary to the WWTP e. WWTP facility's actual avg. flow f. Total flow for this specific request g. Total actual and obligated flows to the facility h. Percent of permitted flow used 17.5 2.833 10.426 .0199 13.279 75.878 II. Complete this section for each pump station you are responsible for along the route of this proposed wastewater flow. List pump stations located between the project connection point and the WWTP: (A) Design Pump Average Daily Station Firm Flow" (Name or Capacity, " (Firm / pt), Number) MGD MGD Southside 30.259 12.104 (B) (C) (D)=(B+C) (EMA-D) Obligated, Approx. Not Yet Total Current Current Avg. Tributary Flow Plus Daily Flow, Daily Flow, Obligated Available MGD MGD Flow Capacity*** 5.791 _1.601 7.392 4.712 For 6.513 2.605 1.618 .176 1.794 .811 * The Firm Capacity of any pump station is defined as the maximum pumped flow that can be achieved with the largest pump taken out of service. ** Design Average Daily Flow is the firm capacity of the pump station divided by a peaking factor (pf) not less than 2.5. *** A Ph► wing Assessment Addendum shall be attached for each pump station located between the project connection point and the WWTP where the Available Capacity is < 0. Downstream Facility Name (Sewer): Unknown Downstream Permit Number: Unknown Page 1 of 6 FTSE 04-16 III. Certification Statement: I Clifton H. Cahoon, PE certify to the best of my knowledge that the addition of the volume of wastewater to be permitted in this project has been evaluated along the route to the receiving wastewater treatment facility and that the flow from this project is not anticipated to cause any capacity related sanitary sewer overflows or overburden any downstream pump station en route to the receiving treatment plant under normal circumstances, given the implementation of the planned improvements identified in the planning assessment where applicable. This analysis has been performed in accordance with local established policies and procedures using the best available data. This certification applies to those items listed above in Sections I and II plus all attached planning assessment addendum s for which I am the responsible party. Signature of this form indicates acceptance of this wastewater flow. Page 2 of 6 FTSE 04-16 Average Yearly Flow for: Jan.2023 Feb.2023 Mar.2023 Apr.2023 May2023 Jun2023 Ju12023 Aug2023 Sept2023 Oct2023 Nov2023 Dec2023 GUC, NCO023931 Permitted Flow: 9.9419355 11.4857143 10.5709677 11.4533333 9.8709677 9.7386667 9.9377419 10.1190323 11.5666667 10.4516129 9.4966667 10.6451613 10.43987225 Avg. Flow 2023 % of Permitted Flow 17.50 0.596564129 (< 80% / 90% 0K) 9/5/24, 10:10 AM North Carolina Secretary of State Search Results • File an Annual Report/Amend an Annual Report • Upload a PDF Filing • Order a Document Online Add Entity to My Email Notification List • View Filings • Print a Pre -Populated Annual Report form • Print an Amended a Annual Report form Limited Liability Company Legal Name 2952 LLC Information Sosld: 2517230 Status: Current -Active O Date Formed: 11/3/2022 Citizenship: Foreign State of Incorporation: VA Annual Report Due Date: April 15th Currentgnnual Report Status: Registered Agent: CT Corporation System Addresses Mailing Principal Office 1128 Independence Boulevard, Suite 200 1128 Independence Boulevard, Suite 200 Virginia Beach, VA 23455-5555 Virginia Beach, VA 23455-5555 Reg Office Reg Mailing 160 Mine Lake Ct Ste 200 160 Mine Lake Ct Ste 200 Raleigh, NC 27615 Company Officials Raleigh, NC 27615 All LLCs are managed by their managers pursuant to N.C.G.S. 57D-3-20. https://w .sosnc.gov/online_services/search/Business_Registration_Results 1/2 9/5124, 10:10 AM North Carolina Secretary of State Search Results Manager Basil O. Kotarides 1128 Independence Blvd Suite 200 Virginia Beach VA 23455-5555 Manager Pete O. Kotarides 1128 Independence Blvd Suite 200 Virginia Beach VA 23455-5555 Manager Kotarides Holdings LLC 1128 Independence Blvd Suite 200 Virginia Beach VA 23455-5555 Manager Pete Alex Kotarides 1128 Independence Blvd Suite 200 Virginia Beach VA 23455-5555 Manager Petro A. Kotarides 1128 Independence Blvd Suite 200 Virginia Beach VA 23455-5555 2/2 Bayswater Apartments — USGS Topographical Map c � F \4. t1EI .r._- 38 37 At ON y— 36 . % r 35 -WINTER � Portion of USGS Topographical Map- Greenville SE Quadrangle North Carolina - Pitt County 7.5-minute series e�� Toppen, Sarah A From: Brian Edwards <bedwards@riversandassociates.com> Sent: Thursday, September 5, 2024 9:28 AM To: Toppen, Sarah A Cc: Clay Johnston Subject: [External] Re: Additional Information Needed for Bayswater Apartment Fast Track Application Attachments: FTSE 04-16.pdf IYou don't often get email from bedwards@riversandassociates.com. learn why this is important CAUTION: External email. Do not click links or open attachments unless verified. Report suspicious emails with the Report Message button located on your Outlook menu bar on the Home tab. Hi Sarah, Please find attached the requested form executed attached. Do you need a hard copy mailed to you? Thanks, Brian Edwards, PE Project Engineer 11 W: (252) 752-4135 C. (252) 350-0946 Rivers & Associates Inc 107 E 2nd St Greenville, NC 27858 "For every house is built by someone, but God is the builder of everything." Hebrews 3:4 From: Brian Edwards <bedwards@ rive rsandassociates.com> Sent: Wednesday, September 4, 2024 1:29 PM To: Toppen, Sarah A <Sarah.Toppen@deq.nc.gov> Cc: Clay Johnston <johnstcp@guc.com> Subject: Re: Additional Information Needed for Bayswater Apartment Fast Track Application Hi Sarah, Apologies I let this email slip. I will have GUC sign anew copy and email to you a scan and mail the hard copy, hopefully have it by end of the week. That would bean incorrect error, if you can please mark that on the application. Thanks, Brian Edwards, PE Project Engineer /l W: (252) 752-4135 C: (252) 350-0946 Rivers & Associates Inc 107 E 2nd St, Greenville, NC 27858 "For every house is built by someone, but God is the builder of everything." Hebrews 3:4 From: Toppen, Sarah A <Sarah.Toppen@deq.nc.gov> Sent: Friday, August 23, 2024 2:53 PM To: Brian Edwards <bedwards@riversandassociates.com> Subject: Additional Information Needed for Bayswater Apartment Fast Track Application Good afternoon Brian, I am reviewing the Bayswater Apartments Fast Track Application. I see that the wastewater generated by the project is 19,425 gpd but I cannot find the flow tracking application completed by GLIC. Do you have a copy of that? Also, on page 2 of 5, number eight on the application you have 46,080 gpd listed as the wastewater generate bythe project. I assume this is wrong and maybe left from a prior project. If it is let me know and I can mark through it and state that on the application as an error. Let me know if you have any questions and I will start working on the permit once I receive the needed additional information. Kind Regards, Sarah Sarah A Toppen Environmental Specialist II Division of Water Resources Water Quality Regional Operations 252-948-3918 office 252-402-6155 mobile Sarah. Toppen no.deo.nc.gov Email 943 Washington Square Mall Washington NC 27889 Email correspondence to and from this address may be subject to the North Carolina Public Records Law and may be disclosed to third parties by an authorized stale official. State of North Carolina Department of Environmental Quality Division of Water Resources Dhision of kcsourccs Flow Tracking/Acceptance for Sewer Extension Applications (FTSE 04-16) Entity Requesting Allocation: 2952 LLC Project Name for which flow is being requested: Bay swater Apartments More than one ME maybe required for a single project if dw owner of the WWTP is not responsible for all psmp stations along the route of the proposed wastewater flow. I. Complete this section only if you are the owner of the wastewater treatment plant. a. WWTP Facility Name: Greenville Utilities Commission b. WWTP Facility Permit#: NC0023931 All flows are in MGD c. WWTP facility's permitted flow 17.5 d. Estimated obligated flow not yet tributary to the WWTP 2.87 e. WWTP facility's actual avg. flow 10.426 f. Total flow for this specific request g. Total actual and obligated flows to the facility h. Percent of permitted flow used .0194 13.316 76.090 II. Complete this section for each pump station you are responsible for along the route of this proposed wastewater flow. List pump stations located between the project connection point and the WWTP: (A) (B) (C) (D)=(B+C) (E)=(A-D) Design Obligated, Pomp Average Daffy Approx. Not yet Total Current Station Firm Flow" Curtest Avg. Tributary Flow Plus (Name or Capacity, ` (Firm / pf), Daily Flow. Daily Flow, Obligated Available Number) MGD MGD MGD MGD Flow Capacity**' Southside 30.259 12.104 5.791 1.581 7.372 4.732 Fork 6.513 2.605 1.618 156 1.774 .831 * The Firm Capacity of any pump station is defined w the maximum pumped flow that can be achieved with the largest pump taken out of service. ** Design Average Daily Flow is the firm capacity of the pump station divided by a peabing factor (pf) not leas than 2.5. *** A Planning Assessment Addendum shall be attached for each pump station located between the project connection point and the WWTP where the Available Capacity is < 0. Downstream Facility Name (Sewer): Unknown Downstream Permit Number. Unknown Page 1 of 6 FTCF. (14-1 A III. Certification Statement: I Clifton H. Cahoon, PE certify to the best of my knowledge that the addition of the volume of wastewater to be permitted in this project has been evaluated along the route to the receiving wastewater treataent facility and that the flow from this project is not anticipated to cause any capacity related sanitary sewer overflows or overburden any downstream pump station en route to the receiving treatment plant under normal circumstances, given the implementation of the planned improvements identified in the planning assessment where applicable. This analysis has been performed in accordance with local established policies and procedures using the best available data. This certification applies to those items listed above in Sections I and II plus all attached planning assessment addendums for which I am the responsible party_ Signature of this form indicates acceptance of this wastewater flow. SIgni Official Signature Date -- Page 2 of 6 FTSF 04-16 ,N-Mivers ENGINEERS PLANNERS SURVEYORS 6 ASSOCIATES, INC SANITARY SEWER NARRATIVE Bayswater Apartments (Greenville, NQ — Proj. #: 2022044 Service Area Description: This sewer system is to serve an 12+/- acres site of which 11 acres are developed for the purpose of a multi -family residential site. The proposed project consists of 5 Apartment Buildings, a Clubhouse and pool area, private access and parking, sidewalks, mail kiosk, and other features as depicted on the plans. Calculated Design Flow The calculated design flow is shown by the chart below. Daily flow rates are determined based upon the recommendations for daily design flow from 15A NCAC 02T .0714 - WasteWater Design flow Rates; multiplied by a peaking factor of 2.5. The project calculated design daily flow is shown calculated on the following table. C- Total Permitted DDF Wastewater Facilities Design Flow: 80.0 Project Location: 0 Bayswater Rd —Greenville, INC. LANDSCAPE ARCHITECTS The property is vacant land located adjacent to Ignite Church and Legacy at Fire Tower Apartment complex, in the Firetower Junction Subdivision, within Greenville, NC. Extent of Work: This permit is for the installation of 1,260 If of new private 8" sanitary sewer line from center line to centerline of manholes. 'X'-Bedroom A - Units Q (gl DDF (gl DDF (g m) Peaking Factor QD (gpm) 1-Bedroom 121 240 29040 20.17 2.5 50.42 2-Bedroom 71 240 17040 11.83 2.5 29.S8 3-Bedroom 0 360 0 0.00 2.5 0.00 _ 'X' • 120 " Based on 15A NCAC 02T .0114 - Wastewater Desion Flow SEAL 043152 01/09/2023 Brian K Edwards, PE Project Engineer of Record 107 E, Second Street, Greenville, NC 27858 a PO Box 929, Greenville, NC 27835 a Phone: 252-752-4135 a Fax: 252-752-3974 NCBELS Lic. No. F-0334 www.riversandassociates.com NCBOLA Lic. No. C-312 Greenville .X_I Utilities August 1, 2024 Mr. Pete 0. Kotarides 2952 LLC 1128 Independence Blvd. Virginia Beach, VA 234SS RECEIVED/NCDENR/DWR AUG 19 ?V`4 Water Quality Regional Operations Section Washington Regional Office Subject: Proposed Bayswater Apartments Pitt County Tax Parcel 89239 Intersection of Bayswater Drive & Legacy Court Public Water & Sanitary Sewer Service Availability/Capacity to Serve Dear Mr. Kotarides: This will confirm Greenville Utilities Commission's (GUC) willingness and capacity to serve the subject project with potable water and sanitary sewer. Water service is available to the project site via a 10-inch main located on the north side of Bayswater Drive and an 8-inch main located on the west side of Legacy Court. The GUC water system has adequate capacity for the proposed domestic design demand of 19,425 gallons per day. Sanitary sewer service is available to the project site via an 8-inch main located on the property at the southeast corner. The GUC sewer system has adequate capacity to accommodate the peak flows associated with the proposed domestic design water demand of 19,425 gallons per day. The receiving facility will be Greenville Utilities Commission Wastewater Treatment Plant (NCO023931). If you should have any questions or require any additional information concerning this matter, please contact me at 252-551-3386 or at cahoonch(Mguc.com. Sincerely, ,41 Clifton H. Cahoon, P.E. Water Resources Construction/Contracts Engineer Cc: Mr. David Springer, PE, Director of Water Resources w9r. Brian Edwards, PE, Rivers and Associates Connected To You Post Office Box 1847 1 Greenville, North Carolina 27835-1847 1 guc.com 1 252-752-7166 Bayswater Apartments — USGS Topographical Map Bell ( Fvr Fork38 oN, RO O 4{ IIANN(PSNIIF DF 9 - I., 43r /.PAP I- O 37 d I� � P 36 i fPP'F 35 %'IINTERVII.LE i3 f� - c Portion of USGS Topographical Map— Greenville SE Quadrangle North Carolina — Pitt County 7.5-minute series