HomeMy WebLinkAboutWQCS00372_WQCS00372 CEI Response Letter 20240930_20240926 (2)/
September 26, 2024
Vanessa Manuel
Assistant Regional Supervisor
Water Quality Regional Operations Section
Raleigh Regional Office
Division of Water Resources, NCDEQ
Subject: Compliance Evaluation Inspection
Briar Chapel Collection System
WWCS Permit WQC00372
Chatham County, NC
Re: Collection Inspection Response
Dear Vanessa Manuel,
ONSWC is in receipt of your request for response to items 4 and 6 noted in the compliance inspection evaluation dated July 18,2024.
In response to item 4. Contingency Plan for Pump Failure:
ONSWC staff determined to purchase an additional bypass pump rather than installing generators at the lift stations in question. A portable bypass pump provides redundancy as it can
be used in emergencies at various other sewer lift stations.
Your office requested a current list of all Briar Chapel duplex pump stations to include identification, physical address, capacity, emergency power supply and remote monitoring capabilities.
The list is as follows.
BC L/S Name
ADDRESS
Generator
Pump 1
Pump 2
Crane
SCADA
Pump Capacity
16N
85 Cliffridge Court
No
13 HP - 460V
13 HP - 460V
Y
M
115 GPM
A
77 Turtle Point Bend
Yes
100 HP - 480V
100 HP - 480V
Y
M
676 GPM
B
1146 Great Ridge Parkway
Yes
15 HP - 480V
15 HP - 480V
Y
M
386 GPM
C
260 Taylor Road
Yes
30.8 HP - 460V
30.8 HP - 460V
N
M
180 GPM
D
187 Tyner Loop Circle
No
60.7 HP - 460V
60.7 HP - 460V
Y
M
360 GPM
E
88 Quarter Gate Trace
No
15 HP - 460V
15 HP - 460V
Y
M
145 GPM
F
149 Landover Circle
No
13 HP - 460V
13 HP - 460V
Y
M
115 GPM
G
651 S. Rosebank Drive
No
40 HP - 460V
40 HP - 460V
Y
M
260 GPM
H
111 Monteith Drive
Yes
30 HP - 460V
30 HP - 460V
Y
M
260 GPM
I
216 Birch Hollow Road
No
17.4 HP - 460V
17.4 HP - 460V
Y
M
130 GPM
J
326 Deardom Way
Yes
61 HP - 460V
61 HP - 460V
Y
M
200 GPM
S.D.E
9090 US-15 North
Pump
161HP - 480V
161HP - 480V
N
VT
1125 GPM
W.C
138 Woodland Grove Lane
No
480V
480V
N
M
825 GPM
Your office requested our contingency plan updated to include specific response and deployment of mobile generators and pumps in the event of pump failures.
Please find our Emergency Response Plan attached with the requested information.
In response to item 6. Pump Station Signage.
To comply with the missing identification of pump station A and WC, we have posted the following signs.
/
Woods Charter Lift Station sign.
/
In response to 5 g, please find a photo of the Indigo manhole cleaned of all debris.
/
We believe we have addressed the requests related to the Briar Chapel Compliance Evaluation Inspection. Please let us know if you have any questions or additional information is needed.
Sincerely,
/
President, ONSWC
jmcdonald@onswc.com
P.O.Box 10127
Birmingham, AL 35202
Cc: Chip White
Zac Combs
Sean McMillan
Daniel Allred