Division of Water Resources Reg Water Quali FAST TRACK SEWER SYSTEM EXTENSION APPLICATION
I �FOR FORM: FTA 10-23 & SUPPORTING DOCUMENTATION
Was ington Regional nr.; or'
This application is for sewer extensions involving gravity sewers, pump stations and force mains, or any combination that has been
certified by a professional engineer and the applicant that the project meets the requirements of 15A NCAC 02T and the Division's
Minimum Design Criteria (Gravity Sewer & Pump Stations/Force Mains) and that plans, specifications and supporting documents
have been prepared in accordance with 15A NCAC 02T, 15A NCAC 02T 0300 Division policies, and good engineering practices.
While no upfront engineering design documents are required for submittal, in accordance with 15A NCAC 02T .0305(b), design
documents must be prepared prior to submittal of a fast track permit application to the Division. This would include plans, design
calculations, and project specifications referenced in 15A NCAC 02T .0305 and the applicable minimum design criteria. These
documents shall be immediately available upon request by the Division.
Projects that are deemed permitted (do not require a permit from the Division) are explained in 15A NCAC 02T.0303.
Projects not eligible for review via the fast track process (must be submitted for full technical review):
➢ Projects that do not meet any part of the minimum design criteria (MDC) documents;
➢ Projects that involve more than one variance from the requirements of 15A NCAC 02T,
➢ Pressure sewer systems utilizing simplex septic tank -effluent pumps (STEPs) or simplex grinder pumps;
➢ Simplex STEP or simplex grinder pumps connecting to pressurized systems (e.g. force mains);
➢ Vacuum sewer systems.
General — When submitting an application, please use the following instructions as a checklist in order to ensure all required items are
submitted. Adherence to these instructions and checking the provided boxes will help produce a quicker review time and reduce the
amount of requested additional information. Failure to submit all required items will necessitate additional processing and review
time, and may result in return of the application. Unless otherwise noted, the Applicant shall submit one original and one copy of
the application and supporting documentation.
A. One Original and One Copy (second copy maybe digital) of Application and Supporting Documents
❑ Required unless otherwise noted. Signatures on original must be "wet ink" or secure digital signatures.
Please do not submit engineering design plans with the application unless specifically requested.
B. Cover Letter/Narrative Description (Required for All Application Packages):
❑ List all items included in the application package, as well as a brief description of the requested permitting action.
➢ Be specific as to the system type, number of homes served, flow allocation required, etc.
➢ Include the permit number/status of any other required sewer permits (downstream/upstream)
➢ If necessary for clarity, include attachments to the application form.
C. Application Fee (All New and Modification Application Packages):
❑ Submit a check or money order in the amount of $600.00, dated no more than 90 days prior to application submittal.
➢ Payable to North Carolina Department of Environmental Quality (NCDEQ)
D. Fast Track Application (Required for All Application Packages, Form FTA 10-23):
❑ Submit the completed and appropriately executed application.
➢ If necessary for clarity or due to space restrictions, attachments to the application may be made.
❑ If the Applicant Type in Item 1.2 is a corporation or company, provide documentation it is registered for business with the
North Carolina Secretary of State.
❑ If the Applicant Type in Item 1.2 is a partnership or d/b/a, enclose a copy of the certificate filed with the Register of Deeds in
the county of business.
❑ The Project Name in Item 11.1 shall be consistent with the project name on the flow acceptance letters, agreements, etc.
❑ The Professional Engineer's Certification on Page 5 of the application shall be signed, seated and dated by a North Carolina
licensed Professional Engineer.
❑ The Applicant's Certification on Page 5 of the application shall be signed in accordance with 15A NCAC 02T 0106(b1. Per
15A NCAC 02T .0106(c), an alternate person may be designated as the signing official if a delegation letter is provided from
a person who meets the criteria in 15A NCAC 02T .0106(b).
INSTRUCTIONS FOR FORM: FTA 10-23 & SUPPORTING DOCUMENTATION Pagel of 3
E. Flow Tracking/Acceptance Form (Form: FTSE 10-23) (If Applicable):
❑ Submit the completed and executed FTSE form from the owners of the downstream sewers and treatment facility.
➢ Multiple forms maybe required where the downstream sewer owner and wastewater treatment facility are different.
➢ The flow acceptance indicated in form FTSE must not expire prior to permit issuance and must be dated less than one year
prior to the application date.
➢ Submittal of this application and forth FTSE indicates that owner has adequate capacity and will not violate G.S. 143-215.67(a).
➢ Intergovernmental agreements or other contracts will not be accepted in lieu of a project -specific FTSE.
Site Maps (All Application Packages):
❑ Submit an 8.5-inch x 1 I -inch color copy of a USGS Topographic Map of sufficient scale to identify the entire project area,
including the closest surface waters.
➢ General location of the project components (gravity sewer, pump stations, & force main)
➢ Downstream connection points and permit number (if known) for the receiving sewer
❑ Include an aerial location map showing general project area (such as street names or latitude/longitude) so that Division staff
can easily locate it in the field.
G. Existing Permit (Application Packages for Modifications to an Existing Permit):
❑ Submit a copy of the most recently issued existing permit.
❑ Include a descriptive and clear narrative identifying the previously permitted items to remain in the permit, items to be
added, and/or items to be modified (the application form itself should include only include items to be added/modified). The
narrative should also include whether any previously permitted items have been certified.
❑ The narrative should clearly identify the requested permitting action and accurately describe the sewers to be listed in
the final permit.
H. Power Reliability Plan (Required if portable reliability option utilized for Pump Station):
❑ Per 15A NCAC 02T .0305(h)(I ), submit documentation of power reliability for pumping stations.
➢ This alternative is only available for average daily flows less than 15,000 gallons per day
➢ It shall be demonstrated to the Division that the portable source is owned or contracted by the applicant and is compatible with
the station. The Division will accept a letter signed by the applicant (see 15A NCAC 02T .0106(b)) or proposed contractor,
stating that "the portable power generation unit or portable, independently -powered pumping units, associated appurtenances
and personnel are available for distribution and operation of this pump station."
➢ If the portable power source or pump is dedicated to multiple pump stations, an evaluation of all the pump stations'
storage capacities and the rotation schedule of the portable power source or pump, including travel timeframes, shall
be provided in the case of a multiple station power outage. (Required at time of certification)
Certificate of Public Convenience and Necessity (All Application Packages for Privately -Owned Public Utilities):
❑ Per 15A NCAC 02T .01 Wall I) provide the Certificate of Public Convenience and Necessity from the North Carolina Utilities
Commission demonstrating the Applicant is authorized to hold the utility franchise for the area to be served by the sewer
extension, or
❑ Provide a letter from the North Carolina Utilities Commission's Water and Sewer Division Public Staff stating an application
for a franchise has been received and that the service area is contiguous to an existing franchised area or that franchise approval
is expected.
J. Operational Agreements (Applications from HOA/POA and Developers for lots to be sold):
❑ Home/Property Owners' Associations
❑ Per 15A NCAC 02T .0115(c), submit the properly executed Operational Agreement (FORM: HOAI.
❑ Per 15A NCAC 02T .0115(c), submit a copy of the Articles of Incorporation, Declarations and By-laws.
❑ Developers of lots to be sold
❑ Per 15A NCAC 02T .0115(b). submit the properly executed ODerational Agreement (FORM: DEV).
For more information, visit the Division's collection systems website
INSTRUCTIONS FOR FORM: FTA 10-23 & SUPPORTING DOCUMENTATION Page 2 of 3
THE COMPLETED APPLICATION PACKAGE INCLDING ALL SUPPORTING INFORMATION AND
MATERIALS, SHOULD BE SENT TO THE APPROPRIATE REGIONAL OFFICE:
REGIONAL OFFICE
ADDRESS
COUNTIES SERVED
Asheville Regional Office
2090 US Highway 70
Avery, Buncombe, Burke, Caldwell, Cherokee,
Water Quality Section
Swannanoa, North Carolina 28778-8211
Clay, Graham, Haywood, Henderson, Jackson,
(828) 296-4500
Macon, Madison, McDowell, Mitchell, Polk,
(828) 299-7043 Fax
Rutherford, Swain, Transylvania, Yancey
Fayetteville Regional Office
225 Green Street Suite 714
Anson, Bladen, Cumberland, Hamett, Hoke,
Water Quality Section
Fayetteville, North Carolina 28301-5095
Montgomery, Moore, Robeson, Richmond,
(910) 433-3300
Sampson, Scotland
(910)486-0707 Fax
Mooresville Regional Office
610 E. Center Avenue
Alexander, Cabarrus, Catawba, Cleveland,
Water Quality Section
Mooresville, North Carolina 28115
Gaston, Iredell, Lincoln, Mecklenburg, Rowan,
(704) 663-1699
Stanly, Union
(704)663-6040 Fax
Raleigh Regional Office
3800 Barrett Drive
Chatham, Durham, Edgecombe, Franklin,
Water Quality Section
Raleigh, North Carolina 27609
Granville, Halifax, Johnston, Lee, Nash,
(919) 791-4200
Northampton, Orange, Person, Vance, Wake,
(919) 571-4718 Fax
Warren, Wilson
Washington Regional Office
943 Washington Square Mall
Beaufort, Bertie, Camden, Chowan, Craven,
Water Quality Section
Washington, North Carolina 27889
Cunituck, Dare, Gates, Greene, Hertford, Hyde,
(252) 946-6481
Jones, Lenoir, Martin, Pamlico, Pasquotank,
(252) 975-3716 Fax
Perquimans, Pitt, Tyrrell, Washington, Wayne
Wilmington Regional Office
127 Cardinal Drive Extension
Brunswick, Carteret, Columbus, Duplin, New
Water Quality Section
Wilmington, North Carolina 28405
Hanover, Onslow, Pander
(910)796-7215
(910) 350-2004 Fax
Winston-Salem Regional Office
450 W. Hanes Mill Road
Suite 300
Alamance, Allegheny, Ashe, Caswell, Davidson,
Davie, Forsyth, Guilford, Rockingham, Randolph,
Water Quality Section
Winston-Salem, North Carolina 27105
Stokes, Suny, Watauga, Wilkes, Yadkin
(336) 776-9800
(336)776-9797 Fax
INSTRUCTIONS FOR FORM: FTA 10-23 & SUPPORTING DOCUMENTATION Page 3 of 3
DWR State of North Carolina
Department of Environmental Quality
Division of Water Resources
FAST TRACK SEWER SYSTEM EXTENSION APPLICATION
Division of Water Resources FTA 10-23 & SUPPORTING DOCUMENTATION
Application Number:;�1�3'7 (to be completed by DWR)
All items must be comoleted or the aoolication will be returned
I. APPLICANT INFORMATION:
I. Applicant's name: Greenville Utilities (company, municipality, HOA, utility, etc.)
2. Applicant type: ❑ Individual ❑ Corporation ❑ General Partnership ❑ Privately -Owned Public Utility
❑ Federal ❑ State/County ® Municipal ❑ Other
3. Signature authority's name: Clifton H. Cahoon. P.E. per I5A NCAC 02T 0106(bl
Title: Construction/Contracts Engineer
4. Applicant's mailing address: P.O. Box 1847
City: Greenville State: NC Zip: 27835-
5. Applicant's contact information:
Phone number: 252 551-3386 Email Address: cahoonchAeuc.com
II. PROJECT INFORMATION:
1. Project name: Bells Fork Village
2. Application/Project status: ® Proposed (New Permit) ❑ Existing Permit/Project
If a modification, provide the existing permit number: WQOO_ and issued date: ,
For modifications, also attach a detailed narrative description as described in Item G of the cbecklisL
If new construction, but part of a master plan, provide the existing permit number: WQOO_
3. County where project is located: Pitt
4. Approximate Coordinates (Decimal Degrees): Latitude: 35.5640Longitude:-77.357'
5. Parcel ID (if applicable): 11770 (or Parcel ID to closest downstream sewer)
III. CONSULTANT INFORMATION:
1. Professional Engineer: J. Dwight Vemelson License Number: 13055
Firm: Rivers & Associates. Inc.
Mailing address: 107 E. Second Street
City: Greenville State: NC Zip: 27858-
Phone number: 252 752-4135 Email Address: dvemelson(Zariversandassociates com
IV. WASTEWATER TREATMENT FACILITY (WWTF) INFORMATION:
1. Facility Name: Greenville Utilities Permit Number: NC 0023931
Owner Name: Greenville Utilities
V. RECEIVING DOWNSTREAM SEWER INFORMATION:
1. PermitNumber(s): W00042147
2. Downstream (Receiving) Sewer Information: 8 inch ® Gravity ❑ Force Main
3. System Wide Collection System Permit Number(s) (if applicable): WQCS_
Owner Name(s):
FORM: FTA 10-23 Pagel of 5
VI. GENERAL REQUIREMENTS
1. If the Applicant is a Privately -Owned Public Utility, has a Certificate of Public Convenience and Necessity been attached?
❑ Yes ❑ No ® N/A
2. If the Applicant is a Developer of lots to be sold, has a Develocer's Operational A &eement (FORM DEV) been attached?
❑ Yes ❑ No ® N/A
3. If the Applicant is a Home/Property Owners' Association, has an HOAIPOA Operational Aareement (FORM- HOB and
supplementary documentation as required by 15A NCAC 02T.0115(c) been attached?
❑ Yes ❑ No ® N/A
4. Origin of wastewater: (check all that apply):
❑ Residential (Individually Owned) ❑ Retail (stores, centers, malls)
❑ Car Wash
® Residential (Leased) ❑ Retail with food preparation/service ❑ Hotel and/or Motels
❑ School / preschool / day care ❑ Medical / dental / veterinary facilities Swimming Pool/Clubhouse
❑ Food and drink facilities ❑ Church
Swimming PooUFilter Backwash
❑ Businesses / offices / factories ❑ Nursing Home ❑ Other (Explain in Attachment)
5. Nature of wastewater: 100 % Domestic _% Commercial _ % Industrial (See 15A NCAC OAT 0103(2O))
If Industrial, is there a Pretreatment Program in effect? ❑ Yes❑ No
6. Hasa flow reduction been approved under 15A NCAC 02T 01 I41 f)? ❑ Yes ®No
➢ If yes, provide a cony of flow reduction anproyal letter with this application
Summarize wastewater generated by project:
Establishment Type (see 02T.0114(f))
Daily Design Flow •,°
No. of Units
Flow
12 EA, 1-Bedroom Apts
75 gal/day
12
900 GPD
36 EA, 2-Bedroom Apts
75 gal/day
72
5,400 GPD
24 EA, 3-Bedroom Apts
75 gal/day
72
5,400 GPD
]-Clubhouse
250 gal/fixture/day
10
2,500 GPD
gal/
GPD
gay
GPD
Total
14,200 GPD
See _I5A NCAC 02T 01 1401 rdt (ek t ) and (e)(2) for caveats to wastewater design flow rates (i.e. proposed unknown
non-residential development uses; public access facilities located near high public use areas; and residential property
located south or east of the Atlantic Intracoastal Waterway to be used as vacation rentals as defined in G.S. 42A4).
Per 15A NCAC 02T .0114(c), design flow rates for establishments not identified [in table 15A NCAC 02T.01147 shall be
determined using available flow data, water using fixtures, occupancy or operation patterns, and other measured data.
S. Wastewater generated by project: 14200 GPD (per 15A NCAC 02T 0114 and G 143-215 1)
➢ Do not include future flows or previously permitted allocations
If permitted flow is zero, please indicate why:
❑ Pump Station/Force Main or Gravity Sewer where flow will be permitted in subsequent permits that connect to this line.
Please provide supplementary information indicating the approximate timeframe for permitting upstream sewers with flow.
❑ Flow has already been allocated in Permit Number: __ Issuance Date:
❑ Rehabilitation or replacement of existing sewers with no new flow expected
❑ Other (Explain):
FORM: FTA 10-23 Page 2 of
VIL GRAVITY SEWER DESIGN CRITERIA (If Applicable) - 02T .0305 & MDC (Gravity Sewersl:
L Summarize gravity sewer to be permitted:
Size (inches) Length (feet) Material
8 403 PVC Truss
8 108 DIP
➢ Section II & III of the MDC for Permitting of Gravity Sewers contains information related to design criteria
➢ Section Ill contains information related to minimum slopes for gravity sewer(s)
➢ Oversizing lines to meet minimum slope requirements is not allowed and a violation of the MDC
Vlll. PUMP STATION DESIGN CRITERIA (If Applicable) — 02T .0305 & MDC (Pu no Stations/Force Mains):
PROVIDE A SEPARATE COPY OF THIS PAGE FOR EACH PUMP STATION INCLUDED IN THIS PROJECT
L Pump station number or name:
2. Approximate Coordinates (Decimal Degrees): Latitude: 0 Longitude: - °
3. Total number of pumps at the pump station:
3. Design flow of the pump station: _ millions gallons per day (firm capacity)
➢ This should reflect the total GPM for the pump station with the largest pump out of service.
4. Operational point(s) per pump(s): gallons per minute (GPM) at _ feet total dynamic head (TDH)
5. Summarize the force main to be permitted (for this Pump Station):
Size (inches) Length (feet) Material
If any portion of the force main is less than 4-inches in diameter, please identify the method of solids reduction per
MDCPSFM Section 2.01C.I.b. ❑ Grinder Pump ❑ Mechanical Bar Screen ❑ Other (please specify)
6. Power reliability in accordance with 15A NCAC 02T .0305(hH D:
❑ Standby power source or ❑ Standby pump
➢ Must have automatic activation and telemetry - 15A NCAC 02T.0305(hxl)(B)_
➢ Required for all pump stations with an average daily flow greater than or equal to 15,000 gallons per day
➢ Must be permanent to facility and may not be portable
Or if the pump station has an average daily flow less than 15,000 gallons per day 15A NCACO2T.0305(hXlXQ:
❑ Portable power source with manual activation, quick -connection receptacle and telemetry -
or
❑ Portable pumping unit with plugged emergency pump connection and telemetry
➢ Include documentation that the portable source is owned or contracted by the applicant and is compatible with the station.
➢ If the portable power source or pump is dedicated to multiple pump stations, an evaluation of all the pump stations' storage
capacities and the rotation schedule of the portable power source or pump, including travel timeframes, shall be provided
as part of this permit application in the case of a multiple station power outage.
FORM: FTA 10-23 Page 3 of 5
IX. SETBACKS & SEPARATIONS — (028.0200 & 15A NCAC 02T .0305(f)):
1. Does the project comply with all separafions/altematives found in ISA NCAC 02T.0305(t) & (,g)? ® Yes ❑ No
15A NCAC 02T.0305 contains minimum semrmions that shall be 'd d f
v� a o ror sewers
Setback Parameter*
atoms.
Separation Required
Storm sewers and other utilities not listed below (vertical)
18 inches
'Water mains (vertical - water over sewer preferred, including in benched trenches)
18 inches
'Water mains (horizontal)
10 feet
Reclaimed water lines (vertical - reclaimed over sewer)
18 inches
Reclaimed water lines (horizontal - reclaimed over sewer)
2 feet
"Any private or public water supply source, including any wells, WS-1 waters of Class I or
Class Ii impounded reservoirs used as a source of drinking water, and associated wetlands.
100 feet
"Waters classified WS (except WS-I or WS-V), B, SA, ORW, HQW, or SB from normal
high water (or tide elevation) and wetlands associated with these waters (see item IX.2)
50 feet
"Any other stream, lake, impoundment, or ground water lowering and surface drainage
ditches, as well as wetlands associated with these waters or classified as WL.
10 feet
Any building foundation (horizontal)
5 feet
Any basement (horizontal)
10 feet
Top slope of embankment or cuts of 2 feet or more vertical height
10 feet
Drainage systems and interceptor drains
5 feet
Any swimming pools
10 feet
Final earth grade (vertical)
36 inches
11 ❑uncompnance with uZ t.uswtTt or tei. see Section X.l of this application --
•ISA NCAC 02T.0305(al contains alternatives where separations in 02T.0305(fl cannot be achieved. Please check "yes"
above if these alternatives are used and provide narrative information to explain.
**Stream classifications can be identified using the Division's NC Surface Water Classifications webpage
2. Does this project comply with the minimum separation requirements for water mains? ® Yes ❑ No ❑ N/A
➢ If no, please refer to MA NCAC 18C.0906(f) for documentation requirements and submit a separate document,
signed/sealed by an NC licensed PE, verifying the criteria outlined in that Rule.
3. Does the project comply with separation requirements for wetlands? ❑ Yes [:]No ® N/A
➢ Please provide supplementary information identifying the areas of non-conformance.
➢ See the Division's draft separation requirements for situations where separation cannot be met.
➢ No variance is required if the alternative design criteria specified is utilized in design and construction.
4. Is the project located in a river basin subject to any State buffer rules? ® Yes Basin name: Neuse ❑ No
If yes, does the project comply with setbacks found in the river basin roles per 15A NCAC 02B .02009 ® Yes ❑ No
➢ This includes Trout Buffered Streams per 15A NCAC 2B.0202
5. Does the project require coverage/authorization under a 404 Nationwide/individual permits ❑ Yes ® No
or 401 Water Quality Certifications?
➢ Please provide the permit number/permitting status in the cover letter if coveragetauthorization is required.
6. Does project comply with 15A NCAC 02T.0105(CW6) (additional permits/certifications)? ® Yes ❑ No
Per 15A NCAC 02T OI05(c)(6). directly related environmental permits or certification applications must be being prepared,
have been applied for, or have been obtained. Issuance of this permit is contingent on issuance of dependent permits (erosion
and sedimentation control plans, stormwater management plans, etc.).
7. Does this project include any sewer collection lines that are deemed "high -priority?" ❑ Yes ® No
Per I SA NCAC 02T.0402 "high -priority sewer" means any aerial sewer, sewer contacting surface waters,
siphon, or sewers positioned parallel to streambanks that are subject to erosion that undermines or deteriorates the sewer.
Siphons and sewers suspended through interferencetconflict boxes require a variance approval.
➢ If yes, include an attachment with details for each line, including type (aerial line, size, material, and location).
High priority lines shall be inspected by the permittee or its representative at least once every six -months and
inspections documented per 15A NCAC 02T.0403(ax5) or the perm ittee's individual System -Wide Collection permit
FORM: FTA 10-23 Page 4 of 5
X. CERTIFICATIONS:
I. Does the submitted system comply with 15A NCAC 02T, the Minimum Design Criteria for the Permitting of Pumn Stations
and Force Mains (latest version) and the Gravily Sewer Minimum Design Criteria flat t version) as applicable?
® Yes ❑ No
If no, for projects requiring a single variance, complete and submit the Variance/Altemative Design Request application
(VADC 10-14) and supporting documents for review to the Central Office. Approval of the request will be issued
coneurrently with the nnnrn.•st ..r.h_ __., _-_:__._
2. Professional Engineer's Certification: • /
yI�A�EGSON - attest that this application for
(Professional Engineer's name from Application Item m.l.) (Project Name from Application Item 11.1)
has been reviewed by me and is accurate, complete and consistent with the information supplied in the plans,
specifications, engineering calculations, and all other supporting documentation to the best of my knowledge. I further
attest that to the best of my knowledge the proposed design has been prepared in accordance with the applicable regulations,
Minimum Design Criteria for Gravity Sewers (latest version), and the Minimum Design Criteria for the Fast -Track Permitting
Of Pump Stations and Force Mains (latest version). Although other professionals may have developed certain portions of this
submittal package, inclusion of these materials under my signature and seal signifies that I have reviewed this material and
have judged it to be consistent with the proposed design.
NOTE — In accordance with General Statutes 143-215.6A and 143-215.613, any person who knowingly makes any false
statement, representation, or certification in any application package shall be guilty of a Class 2 misdemeanor, which may
include a fine not to exceed $10,000, as well as civil penalties up to $25,000 per violation. Misrepresentation of the application
information, including failure to disclose any design non-compliance with the applicable Rules and design criteria, may subject
the North Carolina -licensed Professional Engineer to referral to the licensing board. (21 NCAC 56.0701)
North Carolina Professional Engineer's seal, signature, and d
IV-Z1(
3. Applicant's Certification per 15A NCAC 02T .0106(b):
attest that this application for
(Signature Authority Name from Application Item 1.3.) (Project Name from Application item 11.
attest that this application has been reviewed by me and is accurate and complete to the best of my knowledge.
I understand that if all required parts of this application are not completed and that if all required supporting documentation
and attachments are not included, this application package is subject to being returned as incomplete. 1 understand that any
discharge of wastewater from this non -discharge system to surface waters or the land will result in an immediate enforcement
action that may include civil penalties, injunctive relief, and/or criminal prosecution. I will make no claim against the Division
of Water Resources should a condition of this permit be violated. I also understand that if all required parts of this application
package are not completed and that if all required supporting information and attachments are not included, this application
package will be returned to me as incomplete.
NOTE — In accordance with General Statutes 143-215.6A and 143-215.6B, any person who knowingly makes any false
statement, representation, or certification in any application package shall be guilty of a Class 2 misdemeanor, which may
include a fine not to�exceed $10,000 as well as civil penalties up to $25,000 per violation.
Signature: L/Zfij!/1,� Date:
"'..'--��;��
FORM: FTA 10-23 Page 5 of 5
7ULKAHOE'DR
E DR
SIGN4IU
- J r
n5.iry�
S� AV/
agoo
CK
W. 047
cc
W
O r 4y,
-oc EDON DRY
�� M y11Mb VR 1 o ( SO
LN%
� l
-�, �. _ _ x -.� >' `
je 1 BS�t +ry'•a+�-tee. s - i
4.0 � f 4
1 .gym s
�y "w ♦ jr ry� R
Y
31
2
1
l
sTR
A
\
� Y
Gt'
�
-
i 5
r• � �
t t. tt� �I•ttt �''''.
p. a
R
LE U
State of North Carolina
Department of Environmental Quality
Division of Water Resources
Dtvislon of Water Resources Flow Tracking/Acceptance for Sewer Extension Applications
(FTSE 04-16)
Entity Requesting Allocation: Greenville Utilities Commission
Project Name for which flow is being requested: Bells Fork Village
More than one FTSE may be required for a single project if the owner of the WWTP is not responsible for all pump
stations along the route of the proposed wastewater flow.
I. Complete this section only if you are the owner of the wastewater treatment plant
a. WWTP Facility Name: Greenville Utilities Commission
b. WWTP Facility Permit #: NC0023931
All flows are in MGD
c. WWTP facility's permitted flow 17.5
d. Estimated obligated flow not yet tributary to the WWTP 2.87
e. WWTP facility's actual avg. flow 10.426
f. Total flow for this specific request .0142
g. Total actual and obligated flows to the facility 13.310
h. Percent of permitted flow used 76.060
II. Complete this section for each pump station you are responsible for along the route of this
proposed wastewater flow.
List pump stations located between the project connection point and the WWTP:
(A) (B) (C)
(D)�(B+C)
(E)=(A-D)
Design Obligated,
PUMP Average Daily Approx. Not Yet
Total Current
Station Firm Flow** Current Avg. Tributary
Flow Plus
(Name or Capacity, * (Firm / pf), Daily Flow, Daily Flow,
Obligated
Available
Number) MGD MGD MGD MGD
Flow
Capacity***
Southside 30.259 12.104 5.791 1.596
7.387
4.717
Fork
6.513 2.605 1.618 .209
1.827
.778
* The Firm Capacity of any pump station is defined as the maximum pumped Flow that
can be achieved with the largest pump taken out of service.
** Design Average Daily Flow is the firm capacity of the pump station divided by a pealing
factor (pf) not less than 2.5.
*** A Planning Assessment Addendum shall be attached for each pump station located
between the project connection point and the WWTP where the Available Capacity is < 0.
Downstream Facility Name (Sewer): Unknown
Downstream Permit Number: Unknown
Page 1 of 6
FTSE 04-16
III. Certification Statement:
I Clifton H. Cahoon, PE certify to the best of my knowledge that the addition of
the volume of wastewater to be permitted in this project has been evaluated along the route to the
receiving wastewater treatment facility and that the flow from this project is not anticipated to
cause any capacity related sanitary sewer overflows or overburden any downstream pump station
en route to the receiving treatment plant under normal circumstances, given the implementation
of the planned improvements identified in the planning assessment where applicable. This
analysis has been performed in accordance with local established policies and procedures using
the best available data. This certification applies to those items listed above in Sections I and II
plus all attached planning assessment addendums for which I am the responsible party.
Signature of this form indicates acceptance of this wastewater flow.
Page 2 of 6
FTSE 04-16
fiversENGINEERS PLANNERS SURVEYORS LANDSCAPE ARCHITECTS
& ASSOCIATES, INC.
RECEIVED/NCDENR/DWR
July 24, 2024
AUG 2 2 2024
Ms. Sarah Toppen — Environmental Specialist II Water Duality
NCDEQ Regional Operations Section
Washington Regional Office Washington Regional Office
943 Washington Square Mall
Washington, NC 27889
Phone: (252) 948-3845
Email: sarah.toppen@n.edenr.gov
Subject: Bells Fork Village
Near NW Comer of SR 2235 — Old Fire Tower Road and SR 1725 — County
Home Road
Greenville, NC
Dear Ms. Toppen:
The purpose of this submittal is to acquire a sewer permit to install approximately 511 if of 8"
sewer main to serve a proposed apartment complex near the NW corner of SR 2235 — Old Fire
Tower Road and SR 1725 — County Home Road in Greenville, NC.
The proposed apartment complex is comprised of the following units: 12- One Bedroom
Apartments, 36- Two Bedroom Apartments and 24- Three Bedroom Apartments, for a total of 72
units. It should be noted that this complex will also have a clubhouse. The original site
conditions included a mobile home park with approximately nineteen mobile homes, which were
served by septic tank systems. The septic tanks will be removed and Greenville Utilities will
serve this complex with gravity sanitary sewer.
Should you have any questions or need any additional information, please do not hesitate to
contact me.
With best regards,
J. t Vernelson, PE
'vers & Associates, Inc.
P: LandDev/Pivotal-Bells_Fork_V ilg-2023113/Admin/D-Permitting/SanitarySewer/CvrLtnoGUC
107 E. Second Street, Greenville, NC 27858 • PO Box 929, Greenville, NC 27835 • Phone: 252-752-4135 • Fax: 252-752-3974
NCBELS Lic. No. F-0334 www.riversandassociates.com NCBOLA Lic. No. C-312
Greenville
Utilities
August 19, 2024
Mr. Robert Tankard
Assistant Regional Supervisor
North Carolina Division of Water Quality
943 Washington Square Mall
Washington, NC 27889
Subject: Bells Fork Village
Sewer Main Extension
Dear Mr. Tankard:
RECEIVED/NCDENR/DWR
AUG 2 2 2024
Water Quality
Regional Operations Section
Washington Regional Office
We are submitting herewith one (1) original and one (1) copy of the executed Non -Discharge
Permit Application and Flow Tracking/Acceptance for Sewer Extension Permit Applications
along with a check for $600.00 for the subject project. We request your approval of the sewer
improvements.
We trust that you will find this submittal to be in order and that your approval will be
forthcoming. In the meantime, should you have any questions or require any additional
information, please let us know.
Sincerely,
40on H. Cahoon, PE