HomeMy WebLinkAboutWQCS00161_NOD2024PC0145 & CEI Report_20240806 SENT VIA ELECTRONIC MAIL ONLY: NO HARD COPY WILL BE MAILED August 13, 2024 Rick Owen, Town Manager Town of Banner Elk manager@townofbannerelk.org SUBJECT: NOTICE OF DEFICIENCY Tracking Number: NOD-2024-PC-0145 Permit No. WQCS00161 Banner Elk Collection System Avery County Dear Permittee: The North Carolina Division of Water Resources conducted an inspection of the Banner Elk Collection System on August 6, 2024. This inspection was conducted to verify that the facility is operating in compliance with the conditions and limitations specified in Collection System Permit No. WQCS00161. A summary of the findings and comments noted during the inspection are provided in the enclosed copy of the inspection report. The Collection System Non-sampling inspection was conducted by Division of Water Resources staff from the Asheville Regional Office. The following deficiency(s) was noted during the inspection: Inspection Area Description of Deficiency _________________________________________________________________________________________________________________________________________________________________________ Inspections The entire system is being observed on an annual basis, but it is not specifically documented. Per section (III)1 of the permit, “Records shall be maintained to document compliance with Conditions I(4), II(2)-II(4), II(7)-II(8), IV(3) and V(1)-V(4).” _________________________________________________________________________________________________________________________________________________________________________ Docusign Envelope ID: 29535411-7F86-4321-89B3-31667D4F3B04 Remedial actions should have already been taken to correct this problem and prevent further occurrences in the future. The Division of Water Resources may pursue enforcement action for this and any additional violations of State law. To prevent further action, carefully review these deficiencies and address the causes of non-compliance to prevent the recurrence of similar situations. If you should have any questions, please do not hesitate to contact Richard Eguino with the Water Quality Regional Operations Section in the Asheville Regional Office at 828-296-4500. Sincerely, Daniel Boss, Assistant Regional Supervisor Water Quality Regional Operations Section Asheville Regional Office Division of Water Resources, NCDEQ ATTACHMENTS: Inspection Report Ec: Laserfische Docusign Envelope ID: 29535411-7F86-4321-89B3-31667D4F3B04 Compliance Inspection Report Permit:WQCS00161 Effective:07/09/21 Expiration:06/30/29 Owner :Town of Banner Elk SOC: Contact Person: Region: County: Directions to Facility: Avery Asheville Steve Smith Effective:Expiration:Facility:Banner Elk Collection System PO Box 156 Title:Phone:828-898-5398 Secondary ORC(s): 828-898-6277Phone:14706Certification:Paul E. IsenhourPrimary ORC: CS1,System Classifications: On-Site Representative(s): Related Permits: NC0032115 Town of Banner Elk - Banner Elk WWTP WQ0022720 Lees McRae College - Hemlock Village at Lees McRae College Secondary Inspector(s): Primary Inspector: Inspection Date:Exit Time:Entry Time: Phone: 08/06/2024 09:00AM 12:00PM Richard Eguino 828-296-4500 Facility Status: Permit Inspection Type: Reason for Inspection:Inspection Type: Not CompliantCompliant Routine Collection system management and operation Collection System Inspect Non Sampling Question Areas: Miscellaneous Questions General Sewer & FOG Ordinances Capital Improvement Plan Map Reporting Requirements Inspections Spill Response Plan Spills Lines Manholes Pump Stations (See attachment summary) Page 1 of 7 Docusign Envelope ID: 29535411-7F86-4321-89B3-31667D4F3B04 Inspection Date: Permit: Inspection Type : Owner - Facility: Reason for Visit: WQCS00161 08/06/2024 Collection System Inspect Non Sampling Town of Banner Elk Routine Inspection Summary: Richard Eguino, with the Asheville Regional Office, conducted a Compliance Evaluation Inspection of the Banner Elk Collection System on August 6, 2024, to verify compliance with Permit # WQCS00161. Paul Isenhour (ORC) was present and assisted with the records review portion of the inspection and Justin Hodges (Public Works Director) was present and assisted with the records review and system observation portions of the inspection. General: The subject collection system consists of 17.67 miles of gravity lines and 0.25 miles of force main with one duplex pump station. Spare pump station pumps are kept at the Town’s wastewater treatment plant. Sewer Use and FOG Ordinances: The Sewer Use and FOG ordinances were reviewed and appeared satisfactory. The town requires restaurants to clean grease traps every three months, and inspections of grease traps by Town personnel are conducted twice per year. Mr. Hodges explained that food service establishments have been overall compliant with the FOG ordinance requirements and that the collection system has not been experiencing any ongoing issues with grease, rags, flushable wipes, etc. Inspections: Staff visit the entire system throughout the year during routine maintenance and observations; however, the annual system observation is not specifically documented. Permit section V(3) establishes the requirement for the annual observation of the entire system and permit section III(1) establishes the requirement to maintain records of it. Line cleaning: Records for the annual line cleaning appeared satisfactory with 10K to 11K feet of line being cleaned per year. Manholes: Three manholes were visually inspected. All three appeared in good condition with no issues observed. These were located on Old Town Rd (~500ft east of Silver Springs Dr.), Shawneehaw Heights (~100ft south of Maint St E.), and on Mill Pond Road (near Hemlock trail). Per Mr. Hodges, the gravity line on Mill Pond Road is the only clay pipe in the system and is the main line leading to the Town's wastewater treatment plant. Pump Stations: The system’s only pump station was visually inspected. It appeared in good condition with no issues observed. The float switches, visual and audible alarms, and the SCADA system were tested satisfactorily. Grease accumulation was minimal. A propane emergency generator is installed at the pump station and is tested weekly. Propane is supplied by Freeman Gas. High Priority Lines: Three high priority lines (HPL) 33 (Shawneehaw HTS), 37 (Lecka Lane), 132 (Tate-Evans Park) were visually inspected. No issues were observed at HPLs 37 and 132. A pin hole leak was observed on HPL 33. The leak rate was too little to quantify, and Mr. Hodges had the issue corrected by having a repair band installed over the pipe shortly after the observation. The following deficiency was noted during the inspection: Annual inspections of the entire system appear to be conducted but are not fully documented. Per. Section III(1) of the permit, “Records shall be maintained to document compliance with conditions I(4), II(2)-II(4), II(7)-II(8), IV(3) and V(1)-V(4).” Page 2 of 7 Docusign Envelope ID: 29535411-7F86-4321-89B3-31667D4F3B04 Inspection Date: Permit: Inspection Type : Owner - Facility: Reason for Visit: WQCS00161 08/06/2024 Collection System Inspect Non Sampling Town of Banner Elk Routine General Yes No NA NE Is there a properly designated primary ORC and at least one back-up of proper grade? Are logs being reviewed by the system management or owner on a regular basis? # What is that frequency?Quarterly # Are there any issues being addressed currently or any in the planning stages? Is there a specific pump failure plan available for all pump stations? Does plan indicate if pump parts/new pumps are in spare parts/equipment inventory? Are new/significantly upgraded pump stations equipped with anti-corrosion materials? Does the permittee have a copy of their permit? # Is permit expiring within the next 6 months? If Yes, has the Permittee applied for renewal? Mr. Hodges explaiend they are continuously working to identify and reduce infiltration and inflow. See summary for details. Comment: Sewer and FOG Ordinances Yes No NA NE Is Sewer Use Ordinance (SUO) or other Legal Authority available? Does it appear that the Sewer Use Ordinance is enforced? Is there a Grease Control Program that legally requires grease control devices? What is the standard grease trap cleaning requirement in the FOG ordinance?Every 3 months Is Grease Control Program enforced via periodic inspections/records review? Is action taken against violators? # Have satellite systems adopted an equivalent or more stringent ordinance? Is grease/sewer education program documented with req'd customer distribution? # Are other types of education tools used like websites, booths, special meetings, etc? If Yes, what are they? (This can reduce mailing to annual.) See summary for details. Comment: Capital Improvement Plan Yes No NA NE Has a Capital (CIP) or System Improvement Plan been developed and adopted? Is it designated for wastewater only or does it have a dedicated section? Does CIP cover three to five year period of earmarked improvements? Does CIP include description of project area? Does CIP include description of existing facilities? Does CIP include known deficiencies? Does CIP include forecasted future needs? While the CIP lists project details and allocated capital funds, it does not list timeframes for completion.It is recommended to include timeframes for clarity. Comment: Page 3 of 7 Docusign Envelope ID: 29535411-7F86-4321-89B3-31667D4F3B04 Inspection Date: Permit: Inspection Type : Owner - Facility: Reason for Visit: WQCS00161 08/06/2024 Collection System Inspect Non Sampling Town of Banner Elk Routine Map Yes No NA NE Is there a overall sewer system map? Does the map include: Pipe Type (GS/FM) Pipe sizes Pipe materials (PVC, DIP, etc) Pipe location Flow direction Approximate pipe age Pump station ID, location and capacity # Force main air release valve location & type # Location of satellite connections Is the map being updated for changes/additions within 1 year of activation? Mr. Hodges explained approximate pipe age is included when known, and is added when any sections of pipe are replaced. Comment: Reporting Requirements Yes No NA NE # Have there been any sewer spills in the past 3 years? If Yes, were they reported to the Division if meeting the reportable criteria? If applicable, is there documentation of press releases and public notices issued? Is an Annual Wastewater Performance Report being filed with the Division, if required? Is the report being made available to all its sewer customers? # How is it being made available?Through website which is indicated on the bill Comment: Inspections Yes No NA NE Are adequate maintenance records maintained? Are pump stations being inspected at the required frequency? # Is at least one complete functionality test conducted weekly per pump station? Is there a system or plan in place to observe the entire system annually? Is the annual inspection documented? # Does the system have any high-priority lines/locations? Are inspections of HPL documented at least every 6 months? Are new lines being added to the HPL list when found or created? The entire system is being observed on an annual basis but it is not specifically documented. See summary for details. Comment: Spill Response Action Plan Yes No NA NE Page 4 of 7 Docusign Envelope ID: 29535411-7F86-4321-89B3-31667D4F3B04 Inspection Date: Permit: Inspection Type : Owner - Facility: Reason for Visit: WQCS00161 08/06/2024 Collection System Inspect Non Sampling Town of Banner Elk Routine Is a Spill Response Action Plan available? Is a Spill Response Action Plan available for all personnel? Does the plan include: 24-hour contact numbers Response time Equipment list and spare parts inventory Access to cleaning equipment Access to construction crews, contractors, and/or engineers Source of emergency funds Site sanitation and cleanup materials Post-overflow/spill assessment Does the Permittee appear to respond within 2 hours of first knowledge of a spill? Comment: Spills Yes No NA NE Is system free of known points of bypass? If No, describe type of bypass and location Are all spills or sewer related issues/complaints documented? # Are there repeated overflows/problems (2 or more in 12 months) at same location? # If Yes, is there a corrective action plan? Comment: Lines/Right-of-Ways/Aerial Lines Yes No NA NE Please list the Lines/Right of Ways/Aerial Lines Inspected: HPLs #37, #33, and #132. Are right-of-ways/easements maintained for full width for access by staff/equipment? If No, give details on temporary access: Is maintenance documented? Are gravity sewer cleaning records available? Has at least 10% of lines older than 5 yrs been cleaned annually? Were all areas/lines inspected free of issues? Pin hole leak observed on HPL # 37 and was quickly addressed with a repair band. See summary for details. Comment: Manholes Yes No NA NE Please list the Manholes Inspected: 1. Old Town Rd, ~ 500ft east of Silver Springs Dr. 2. Shaweehaw Heights, ~100ft south of Maint St E. 3. Mill Pond Road & Hemlock Trail Are manholes accessible? Page 5 of 7 Docusign Envelope ID: 29535411-7F86-4321-89B3-31667D4F3B04 Inspection Date: Permit: Inspection Type : Owner - Facility: Reason for Visit: WQCS00161 08/06/2024 Collection System Inspect Non Sampling Town of Banner Elk Routine # Are manhole covers/vents above grade? Are manholes free of visible signs of overflow? Are manholes free of sinkholes and depressions? Are manhole covers present? # Are manholes properly seated? # Are manholes in good condition? # Are inverts in good condition? Is flow unrestricted in manholes? Are manholes free of excessive amounts of grease? Are manholes free of excessive roots? Are manholes free of excessive sand? Are manhole vents screened? Are vents free of submergence? Are manholes free of bypass structures or pipes? Roadway manholes are at grade. See summary for details.Comment: Pump Stations Yes No NA NE Please list the Pump Stations Inspected: The system has one duplex pump station located on Banner Elk Hwy # Number of duplex or larger pump stations in system 1 # Number of vacuum stations in system 0 # Number of simplex pump stations in system 0 # Number of simplex pump stations in system serving more than one building 0 How many pump/vacuum stations have: # A two-way "auto polling" communication system (SCADA) installed?1 # A simple one-way telemetry/communication system (auto-dialer) installed?0 For pump stations inspected: Are they secure with restricted access? Were they free of by-pass structures/pipes? Were wet wells free of excessive grease/debris? # Do they all have telemetry installed? Is the communication system functional? Is a 24-hour notification sign posted ? Does the sign include: Owner Name? Pump station identifier? # Address? Page 6 of 7 Docusign Envelope ID: 29535411-7F86-4321-89B3-31667D4F3B04 Inspection Date: Permit: Inspection Type : Owner - Facility: Reason for Visit: WQCS00161 08/06/2024 Collection System Inspect Non Sampling Town of Banner Elk Routine Instructions for notification? 24-hour emergency contact numbers? Are audio and visual alarms present? Are audio and visual alarms operable? # Is there a backup generator or bypass pump connected? If tested during inspection, did it function properly? Is the back-up system tested at least bi-annually under normal operating conditions? # Does it have a dedicated connection for a portable generator? # Is the owner relying on portable units in the event of a power outage? # If Yes, is there a distribution plan? If Yes, what resources (Units/Staff/Vehicles/etc) are included in Plan? # Does Permittee have the approved percentage of replacement simplex pumps? Is recordkeeping of pump station inspection and maintenance program adequate? Do pump station logs include at a minimum: Inside and outside cleaning and debris removal? Inspecting and exercising all valves? Inspecting and lubricating pumps and other equipment? Inspecting alarms, telemetry and auxiliary equipment? See summary for details.Comment: Page 7 of 7 Docusign Envelope ID: 29535411-7F86-4321-89B3-31667D4F3B04