HomeMy WebLinkAboutWQ0035784_Notice of Deficiency_20240909ROY COOPER Governor ELIZABETH S. BISER Secretary RICHARD E. ROGERS, JR. Director NORTH CAROLINA Environmental Quality September 9, 2024 Delivered electronically via email to: astark(a_timberlinerev.com Andrew Stark Boone Owner, LLC 2 School St Rye, NY 10580 SUBJECT: Notice of Deficiency (NOD-2024-PC-0166) Compliance Evaluation Inspection Cottages of Boone WWTF Permit No. WQ0035784 Watauga County Dear Mr. Stark: On August 29, 2024, Division of Water Resources staff Caitlin Williams conducted a routine compliance inspection of the Cottages of Boone WWTF and the deemed collection system. Todd Robinson, David Rogers, and Matthew Hukill from EnivroLink, David Smith from the Cottages of Boone, and Jeremey Cumbo of Boone Owner, LLC, were present. A review of available records, treatment units, storage tanks, monitoring wells, and collection system was completed. This review reflected non-compliance with permit requirements. The following deficiencies were noted: 1. Standing water was observed next to the wet weather storage tank. Staff also noted this in correspondence dated January 9, 2023. Per Permit Condition V.1 the Permittee shall perform inspections and maintenance to ensure proper operation of the wastewater treatment and irrigation facilities and Permit Condition V.2 the Permittee shall inspect the wastewater treatment and irrigation facilities to prevent malfunctions, facility deterioration, and operator errors... Take measures to improve the stormwater diversions to prevent water from ponding around the storage tanks. North Carolina Department of Environmental Quality I Division of Water Resources Winston-Salem Regional Office 1 450 W. Hanes Mill Rd, Suite 300 I Winston-Salem, North Carolina 27105 NoanicaaouNn oep.m.m or em�nmen� Qualm 336.776.9800 The following items of concern were noted: A. To remove the floating mats from the wet weather storage tank, the tank was emptied and an access hatch cover was removed. For the wet weather storage tank to be put back in service the hatch cover and a new gasket must be installed. The same method will be used to remove the mats from the 5-day upset tank. Please provide an explanation for how the hatches will be leak tested prior to effluent entering the tanks again. B. Mr. Smith reported that an overflow from one of the grinder tanks within the collection system was noticed on August 26, 2024. An estimated 50 gallons left the tank and reached ground surface. Mr. Smith made necessary repairs and limed the impacted area. Mrs. Williams provided the 5-day report form to Mr. Robinson on August 30, 2024, and requested it be submitted by September 6, 2024. Per 15A NCAC 02T .0403A(a)(1) the collection system shall be effectively maintained and operated at all times to prevent discharge to land or surface waters and 15A NCAC 02T .0403(a)(7) overflows and bypasses shall be reported to the appropriate Division regional office... Moving forward, be sure to report all bypasses or overflows from the collection system and wastewater treatment facility within twenty-four (24) hours of first notice. Please refer to the enclosed inspection report for additional comments and observations. Also enclosed are the deemed collection system rules for reference. If you have any questions, please contact Caitlin Williams at the letterhead address and phone number, or by email at caitlin.williams(Qdeg.nc.gov. Sincerely, Docu Signed by: OD D C FIB 56 Jenni er . raznak, Assistant Regional Supervisor Water Quality Regional Operations Section Division of Water Resources, NCDEQ — WSRO Enc: Deemed Collection System Rules Inspection Report Cc: Todd Robinson, Area Manager (electronic copy) David Rogers, ORC (electronic copy) Madelyn Mills, EnviroLink (electronic copy) Shelby Brown, Complex Manager (electronic copy) NORTH CAROLINAD E Q oeo+ro�.m m F,mro���w n�si� North Carolina Department of Environmental Quality I Division of Water Resources Winston-Salem Regional Office 1 450 W. Hanes Mill Rd, Suite 300 1 Winston-Salem, North Carolina 27105 336.776.9800 Compliance Inspection Report Permit: WQ0035784 Effective: 06/05/23 Expiration: 04/30/30 Owner: Boone Owner LLC SOC: Effective: Expiration: Facility: The Cottages of Boone WWTP County: Watauga 1002 Fallview Ln Region: Winston-Salem Boone NC 28607 Contact Person: Ashley Vargo Title: Phone: Directions to Facility: Take 140 BUS W/US-158 W/US-421 N from N Lierty Street. Follow 421 N to E King Street in Boone. Take US 221 S and NC 105 S to Boone Circle System Classifications: SI, WW2, Primary ORC: Certification: Phone: Secondary ORC(s): Todd Franklin Robinson 1006252 704-881-4598 David Aaron Rogers 1015349 252-235-8809 On -Site Representative(s): Related Permits: WQCSD0738 Wallace Loft LLC - Cottages of Boone WWCS Inspection Date: 08/29/2024 Entry Time 10:18AM DocuSigned by: Primary Inspector: Caitlin rWt�iiagps 1w, (1�il 1, ms Secondary Inspect_8s834968199D49D.. Reason for Inspection: Routine Permit Inspection Type: Wastewater Irrigation Facility Status: ❑ Compliant 0 Not Compliant Question Areas: Treatment Flow Measurement -Effluent Treatment Flow Measurement -Water Use Records Treatment Filters Treatment Sludge Storage/Treatment Treatment Disinfection Standby Power (See attachment summary) Exit Time: 01:OOPM Phone: 336-776-9699 Inspection Type: Compliance Evaluation Treatment Flow Measurement -Influent Miscellaneous Questions Treatment Treatment Barscreen Record Keeping End Use -Irrigation Treatment Flow Measurement Wells Treatment Activated Sludge Treatment Influent Pump Station Storage Page 1 of 9 Permit: WQ0035784 Owner - Facility: Boone Owner LLC Inspection Date: 08/29/2024 Inspection Type: Compliance Evaluation Reason for Visit: Routine Inspection Summary: On August 29, 2024, Division of Water Resources staff Caitlin Williams conducted a routine compliance inspection of the Cottages of Boone WWTF and the deemed collection system. Todd Robinson, David Rogers, and Matthew Hukill from EnivroLink, David Smith from the Cottages of Boone, and Jeremey Cumbo of Boone Owner, LLC, were present. A review of available records, treatment units, storage tanks, monitoring wells, and collection system was completed. This review reflected non-compliance with permit requirements. The following deficiencies were noted: 1. Standing water was observed next to the wet weather storage tank. Staff also noted this in correspondence dated January 9, 2023. Per Permit Condition V.1 the Permittee shall perform inspections and maintenance to ensure proper operation of the wastewater treatment and irrigation facilities and Permit Condition V.2 the Permittee shall inspect the wastewater treatment and irrigation facilities to prevent malfunctions, facility deterioration, and operator errors... Take measures to improve the stormwater diversions to prevent water from ponding around the storage tanks. The following items of concern were noted: A. To remove the floating mats from the wet weather storage tank, the tank was emptied and an access hatch cover was removed. For the wet weather storage tank to be put back in service the hatch cover and a new gasket must be installed. The same method will be used to remove the mats from the 5-day upset tank. Please provide an explanation for how the hatches will be leak tested prior to effluent entering the tanks again. B. Mr. Smith reported that an overflow from one of the grinder tanks within the collection system was noticed on August26, 2024. An estimated 50 gallons left the tank and reached ground surface. Mr. Smith made necessary repairs and limed the impacted area. Mrs. Williams provided the 5-day report form to Mr. Robinson on August 30, 2024, and requested it be submitted by September 6, 2024. Per 15A NCAC 02T .0403A(a)(1) the collection system shall be effectively maintained and operated at all times to prevent discharge to land or surface waters and 15A NCAC 02T .0403(a)(7) overflows and bypasses shall be reported to the appropriate Division regional office... Moving forward, be sure to report all bypasses or overflows fron the collection system and wastewater treatment facility within twenty-four (24) hours of first notice. Other observations: • No leaks were noted around the knife valve. There have been some issues with the air hose that controls the knife valve. • The outlet pipe on the EQ tank has been installed. The level sensor in the EQ tank was also replaced when the outlet pipe was installed. • Drip zones are still being repaired by EnviroLink. • All pumps in the WWTF were operational. • The bank above the storage tank had contractor matting placed on it. • The anoxic tanks were replaced on July 24th, 2024. • Leaks in storage tanks are still being repaired as needed. • The irrigation system was calibrated 12/29/2023. • The wet weather storage tank was emptied, and mats removed from the storage tank. The 5-day upset tank is currently being emptied by pulling effluent from the tank and being transferred to the large lift station to be retreated • While the 5-day storage tank is offline, pump and haul will be used to remove the effluent> 10NTU • Freeboard was reported as 24' for both tanks since March 2024. Mr. Robinson stated the tanks were being pulled down starting in March to begin replacing the anoxic tanks and remove the mats. • The brush screen room was in good condition. The full dumpster has been removed, and the dumpster is emptied 1x3months. • The out of order UV bank was repaired. This was listed in a deficiency in correspondence dated January 9, 2023. • The 2024 soil samples showed that all drip zones had a sodium index of about 3 and exchangeable sodium value of 30%. The 2023 soil samples show lower results. The higher values could be a result of sample contamination. Staff recommended washing all sample equipment prior to the next soil sample event. • The flow meter is an inline meter. It was calibrated 12/29/2023. • The turbidimeter was calibrated on 12/29/2023. Page 2 of 9 Permit: WQ0035784 Owner - Facility: Boone Owner LLC Inspection Date: 08/29/2024 Inspection Type: Compliance Evaluation Reason for Visit: Routine • The Spill Plan did not have updated ORC info listed. An updated copy was provided on 8/29/2024. • Z3 had a high flow warning. Z4 had limited irrigation compared to the other zones, likely due to the fluctuation in incoming flow and current WWTF operations. • Mr. Robinson stated that pump and haul will be used if turbidity >10NTU while the 5-day upset tank is out of service. • A hard copy of the most recent permit was not available, but it was printed while staff were on site. • The large lift station had a float tangled around the pump stands. This was corrected while staff were on site. • COB staff inspect the grinder pump stations, and Envirol-ink staff inspect the two main lift stations. • An ORC designation form was submitted for the WW2 classification on 9/4/2024. Mr. Rogers was changed to the ORC. • The new anoxic tanks do not have a valve at the bottom and additional valves were added to isolate the tanks if needed. • Sludge is removed once every 2-3 months, with 2-3 loads removed at each event. • Staff observed Z4 irrigating while on site. No warnings or errors were noted and the irrigation pump was operational. Page 3 of 9 Permit: WQ0035784 Owner - Facility: Boone Owner LLC Inspection Date: 08/29/2024 Inspection Type: Compliance Evaluation Reason for Visit: Routine Type Yes No NA NE Reuse (Quality) ❑ Infiltration System ❑ Lagoon Spray, LR ❑ Single Family Spray, LR ❑ Activated Sludge Spray, LR ❑ Activated Sludge Drip, LR ❑ Recycle/Reuse ❑ Single Family Drip ❑ Activated Sludge Spray, HR Treatment Yes No NA NE Are Treatment facilities consistent with those outlined in the current permit? 0 ❑ ❑ ❑ Do all treatment units appear to be operational? (if no, note below.) 0 ❑ ❑ ❑ Comment: Treatment Influent Pump Station Yes No NA NE Is the pump station free of bypass lines or structures? 0 ❑ ❑ ❑ Is the general housekeeping acceptable? ❑ ❑ ❑ Are all pumps present? ❑ ❑ ❑ Are all pumps operable? ❑ ❑ ❑ Are floats/controls operable? ❑ ❑ ❑ Are audio and visual alarms available? ❑ ❑ ❑ Are audio and visual alarms operational? ❑ ❑ ❑ # Are SCADA/Telemetry alarms required? ❑ ❑ ❑ Are SCADA/Telemetry available? ❑ ❑ ❑ Are SCADA/Telemetry operational? ❑ ❑ 0 ❑ Comment: Treatment Flow Measurement -Influent Yes No NA NE Is flowmeter calibrated annually? ❑ ❑ 0❑ Is flowmeter operating properly? ❑ ❑ ❑ Does flowmeter monitor continuously? ❑ ❑ ❑ Does flowmeter record flow? ❑ ❑ ❑ Does flowmeter appear to monitor accurately? ❑ ❑ ❑ Comment: Treatment Flow Measurement -Water Use Records Yes No NA NE Page 4 of 9 Permit: WQ0035784 Owner - Facility: Boone Owner LLC Inspection Date: 08/29/2024 Inspection Type: Compliance Evaluation Reason for Visit: Routine Is water use metered? ❑ ❑ 0 ❑ Are the daily average values properly calculated? ❑ ❑ 0 ❑ Comment: Treatment Flow Measurement -Effluent Yes No NA NE Is flowmeter calibrated annually? 0 ❑ ❑ ❑ Is flowmeter operating properly? 0 ❑ ❑ ❑ Does flowmeter monitor continuously? 0 ❑ ❑ ❑ Does flowmeter record flow? 0 ❑ ❑ ❑ Does flowmeter appear to monitor accurately? 0 ❑ ❑ ❑ Comment: Standby Power Yes No NA NE Is automatically activated standby power available? ❑ ❑ ❑ Is generator tested weekly by interrupting primary power source? ❑ ❑ ❑ Is generator operable? ❑ ❑ ❑ Does generator have adequate fuel? ❑ ❑ ❑ Comment: Treatment Barscreen Yes No NA NE Is it free of excessive debris? 0 ❑ ❑ ❑ Is disposal of screenings in compliance? 0 ❑ ❑ ❑ Are the bars spaced properly? ❑ ❑ 0 ❑ Is the unit in good condition? 0 ❑ ❑ ❑ Comment: Treatment Activated Sludge Yes No NA NE Is the aeration mechanism operable? ❑ ❑ ❑ Is the aeration basin thoroughly mixed? ❑ ❑ ❑ Is the aeration equipment easily accessed? ❑ ❑ ❑ Is Dissolved Oxygen adequate? ❑ ❑ ❑ Are Settleometer results acceptable? ❑ ❑ ❑ Is activated sludge an acceptable color? ❑ ❑ ❑ •AZT17, 17-XiU Treatment Filters Yes No NA NE Is the filter media present? 0 ❑ ❑ ❑ Is the filter media the correct size and type? ❑ ❑ ❑ Is the air scour operational? 0 ❑ ❑ ❑ Is the scouring acceptable? 0 ❑ ❑ ❑ Page 5 of 9 Permit: WQ0035784 Owner - Facility: Boone Owner LLC Inspection Date: 08/29/2024 Inspection Type: Compliance Evaluation Reason for Visit: Routine Is the clear well free of excessive solids? ❑ ❑ 0 ❑ Is the mud well free of excessive solids and filter media? ❑ ❑ 0 ❑ Does backwashing frequency appear adequate? 0 ❑ ❑ ❑ Comment: Treatment Sludge Storage/Treatment Yes No NA NE Is the aeration operational? 0 ❑ ❑ ❑ Is the aeration pattern even? ❑ ❑ ❑ If required, are Sanitary "Ts" present in tankage? ❑ ❑ 0 ❑ Comment: Treatment Disinfection Yes No NA NE Is the system working? ❑ ❑ ❑ Do the fecal coliform results indicate proper disinfection? ❑ ❑ ❑ Is there adequate detention time (-30 minutes)? ❑ ❑ ❑ Is the system properly maintained? ❑ ❑ ❑ If gas, does the cylinder storage appear safe? ❑ ❑ ❑ Is the fan in the chlorine feed room and storage area operable? ❑ ❑ ❑ Is the chlorinator accessible? ❑ ❑ ❑ If tablets, are tablets present? ❑ ❑ ❑ Are the tablets the proper size and type? ❑ ❑ ❑ Is contact chamber free of sludge, solids, and growth? ❑ ❑ ❑ If UV, are extra UV bulbs available? ❑ ❑ ❑ If UV, is the UV intensity adequate? ❑ ❑ ❑ # Is it a dual feed system? ❑ ❑ ❑ Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)? ❑ ❑ ❑ If yes, then is there a Risk Management Plan on site? ❑ ❑ ❑ If yes, then what is the EPA twelve digit ID Number? (1000- If yes, then when was the RMP last updated? Comment: Record Keeping Yes No NA NE Is a copy of current permit available? 0 ❑ ❑ ❑ Are monitoring reports present: NDMR? 0 ❑ ❑ ❑ NDAR? 0 ❑ ❑ ❑ Are flow rates less than of permitted flow? 0 ❑ ❑ ❑ Are flow rates less than of permitted flow? 0 ❑ ❑ ❑ Are application rates adhered to? 0 ❑ ❑ ❑ Page 6 of 9 Permit: WQ0035784 Owner - Facility: Boone Owner LLC Inspection Date: 08/29/2024 Inspection Type: Compliance Evaluation Reason for Visit: Routine Is GW monitoring being conducted, if required (GW-59s submitted)? 0 ❑ ❑ ❑ Are all samples analyzed for all required parameters? 0 ❑ ❑ ❑ Are there any 2L GW quality violations? ❑ ❑ 0 ❑ Is GW-59A certification form completed for facility? 0 ❑ ❑ ❑ Is effluent sampled for same parameters as GW? ❑ ❑ 0 ❑ Do effluent concentrations exceed GW standards? ❑ ❑ 0 ❑ Are annual soil reports available? 0 ❑ ❑ ❑ # Are PAN records required? ❑ ❑ 0 ❑ # Did last soil report indicate a need for lime? ❑ 0 ❑ ❑ If so, has it been applied? ❑ ❑ 0 ❑ Are operational logs present? 0 ❑ ❑ ❑ Are lab sheets available for review? 0 ❑ ❑ ❑ Do lab sheets support data reported on NDMR? 0 ❑ ❑ ❑ Do lab sheets support data reported on GW-59s? 0 ❑ ❑ ❑ Are Operational and Maintenance records present? 0 ❑ ❑ ❑ Were Operational and Maintenance records complete? 0 ❑ ❑ ❑ Has permittee been free of public complaints in last 12 months? 0 ❑ ❑ ❑ Is a copy of the SOC readily available? ❑ ❑ 0 ❑ No treatment units bypassed since last inspection? ❑ 0 ❑ ❑ Comment: See summary. End Use -Irrigation Yes No NA NE Are buffers adequate? 0 ❑ ❑ ❑ Is the cover crop type specified in permit? 0 ❑ ❑ ❑ Is the crop cover acceptable? ❑ ❑ ❑ Is the site condition adequate? ❑ ❑ ❑ Is the site free of runoff / ponding? ❑ ❑ ❑ Is the acreage specified in the permit being utilized? ❑ ❑ ❑ Is the application equipment present? ❑ ❑ ❑ Is the application equipment operational? ❑ ❑ ❑ Is the disposal field free of limiting slopes? ❑ ❑ ❑ Is access restricted and/or signs posted during active site use? ❑ ❑ ❑ Are any supply wells within the CB? ❑ ❑ ❑ Are any supply wells within 250' of the CB? ❑ ❑ ❑ How close is the closest water supply well? ❑ ❑ ❑ Is municipal water available in the area? ❑ ❑ ❑ # Info only: Does the permit call for monitoring wells? ❑ ❑ ❑ Page 7 of 9 Permit: WQ0035784 Owner - Facility: Boone Owner LLC Inspection Date: 08/29/2024 Inspection Type: Compliance Evaluation Reason for Visit: Routine Are GW monitoring wells located properly w/ respect to RB and CB? 0 ❑ ❑ ❑ Are GW monitoring wells properly constructed, including screened interval? ❑ ❑ ❑ ❑ Are monitoring wells damaged? 0 ❑ ❑ ❑ Comment: See summary. FIVE-DAY UPSET Storage Yes No NA NE Storage Type? 5-day detention pond Storage amount? 548000 Gallons # At what point is side -stream wastewater returned to treatment? EQ Tank Is there a Spill Control Plan? 0 ❑ ❑ ❑ Aerated or Mixed? NONE If aeration is present, is it adequate? ❑ ❑ ❑ If present, are diffusers cleaned regularly? ❑ ❑ ❑ Is influent structure acceptable? ❑ ❑ ❑ Are banks/berms free of seepage and erosion? ❑ ❑ ❑ Are banks/berms free of excessive vegetation? ❑ ❑ ❑ Is pond lined? ❑ ❑ ❑ Liner Type Is liner acceptable? ❑ ❑ ❑ Are baffles/curtains acceptable? ❑ ❑ ❑ Does the pond have a freeboard marker? 0 ❑ ❑ ❑ Required freeboard? 2 Feet Actual freeboard? 24 Feet Is there suitable grassed vegetation? ❑ ❑ On Is the vegetation maintained? ❑ ❑ 0 ❑ Is the area free of excessive weeds and/or woody species? ❑ ❑ 0 ❑ Is the area free from signs of overflow? 0 ❑ ❑ ❑ Is color acceptable? 0 ❑ ❑ ❑ Are floating mats acceptable? ❑ 0 ❑ ❑ No excessive buildup of solids? 0 ❑ ❑ ❑ Are aerators/mixers acceptable? ❑ ❑ 0 ❑ Is effluent structure acceptable? 0 ❑ ❑ ❑ If present, is pond cover acceptable? ❑ ❑ 0 ❑ Page 8 of 9 Permit: WQ0035784 Owner - Facility: Boone Owner LLC Inspection Date: 08/29/2024 Inspection Type: Compliance Evaluation Comment: Tank is being pumpd down for mats to be removed. WET WEATHER STORAC Storage Storage Type? Storage amount? # At what point is side -stream wastewater returned to treatment? Is there a Spill Control Plan? Aerated or Mixed? If aeration is present, is it adequate? If present, are diffusers cleaned regularly? Is influent structure acceptable? Are banks/berms free of seepage and erosion? Are banks/berms free of excessive vegetation? Is pond lined? Liner Type Is liner acceptable? Are baffles/curtains acceptable? Does the pond have a freeboard marker? Required freeboard? Actual freeboard? Is there suitable grassed vegetation? Is the vegetation maintained? Is the area free of excessive weeds and/or woody species? Is the area free from signs of overflow? Is color acceptable? Are floating mats acceptable? No excessive buildup of solids? Are aerators/mixers acceptable? Is effluent structure acceptable? If present, is pond cover acceptable? Comment: Floating mats have been removed. Tank was empty. Reason for Visit: Routine Yes No NA NE Aboveground storage tank 1562000 Gallons ■❑❑❑ NONE 2 Feet 24 Feet Page 9 of 9 15A NCAC 02T .0403 PERMITTING BY REGULATION (a) Collection systems having an actual, permitted or Division -approved average daily flow less than 200,000 gallons per day shall be deemed permitted, pursuant to Rule .0113 of this Subchapter if the system meets the criteria in Rule .0113 of this Subchapter and all criteria required in this Rule: (1) The collection system shall be effectively maintained and operated at all times to prevent discharge to land or surface waters and to prevent any contravention of groundwater standards or surface water standards. (2) A map of the collection system shall have been developed and shall be maintained. (3) An operation and maintenance plan, including pump station inspection frequency, preventative maintenance schedule, spare parts inventory, and overflow response shall have been developed and implemented. (4) Pump stations that are not connected to a telemetry system shall be inspected by the permittee or its representative every day, 365 days per year, unless the permittee demonstrates that daily inspections are not necessary because the pump station has sufficient storage capacity, above the elevation at which the pump activates, to justify a longer inspection interval. In no case shall the inspection interval exceed seven days. Pump stations that are connected to a telemetry system shall be inspected once per week. (5) High -priority sewers shall be inspected by the permittee or its representative once every six - months, and inspections shall be documented. (6) A general observation by the permittee or its representative of the entire collection system shall be conducted once per year. (7) Overflows and bypasses shall be reported to the appropriate Division regional office in accordance with 15A NCAC 02B .0506(a), and public notice shall be provided as required by G.S. 143- 215.1 C. (8) A Grease Control Program shall be in place as follows: (A) For publicly owned collection systems, the Grease Control Program shall include bi- annual distribution of educational materials for both commercial and residential users and the legal means to require grease interceptors for new construction and retrofit and if necessary, of grease interceptors at existing establishments. The plan shall also include legal means for inspections of the grease interceptors, enforcement for violators and the legal means to control grease entering the system from other public and private satellite collection systems. (B) For privately owned collection systems, the Grease Control Program shall include bi- annual distribution of grease education materials to users of the collection system by the permittee or its representative. (C) Grease education materials shall be distributed more often than required in Parts (A) and (B) of this Subparagraph if necessary to prevent grease -related sanitary sewer overflows. (9) Right-of-ways and easements shall be maintained in the full easement width for personnel and equipment accessibility. (10) Documentation of compliance with Subparagraphs (a)(1) through (a)(9) of this Rule shall be maintained by the collection system owner for three years with the exception of the map, which shall be maintained for the life of the system. (b) Private collection systems on a single property serving an industrial facility from which the domestic wastewater contribution is less than 200,000 gallons per day shall be deemed permitted. (c) The Director may determine that a collection system shall not be deemed to be permitted in accordance with this Rule and Rule .0113 of this Subchapter. This determination shall be made in accordance with Rule .0113(e) of this Subchapter. History Note: Authority G.S. 143-215.1(a); 143-215.3(a); 143-215.9B; Eff September 1, 2006; Readopted Eff September], 2018.