HomeMy WebLinkAboutWQ0045779_Application_20240903State of North Carolina
fi fi Department of Environmental Quality
�;.. Division of Water Resources
15A NCAC 01T .0300 — ALTERNATIVE SEWER EXTENSION APPLICATION
Division of Water Resources INSTRUCTIONS FOR FORM: ASEA 10-23 & SUPPORTING DOCUMENTATION
Plans, specifications and supporting documents shall be prepared in accordance with, 15A NCAC 02T .0100, 15A NCAC 02T
.0300, Division Policies and p—god engineering practices. Failure to submit all required items will necessitate additional
processing and review time, and may result in return of the application.
For more information, visit the Water- Quality Permitting Section's collection systems ivebsite
General — When submitting an application, please use the following instructions as a checklist in order to en ��Vre
r�i s are
submitted. Adherence to these instructions and checking the provided boxes will help produce a quicker revs mie an e the
amount of requested additional information.
Unless otherwise noted, the A licant shall submit one on nal and one co AUG 0 men
pp gi py of the application and supportmg ocuentation.
A. One Original and One Copy of Application and Supporting Documents
® Required unless otherwise noted
NCDEQ/DWR/NPDES
B. Cover Letter (Required for All Application Packages):
® List all items included in the application package, as well as a brief description of the requested permitting action.
➢ Be specific as to the system type, number of homes served, flow allocation required, etc.
➢ If necessary for clarity, include attachments to the application form.
➢ If the project is funded by American Rescue Plan Act (ARPA) funds, please include the ARPA project number in the
cover letter and in parentheses under Project Name (Section II.1. of the application).
C. Application Fee (All Nevv and Major Modification Application Packages):
® Submit a check or money order in the amount of $600.00 dated within 90 days of application submittal.
➢ Payable to North Carolina Department of Environmental Quality (NCDEQ).
D. Alternative Sewer Extension (Form: ASEA 10-23) Application (Required for All Application Packages):
® Submit the completed and appropriately executed application.
➢ If necessary for clarity or due to space restrictions, attachments to the application may be made.
® If the Applicant Type in Item 1.2 is a corporation or company, provide documentation it is registered for business with
the North Carolina Secretary of State.
❑ If the Applicant Type in Item I.2 is a partnership or d/b/a, enclose a copy of the certificate filed with the Register of
Deeds in the county of business.
® The project name in Item I1.1 shall be consistent with the project name on the plans, specifications, flow acceptance
letters, agreements, etc.
® The Professional Engineer's Certification on Page 5 of the application shall be signed, sealed and dated by a North
Carolina licensed Professional Engineer.
® The Applicant's Certification on Page 5 of the application shall be signed in accordance with 15A NCAC 02T .0106(b).
Per 15A NCAC 02T .0106(c), an alternate person may be designated as the signing official if a delegation letter is
provided from a person who meets the criteria in 15A NCAC 02T .0106(b).
E. Section X & XI Attachment (If Applicable):
® If the project includes gravity sewer, pump stations with multiple pumps and force mains, include the Section X & XI
attachment(s).
F. Flow Tracking/Acceptance Form (Form: FTSE 10-23) (If Applicable):
® Submit the completed and appropriately executed Flow Tracking/Acceptance for Sewer Extension Permit Form from the
owners of the downstream sewers and treatment facility.
➢ The flow acceptance indicated in form FTSE 10-23must not expire prior to permit issuance and must be dated less than
one year prior to the application date.
INSTRUCTIONS FOR FORM: ASEA 10-23 & SUPPORTING DOCUMENTATION Pagel of 4
➢ Submittal of this application and form FTSE 10-23indicates that owner has adequate capacity and will not violate G.S.
143-2_ 15.67(a).
➢ Intergovernmental agreements or other contracts will not be accepted in lieu of a project -specific FTSE 10-23.
INSTRUCTIONS FOR FORM: ASEA 10-23 & SUPPORTING DOCUMENTATION Page 2 of 4
G. Engineering Plans (Required for All Application Packages):
® Per 15A NCAC 02T:0305(b)(1), submit two sets of detailed plan sets that have been signed, sealed and dated by a North
Carolina licensed Professional Engineer, and shall include at a minimum:
➢ Table of contents with each sheet numbered.
➢ A general location map with at least two geographic references and a vicinity map.
➢ Plan and profile views of the sewer extension as well as the proximity of the sewer extension to other utilities and natural
features
➢ Detail drawings of all items pertinent to the sewer extension (including clean -out locations) and pump stations.
➢ The location of all wells (including usage and construction details if available), streams (ephemeral, intermittent, and
perennial), springs, lakes, ponds, and other surface drainage features within 100 feet of the project.
➢ Minimum separations required per 15A NCAC 02T.0305(f), and where separations cannot be maintained, alternative
criteria per 15A NCAC 02T.0305(g).
➢ Minimum cover for sewer extensions required per 15A NCAC 02T.0305(f) must also be shown clearly on the plans.
➢ Nodes/Zones listed in calculations and computer models must be accurately reflected on the plans.
➢ Plans must include lot numbers, zones, approximate pump and top of wet well elevations, and pump model number and
capacity in a table format.
® Plans shall represent a completed design and not be labeled with preliminary phrases (e.g., FOR REVIEW ONLY, NOT
FOR CONSTRUCTION, etc.) that indicate they are anything other than final plans. However, the plans may be labeled
with the phrase: FINAL DESIGN - NOT RELEASED FOR CONSTRUCTION.
H. Specifications (Required for All Application Packages):
® Per _15A NCAC 02T .0305(b)(3), submit specifications that have been signed, sealed and dated by a North Carolina
licensed Professional Engine , and shall include at a minimum:
➢ Table of contents with each section/page numbered.
➢ Detailed specifications for pump stations (i.e. packaged grinder pump requirements, valves, controls, etc.)
➢ Site Work (i.e., earthwork, clearing, grubbing, excavation, trenching, backfilling, compacting, fencing, seeding, etc.)
➢ Materials (i.e., low pressure mains and laterals, force main, gravity, concrete, method of construction, etc.)
➢ Electrical (i.e., control panels, transfer switches, automatically activated standby power source, etc.)
➢ Means for ensuring quality and integrity of the finished product in accordance with the Minimum Design Criteria,
including leakage and pressure testing for the sewer extension.
® Specifications shall represent a completed design and not be labeled with preliminary phrases (e.g., FOR REVIEW
ONLY, NOT FOR CONSTRUCTION, etc.) that indicate they are anything other than final specifications. However, the
specifications may be labeled with the phrase: FINAL DESIGN - NOT RELEASED FOR CONSTRUCTION.
® Specifications for standard equipment may only be omitted for municipalities with approved standard specifications, but
the use of the standard specifications must be noted on each sheet of the plans.
I. Engineering Calculations (All Application Packages):
® Per 15A NCAC 02T .0305 2 and 15A NCAC 02T .0305fj 1), submit engineering calculations that have been signed,
sealed and dated by a North Carolina licensed Professional Engineer, and shall include at a minimum:
➢ Friction/Total Dynamic Head calculations and system curve analysis (with one pump running, two pumps running, etc.)
➢ Pump selection information including pump curves, manufacturer's information, and recommended installation
guidelines.
➢ Pump station cycle times and pump run times.
➢ Minimum velocities in the sewer extension in accordance with the Minimum Design Criteria
➢ Flotation calculations for all units constructed partially or entirely below grade (i.e. pump stations)
® If computer models are provided to document system design, the model and corresponding node/zone nomenclature must
clearly and accurately reflect the plans and specifications.
Note that upon completion of the review process and prior to permit issuance, a request for the final plans and
specifications will be requested on digital media (CD, DVD, Jump Drive, etc.) for our records. You -will be notified when
this information is requested, as the review may necessitate changes
INSTRUCTIONS FOR FORM: ASEA 10-23 & SUPPORTING DOCUMENTATION Page 3 of 4
J. Downstream Sewer Evaluations (All Application Packages)
® Per 15A NCAC 02T .0305(b)(2) and 15A NCAC 02T .0304 1 , submit engineering calculations that have been signed,
sealed and dated by a North Carolina licensed Professional Engineer, for receiving collection systems:
❑ For connection to a gravity sewer, submit:
An evaluation of the gravity sewer based on peak flow from the proposed project and peak flows already tributary to the
existing gravity sewer. Provide calculations and detail how existing peak flows were determined.
❑ For connection to a pump station, submit:
An evaluation of the existing pump station to pump peak flow from the proposed project and peak flows already tributary
to the existing pump station. Provide calculations and detail how existing peak flows were determined.
® For connection to a force main/low pressures sewer, submit:
An evaluation of the existing system based on peak flows from the proposed project and peak flows already tributary to
the existing system. In addition, evaluate the ability of each pump station tributary to the existing system to pump against
additional head created by greater flows through the system. Evaluation may include alternative designs such as telemetry
to coordinate pumping between pump stations (provided sufficient storage is available). Also include an evaluation of
the discharge point of the existing force main/pressure sewer.
K. Site Maps (All Application Packages):
® Submit an 8.5-inch x 11-inch color copy of a USGS Topographic Map of sufficient scale to identify the entire project
area and closest surface waters.
➢ Location of the project (gravity sewer, pump stations & force main)
➢ Downstream connection points and permit number (if known) for the receiving sewer
® Include a street level map showing general project area.
L. Existing Permit (All Modification Packages):
❑ Submit the most recently issued existing permit.
❑ Provide a list of any items within the permit the Applicant would like the Division to address during the permit
modification (i.e., permit description, flow allocation, treatment facility, etc.).
M. Power Reliability Plan (All Application Packages):
❑ Per 15A NCAC 02T .0305(h)(1)(D), submit documentation of power reliability for simplex/vacuum units.
® Per 15A NCAC 02T .0305(h)(1), submit documentation of power reliability for pumping stations.
➢ This alternative is only available for average daily flows less than 15,000 gallons per day
➢ It shall be demonstrated to the Division that the portable source is owned or contracted by the applicant and is compatible
with the station. The Division will accept a letter signed by the applicant (see 15A NCAC 02T .0106(b)) or proposed
contractor, stating that "the portable power generation unit or portable, independently -powered pumping units, associated
appurtenances and personnel are available for distribution and operation of this pump station."
➢ If the portable power source or pump is dedicated to multiple pump stations, an evaluation of all the pump
stations' storage capacities and the rotation schedule of the portable power source or pump, including travel
tinieframes, shall be provided in the case of a multiple station power outage. (Required at time of certification)
N. Final Environmental Document (If Applicable):
❑ Per 15A NCAC 02T .0105(c)(4), submit one copy of the environmental assessment and one copy of the final
environmental document (i.e., Finding of No Significant hnpact or Record of Decision).
❑ Include information on any mitigating factors from the Enviromnental Assessment that impact the design and/or
construction of the subject sewer.
O. Certificate of Public Convenience and Necessity (All Application Packages for Privately -Owned Public Utilities):
❑ Per 15A NCAC 02T .0115(a)(1) provide the Certificate of Public Convenience and Necessity from the North Carolina
Utilities Commission demonstrating the Applicant is authorized to hold the utility franchise for the area to be served by
the sewer extension. or
❑ Provide a letter from the North Carolina Utilities Commission's Water and Sewer Division Public Staff stating an
application for a franchise has been received and that the service area is contiguous to an existing franchised area or that
franchise approval is expected.
INSTRUCTIONS FOR FORM: ASEA 10-23 & SUPPORTING DOCUMENTATION Page 4 of 4
P. Operational Agreements (Applications from HOA/POA and Developers for lots to be sold):
❑ Home/Propert�wners' Associations
❑ Per 15A NCAC 02T .0115(c, submit the properly executed Operational Agjeement FORM: HOA .
❑ Per 15A NCAC 02T .0115( submit a copy of the Articles of Incorporation, Declarations and By-laws.
❑ Developers of lots to be sold
❑ Per 15A NCAC 02T .0115fb), submit the properly executed Operational Agreement FORM: DEV1.
THE COMPLETED APPLICATION AND SUPPORTING DOCUMENTATION SHALL BE SUBMITTED TO:
NCDEQ/DR'R
WATER QUALITY SECTION
PERCS UNIT
By U.S. Postal Service:
1617 MAIL SERVICE CENTER
RALEIGH, NORTH CAROLINA 27699-1636
TELEPHONE NUMBER: (919) 807-6312
By Courier/Special Deliverv:
512 N. SALISBURY ST. SUITE 925
RALEIGA NORTH CAROLINA 27604
INSTRUCTIONS FOR FORM: ASEA 10-23 & SUPPORTING DOCUMENTATION Page 5 of 4
State of North Carolina
Department of Environmental Quality
Division of Water Resources
15A NCAC 02T .0300 — ALTERNATIVE SEWER EXTENSION APPLICATION
Division of Water Resources ASEA 10-23 & SUPPORTING DOCUMENTATION
Application Number: 00� J � 79 (to be completed by DWR)
I. APPLICANT INFORMATION:
1. Applicant's name: ONWASA (company, municipality, HOA, utility, etc.)
2. Applicant type: ❑ Individual ® Corporation ❑ General Partnership ❑ Privately -Owned Public Utility
❑ Federal ❑ State ❑ Municipal ❑ County
3. Signature authority's name: Jeffrey Lohr, PE per 15A NCAC 02T .0106(b)
Title: Chief of Engineering
4. Applicant's mailing address: 228 Georgetown Road
City: Jacksonville State: NC Zip: 28540-
5. Applicant's contact information:
Phone number: (910) 455-0722 Email Address: JLo onwasa.com
II. PROJECTINFORMATION:
1. Project name: 6632 Gum Branch Road
2. Application/Project status: ® Proposed (New Permit) ❑ Existing PermidProject ❑ ARPA funded
If a modification, provide the existing permit number: WQ00 and issued date:
If new construction but part of a master plan, provide the existing permit number: WQ00
3. County where project is located: Onslow
4. Approximate Coordinates (Decimal Degrees): Latitude: 34.8781' Longitude:-77.5104'
III. CONSULTANT INFORMATION:
1. Professional Engineer: Jason A. Houston License Number: PE 34978
Firm: Tidewater Associates. Inc.
Mailing address: 306 New Bridge Street
City: Jacksonville State: NC Zip: 28540-
Phone number: (910) 455-2414 Email Address: offic tidewaterenc.com
IV. WASTEWATER TREATMENT FACILITY (N4'WTF) INFORMATION:
1. Facility Name: Richlands VdWTF Permit Number: NC 0023230
Owner Name: OnVASA
V. RECEIVIIN'G DOWNSTREAM SEWER INFORMATION:
1. Permit Number(s): W 34892
System Wide Collection System Permit Number(s):
Owner Name(s): ONWASA
FORM: ASEA 10-23 Pagel of 5
N'I. GENERAL REQUIRENIENTS
1. If the Applicant is a Privately -Owned Public Utility, has a Certificate of Public Convenience and Necessity been submitted?
❑ Yes ❑No ®N/A
2. If the Applicant is a Developer of lots to be sold, has a Developer's Operational A reement FORM: DEV been submitted?
❑ Yes ❑No ®N/A
3. If the Applicant is a Home/Property Owners' Association, has an Operational Agreement (FORM: HOA) been submitted?
❑ Yes ❑No ®N/A
4. Origin of wastewater: (check all that apply):
® Residential Owned ❑ Retail (stores, centers, malls) ❑ Car Wash
❑ Residential Leased ❑ Retail with food preparation/service ❑ Hotel and/or Motels
❑ School / preschool / day care ❑ Medical / dental / veterinary facilities ❑ Swimming Pool /Clubhouse
❑ Food and drink facilities ❑ Church
❑ Swimming PoolfFilter Backwash
❑ Businesses / offices / factories ❑ Nursing Home ❑ Other (Explain in Attachment)
5. Is/was an Environmental Assessment required under 15A NCAC OIC? ❑ Yes ® No
If yes, submit the appropriate final environmental document (FONSI, ROD, etc.)
6. Nature of wastewater: 100 % Domestic/Commercial0 % Other waste — specify:
0 % Industrial (See 15A NCAC 02T .0103(20))
7. Wastewater generated by project: 300 GPD q-)er 15A NCAC 02T .0114 and G.S. 143-215.1
Hasa flow reduction been approved under 15A NCAC 02T .0114(f)? ❑ Yes ❑ No
If yes, provide a copy of approval
S. Summarize wastewater generated by project:
Establishment Type
Daily Design Flow °
No. of Units
Flow
4 Bedroom Dwelling Unit
300 gal/Unit
1
300 GPD
gal/
GPD
gall
GPD
gal/
GPD
gal/
GPD
gal/ J
GPD
Total
�30OPD
a See 15A NCAC 02T .0114(b), (d). (e)(1) and (e)(2) for caveats to wastewater design flow rates (i.e., minimum flow per
dwelling; proposed unknown non-residential development uses; public access facilities located near high public use areas;
and residential property located south or east of the Atlantic Intracoastal Waterway to be used as vacation rentals as defined
in G.S. 42A-4).
b Per 15A NCAC 02T .0114(c), design flow rates for establishments not identified below shall be determined using available
flow data, water using fixtures, occupancy or operation patterns, and other measured data.
FORM: ASEA 10-23 Page 2 of 5
VII. PRESSURE SERER DESIGN CRITERIA —15A NCAC 02T .0305:
1. Number of simplex pump stations (STEP tanks/effluent pumps, vacuum pits, etc.) provided: 1
2. What is the nearest 100-year flood elevation to the facility? 25.9 feet mean sea level.
Is any of the proposed project located within the 100-year flood plain? ❑ Yes ®No
3. If Yes, are the following items provided per 15A NCAC 02T .0305 e
Water -tight seals on all station hatches and manholes; and
Control panels vents extend two feet above the100-year flood plain elevation? ❑ Yes ❑ No ® N/A
If No, what measures are being taken to protect them against flooding?
4. Volume of storage in vet ,.yell above pump on elevation: 658 Gallons include calculations
5. How power reliability will be provided in accordance with 15A NCAC 02T .0305(h)(D):
® Wet well storage provides 24 hours worth of wastewater storage; or
❑ Wet well storage provides wastewater storage based on power reliability and response times
(See "Policy for Meeting_ Reliability Requirements")
➢ Provide 3 years of power history date in the area.
➢ Provide response time to replace a failed pump. This would include travel time, time to replace pump, etc.
➢ Wet well storage would be based on whichever is greater.
All other pump stations meet the reliability requirements of 15A NCAC 02T .0305 h 1 : ❑ Yes ❑ No ® N/A
6. Summarize simplex pump station design elements:
Design Element
Plan Sheet Specification
Reference Reference
Emergency Contact Placard or Sticker
1
Screened Wet Well Vent
1
Restricted Access Details
1
Control Panel
High Water Alarms (Audible & Visual)
1
1
Valves (Check, Gate, etc)
1
Air Relief Valves
7. Summarize the pipe length by diameter to be permitted. Lines from a building to the septic or pump tank should be excluded.
(provide attachments if necessary)
Zone a From Node ' To Node I Diar
1 1 45 1 42
Teter (in)
Length (feet)
# Pumps in Zone
Pump Model
Specified for Zone
1
100
i
Flygt 1.7 HP
8. Air release valve station locations per 15A NCAC 02T .03056) (provide attachments if necessary)
----FAir Release Valve # Station Plan Sheet Reference
FORM: ASEA 10-23 Page 3 of 5
VIII. SETBACKS & SEPARATIONS — (02B .0200 & 15A NCAC 02T .0305(f)):
1. Does the project comply with all separations found in 15A NCAC 02T .0305 &
➢ 15A NCAC 02T.0305(fl contains minimum separations that shall he nrovvled fnr saxxrar cuc,
® Yes ❑ No
Setback Parameter*
Separation Required
Storm sewers and other utilities not listed below vertical
24 inches
Water mains vertical -water over sewer including in benched trenches
18 inches
Water mains horizontal
10 feet
Reclaimed water lines vertical - reclaimed over sewer
18 inches
Reclaimed water lines horizontal - reclaimed over sewer
2 feet
**Any private or public water supply source, including any wells, WS-I waters of Class I or
Class Il im ,ounded reservoirs used as a source of drinking water
100 feet
**Waters classified WS (except WS-I or WS-V), B, SA, ORW, HQW, or SB from normal
high water or tide elevation and wetlands see item IX.2
50 feet
**Any other stream, lake, impoundment, or ground water lowering and surface drainage
ditches
10 feet
5 feet
Aa building foundation
Any basement
10 feet
Top slope of embankment or cuts of 2 feet or more vertical height
10 feet
Drainage systems and interceptor drains
5 feet
Any swimmin ools
10 feet
Final earth c:rade vertical
36 inches
➢ 15A NCAC 02T.0305(9) contains alternatives where separations in 02T.0305(fl cannot be achieved.
➢ **Stream classifications can be identified using the Division's NC Surface Water Classifications weboaae
➢ If noncompliance with 02T.0305(f) or (e). see Section IX of this application
2. Does the project comply with separation requirements for wetlands? (50 feet of separation) [:]Yes []No ® N/A
➢ See the Division's draft separation requirements for situations where separation cannot be meet
➢ No variance is required if the alternative design criteria specified is utilized in design and construction
➢ As built documents should reference the location of areas effected
3. Does the project comply with setbacks found in the river basin rules per 15A NCAC 02B .0200? ❑ Yes El No ® N/A
➢ This would include Trout Buffered Streams per 15A NCAC 2B.0202
4. Does the project require coverage/authorization under a 404 Nationwide or [:]Yes ® No
individual permits or 401 Water Quality Certifications?
➢ Information can be obtained from the 401 & Buffer Permittinit Branch
5. Does project comply with 15A NCAC 02T.0105 c 6) (additional permits/certifications)? ® Yes ❑ No
Per 15A NCAC 02T.0105(c)(6), directly related environmental permits or certification applications are being prepared, have
been applied for, or have been obtained. Issuance of this permit is contingent on issuance of dependent permits (erosion and
sedimentation control plans, stormwater management plans, etc.).
6. Does this project include any sewer collection lines that are deemed "high -priority?"
Per 15A NCAC 02T.0402, "high -priority sewer" means "any aerial sewer, sewer contacting surface waters, siphon, or sewer
positioned parallel to streambanks that is subject to erosion that undermines or deteriorates the sewer.
❑ Yes ® No
➢ If yes, include an attachment with details for each line, including type (aerial lute, size, material, and location).
High priority lines shall be inspected by the permittee or its representative at least once every six -months and inspections
documented per 15A NCAC 02T.0403(a)(5) or the permitee's individual System-«'ide Collection permit.
FORM: ASEA 10-23 Page 4 of 5
IX. CERTIFICATIONS:
Does the submitted system comply with 15A NCAC 02T, the Minimum Design Criteria for the PermittiStations
and Force Mains t latest version;, and the Gravity Sewer Minimum Design Cn of Priteria {latest version} as applicable?
// ■
If No, complete and submit the Variance/Alternative Design Request application (VADC 10-14) and supporting documents for
review. Approval of the request is required prior to submittal of the Fast Track Application and supporting documents.
2. Professional Engineer's Certification:
OLS(3n PI'Sion, � t. attest that this application for
' (Professional Engineer's name from Application Item III.1.)
(Facility name from Application Item 11.1.)
has been reviewed by me and is accurate, complete and consistent with the information supplied in the plans, specifications,
engineering calculations, and all other supporting documentation to the best of my knowledge. I further attest that to the best
of my knowledge the proposed design has been prepared in accordance with this application package and its instructions, as
well as all applicable regulations and statutes. Although other professionals may have developed certain portions of this
submittal package, inclusion of these materials under my signature and seal signifies that I have reviewed this material and
have judged it to be consistent with the proposed design.
NOTE — In accordance with General Statutes 143-215.6A and 143-2I5.6B any person who knowingly makes any false
statement, representation, or certification in any application package shall be guilty of a Class 2 misdemeanor, which may
include a fine not to exceed $10,000, as well as civil penalties up to $25,000 per violation..,.,.%
North Carolina Professional Engineer's seal, signature, and date:
3. Applicant's Certification per 15A NCAC 02T .0106 b :
J €� 2
(Signature Authority's name & title from
�(FaciAityname4romVpp1icaAion em
io Sa��,�,,
i
a SEAL fir;
• 34919 '
19*d Y
attest that this application for
has been reviewed by me and is accurate and complete to the best of my knowledge. I understand that any discharge of
wastewater from this non -discharge system to surface waters or the land will result in an immediate enforcement action that
may include civil penalties, injunctive relief, and/or criminal prosecution. I will make no claim against the Division of Water
Resources should a condition of this permit be violated. I also understand that if all required parts of this application package
are not completed and that if all required supporting information and attachments are not included, this application package
will be returned to me as incomplete. As t�permittee for the Pressure sewer system. I understand I will be required to
own, maintain. and operate all individual pump stations.
NOTE — In accordance with General Statutes 143-2I5.6A and 143-215.6B, any person who knowingly makes any false
statement, representation, or certification in any application package shall be guilty of a Class 2 misdemeanor, which may
include a fine not to exceed $10,000 as well as civil penalties up to $25,000 per violation.
Signature: _ _ Date:?/2
FORM: ASEA 10-23 Page 5 of 5