HomeMy WebLinkAboutNC0070033_Fact Sheet_20240815Docusign Envelope ID: 728D37AC-234C-42F6-BE47-D0654BB880EC
NCDEQ / DWR / NPDES
EXPEDITED FACT SHEET - NPDES PERMIT RENEWAL
NPDES Permit NCO070033
Catherine Shadwell, Compliance & Expedited Permitting Unit / 919-707-3613 April 2024
FACILITY INFORMATION
Applicant/Facility Name
Quail Run MHP Pads LLC (attn Kevin Murray, Owner)
Quail Run Mobile Home Park
Applicant Mailing Address
113 Center St Suite 201 Lexington NC 27292
Facility Physical Address
136 Quail Place Dr Winston-Salem NC 27127
Permitted Flow (MGD)
0.017 MGD
Type of Waste
100% Domestic, < 1 MGD
Facility Class
WW-1
County
Davidson
Permit Status
Renewal
Regional Office
WSRO
STREAM CHARACTERISTICS
Receiving Stream
Miller Creek
Stream
Classification
C
Stream Segment
12-94-14
Outfall Lat.
350 59' 12.1" N
7Q10 - Summer (cfs)
0.2
Outfall Long.
800 15' 59" W
7Q 10 - Winter (cfs)
0.4
Drainage basin
Yadkin -Pee Dee
30Q2 (cfs)
0.5
Subbasin
03-07-04
Average Flow (cfs)
1.4
HUC
030401011308
IWC (%)
11.64% (summer) /
6.18% (winter)
303(d) List
Not listed.
BASIC INFO FOR EXPEDITED PERMIT RENEWAL
Does permit need Daily Max NH3 limits?
Already present in permit
Does permit need TRC limits/footnote?
Already present in permit
Does permit have toxicity testing?
No
Does permit have any Special Conditions?
Yes, nutrient reopener for High Rock Lake
Does permit have instream monitoring?
Yes, Upstream and Downstream for temperature and DO
New expiration date:
May 31, 2029
Facility Summary
Quail Run MHP Pads LLC operates a minor (flow < 1 MGD) wastewater facility to serves a Mobile Home
Park of about 100 residents. Quail Run Mobile Home Park's WWTP treats 100% domestic wastewater and
has a design capacity and permitted flow of 0.017 MGD. The WWTP was originally permitted in 1987.
This facility utilizes the following treatment components:
• Two 3,200-gallon septic tanks
• 4,000-gallon septic tank
• Two 4,500-gallon septic tanks
• 8,400-gallon recirculating dosing tank
• 4,250 ftz recirculating surface sand filter
• Tablet chlorinator
• 350-gallon chlorine contact tank
• De -chlorination contact tank*
*observed by WSRO staff at recent inspection but not listed on previous component list.
Fact Sheet for Permit Renewal
April 2024 - NPDES Permit NCO070033 - Page 1
Docusign Envelope ID: 728D37AC-234C-42F6-BE47-D0654BB880EC
Renewal Summary
This renewal contains the following changes:
• Updated Section A. (3.) to reflect current federal requirements for Electronic Reporting of
Discharge Monitoring Reports.
• Updated outfall map
• Updated winter ammonia limits per NCAC 2B .0404(c) — Winter limits can be no less stringent
than 2 times the summer limits. New winter ammonia limits will go into effect January 1, 2029.
Compliance History
Looking through the past 5 years (since 2019), this facility has received 8 NOVs and 3 NODs. 5 out of the 8
NOVs were due to an exceedance of Fecal Coliform.
The most recent inspection (performed June 2023) found that the facility was taking upstream samples in an
UT, instead of the permitted 100ft upstream of the outfall. There were also observations of ponding in the
sand filter; as well as discrepancies in the 5 septic tank locations, and use of the chlorination and
dechlorination systems.
Comments on Draft Permit
Fact Sheet for Permit Renewal
April 2024 - NPDES Permit NC0070033 - Page 2
Docusign Envelope ID: 728D37AC-234C-42F6-BE47-D0654BB880EC
IWC Calculations
Facility: Quail Run Mobile Home Park
Permit No.: NC0070033
Prepared By: Catherine Shadwell
Enter Design Flow (MGD): 0.017 <= Permitted Flow if Different from Design
Enter s7Q10 (cfs): 0.2
Enter w7Q10 (cfs): 0.4
Total Residual Chlorine (TRC)
Ammonia (Summer)
Daily Maximum Limit (ug/1)
Monthly Average Limit (mg NH3-N/1)
Design Permitted
Design Permitted
s7Q10 (CFS)
0.2
s7Q10 (CFS)
0.2
DESIGN FLOW (MGD)
0.017 €
DESIGN FLOW (MGD)
0.017 €
DESIGN FLOW (CFS)
0.02635
DESIGN FLOW (CFS)
0.02635
STREAM STD (UG/L)
17.0
STREAM STD (MG/L)
1.0
Upstream Bkgd (ug/1)
0
Upstream Bkgd (mg/1)
0.22
IWC (%)
11.64
IWC (%)
11.64
Allowable Conc. (ug/1)
146
Allowable Conc. (mg/1)
6.9
Ammonia (Winter)
Monthly Average Limit (mg NH3-N/1)
Design Permitted
Design Permitted
Fecal Coliform
w7Q10 (CFS)
0.4
Monthly Average Limit:
200/100ml € #VALUE!
DESIGN FLOW (MGD)
0.017
(If DF >331; Monitor)
DESIGN FLOW (CFS)
0.02635
(If DF<331; Limit)
STREAM STD (MG/L)
1.8
Dilution Factor (DF)
8.59 #VALUE!
Upstream Bkgd (mg/1)
0.22
IWC (%)
6.18
Allowable Conc. (mg/1)
25.8
*2B .0404 (c) Applies
Total Residual Chlorine
1. Cap Daily Max limit at 28 ug/I to protect for acute toxicity
Ammonia (as NH3-N)
1. If Allowable Conc > 35 mg/l, Monitor Only
2. Monthly Avg limit x 3 = Weekly Avg limit (Municipals)
3. Monthly Avg limit x 5 = Daily Max limit (Non-Munis)
If the allowable ammonia concentration is > 35 mg/L, no limit shall be imposed
By Policy dischargers < 1 MGD get limits no lower than 2 & 4 due to BAT
* From 2B .0404(c) - Winter Limits can be no less stringent than 2 times the summer limits
Fecal Coliform
1. Monthly Avg limit x 2 = 400/100 ml = Weekly Avg limit (Municipals) = Daily Max limit (Non -Muni)
Docusign Envelope ID: 728D37AC-234C-42F6-BE47-D0654BB880EC
70097050 70961415
AFFIDAVIT OF PUBLICATION
STATE OF NORTH CAROLINA LEXINGTON, NC May 16, 2024
DAVIDSON COUNTY
I, Lynn Bowers OF THE DISPATCH, A NEWSPAPER PUBLISHED IN THE CITY OF LEXINGTON, COUNTY AND STATE
AFORESAID, BEING DULY SWORN, SAYS THE FOREGOING LEGAL OF WHICH THE ATTACHED IS A TRUE COPY,
WAS PUBLISHED IN SAID NEWSPAPER ONCE A WEEK FOR 1 WEEK, BEGINNING THE16th DAY OF May, 2024.
PUBLICATION FEE: $ 99.55
�I
(SEAL)
8C. LPOLe
ORN TO AND SUBSCRI D B E, THIS I3�hDAY OF l
MY COMMISSION EXPIRES COURTNEY L LOHR
NOTARY PUBLIC
Davidson County, North Carolina
My Commission Expires 08/0312026
Ad Copy:
Public Notice
North Carolina
Environmental Management Commission/NPDES Unit
1617 Mail Service Center
Raleigh, NC 27699-1617
Notice of Intent to Issue NPDES Wastewater Permit NCO070033 Quail Run Mobile Home Park WWTP-North Carolina
Environmental Management Commission proposesto issue a NPDES wastewater discharge permitto the person(s) listed below.
Written comments regarding the proposed permit will be accepted until 30 days after the publish date of this notice. The
Director of the NC Division of Water Resources (DWR) may hold a public hearing should there be a significant degree of public
Interest. Please mail comments and/or Information requests to DWR at the above address. Interested persons may visit the
DWR at 512 N. Salisbury Street, Raleigh, NC 27604 to review the information on file. Additional information on NPDES permits
and this notice may be found on our website: https://deq.nc.gov/public-notices-hearings,or by calling (919) 707-3601. Quail
Run MHP Pads LLC [113 Center St Suite 201, Lexington, NC 27292] has applied for renewal of NPDES permit NCO070033 for
Quail Run Mobile Home Park WWTP in Davidson County. The permitted facility discharges treated domestic wastewater to Miller
Creek in the Yadkin -Pee Dee River Basin. Currently ammonia nitrogen, total residual chlorine, and fecal coliform are water
quality limited. This discharge may affect future allocations in this portion of Miller Creek.
May 16, 2024