HomeMy WebLinkAboutWQ0002128_Compliance Evaluation Inspection_20240813Docusign Envelope ID: C56CBF24-3A93-4AB3-8058-3A276328A94C
ROY COOPER
Governor
ELIZABETH S. BISER
Secretary
RICHARD E. ROGERS, JR.
Director
Johnny Cameron
Pebble Beach Homeowners' Association Inc
PO Box 4455
Emerald Isle, NC 28594-4455
NORTH CAROLINA
Environmental Quality
August 15, 2024
SUBJECT: Compliance Inspection Report
Pebble Beach Condos WWTP
Non -discharge Permit No. WQ0002128
Carteret County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Pebble Beach Condos
WWTP on 8/13/2024. This inspection was conducted to verify that the facility is operating in
compliance with the conditions and limitations specified in Non -discharge Permit No. WQ0002128. The
findings and comments noted during this inspection are provided in the enclosed copy of the inspection
report entitled "Compliance Inspection Report". There were no significant issues or findings noted during the
inspection and therefore, a response to this inspection report is not required.
If you should have any questions, please do not hesitate to contact Helen Perez with the Water
Quality Regional Operations Section in the Wilmington Regional Office at 910-796-7215 or via email at
helen.perez@deq.nc.gov.
Sincerely,
DocuSigned by:
�Oµ �natrl On,
7F141E73B6F3456...
Tom Tharrington, Assistant Regional Supervisor
Water Quality Regional Operations Section
Wilmington Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS
Cc: WQS Wilmington Regional Office — Electronic File
James Bunger — Electronic copy
Don O'Mara — Electronic copy
Upload to Laserfiche
North Carolina Department of Environmental Quality I Division of Water Resources
Wilmington Regional Office 1 127 CardinaI Drive Extension I Wilmington North Carolina 26405
Docusign Envelope ID: C56CBF24-3A93-4AB3-8058-3A276328A94C
Compliance Inspection Report
Permit: WQ0002128 Effective: 01/30/18 Expiration: 12/31/22 Owner : Pebble Beach Homeowners' Association Inc
SOC: Effective: Expiration: Facility: Pebble Beach Condos WWTP
County: Carteret 9201 Coast Guard Rd
Region: Wilmington
Emerald Isle NC 28594
Contact Person: Johnny Cameron Title: Association Manager Phone: 252-354-6333
Directions to Facility:
From the intersection of NC Highway 24E and NC Highway 58S in Cedar Point, follow NC 58 south over the intercoastal waterway
approximately 2 miles to Coast Guard Rd. Turn R on Coast Guard Rd and travel 0.10 mi. Entrance is on the L on Pebble Beach
Rd.
System Classifications: WW3.,
Primary ORC: Donald P Omara
Secondary ORC(s):
On -Site Representative(s):
On -site representative
Related Permits:
Certification: 7904
Donald P Omara
Phone: 252-247-9167
252-247-9167
Inspection Date: 08/13/2024 Entry Time 10:00AM Exit Time: 11:35AM
Primary Inspector: Helen I Perez DocuSignetd�by: Phone: 910-796-7387
Secondary Inspector(s):E r
39694B 6,.
E_06E68CA488AC4H
DocuSigned by:
Ann M Baxter ¢-A.,,, F-I, L, ,� 4,tiReason for Inspection: Routine spection Type: Compliance Evaluation
Permit Inspection Type: High Rate Infiltration
Facility Status: 0 Compliant ❑ Not Compliant
Question Areas:
Treatment Flow Measurement -Effluent
Treatment Flow Measurement -Water
Use Records
Treatment Filters
Treatment Sludge Storage/Treatment
End Use -Infiltration
(See attachment summary)
Treatment Flow Measurement -Influent Miscellaneous Questions
Treatment Treatment Barscreen
Record Keeping Treatment Activated Sludge
Treatment Influent Pump Station Treatment Disinfection
Treatment Flow Measurement Standby Power
Page 1 of 7
Docusign Envelope ID: C56CBF24-3A93-4AB3-8058-3A276328A94C
Permit: WQ0002128 Owner - Facility: Pebble Beach Homeowners' Association Inc
Inspection Date: 08/13/2024 Inspection Type : Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
A routine compliance inspection of the Pebble Beach Condos WWTF was conducted on August 13, 2024. The purpose of
the evaluation was to verify that the facility is operating in compliance with the conditions and limitations specified in Permit
WQ0002128. Don O'Mara was present during the inspection.
This facility is a three -train Sequencing Batch Reactor (SBR) wastewater treatment system. Disposal consists of two
high -rate infiltration fields with rotary distributors. It is permitted for 70,000 GPD but only averages less than half the
permitted flow during the busy summer season. There were no issues during the heavy rains from recent Tropical Storm
Debby. The facility continues to be well maintained and operated.
The current permit expired on December 31, 2022. A renewal application was received on June 24, 2024 and is in the review
process.
The facility is compliant with Non -Discharge Permit WQ0002128. Please review the comment sections of the inspection
report for more details.
Page 2 of 7
Docusign Envelope ID: C56CBF24-3A93-4AB3-8058-3A276328A94C
Permit: WQ0002128
Inspection Date: 08/13/2024
Owner - Facility: Pebble Beach Homeowners' Association Inc
Inspection Type : Compliance Evaluation Reason for Visit: Routine
Type
Yes No NA NE
Activated Sludge Spray, HR
❑
Activated Sludge Drip, LR
❑
Recycle/Reuse
❑
Single Family Drip
❑
Reuse (Quality)
❑
Lagoon Spray, LR
❑
Single Family Spray, LR
❑
Activated Sludge Spray, LR
❑
Infiltration System
Treatment Yes No NA NE
Are Treatment facilities consistent with those outlined in the current permit? 0 ❑ ❑ ❑
Do all treatment units appear to be operational? (if no, note below.) 0 ❑ ❑ ❑
Comment: No comment.
Treatment Influent Pump Station Yes No NA NE
Is the pump station free of bypass lines or structures? 0 ❑ ❑ ❑
Is the general housekeeping acceptable? ❑ ❑ ❑
Are all pumps present? ❑ ❑ ❑
Are all pumps operable? ❑ ❑ ❑
Are floats/controls operable? ❑ ❑ ❑
Are audio and visual alarms available? 0 ❑ ❑ ❑
Are audio and visual alarms operational? ❑ ❑ ❑
# Are SCADA/Telemetry alarms required? ❑ ❑ ❑
Are SCADA/Telemetry available? 0 ❑ ❑ ❑
Are SCADA/Telemetry operational? 0 ❑ ❑ ❑
Comment: High-level alarms were operational when float was pulled and operator received a notification
through his cell phone during the inspection. Sodium Bicarbonate is added at the influent pump
station to ensure an adequate alkalinity level for nitrification.
Treatment Flow Measurement -Influent
Yes No NA NE
Is flowmeter calibrated annually?
❑
❑ ❑
Is flowmeter operating properly?
❑
❑ ❑
Does flowmeter monitor continuously?
❑
❑ ❑
Does flowmeter record flow?
❑
❑ ❑
Does flowmeter appear to monitor accurately?
❑
❑ ❑
Comment:
Page 3 of 7
Docusign Envelope ID: C56CBF24-3A93-4AB3-8058-3A276328A94C
Permit: WQ0002128 Owner - Facility: Pebble Beach Homeowners' Association Inc
Inspection Date: 08/13/2024 Inspection Type : Compliance Evaluation Reason for Visit: Routine
Treatment Flow Measurement -Water Use Records
Is water use metered?
Are the daily average values properly calculated?
Comment:
Treatment Flow Measurement -Effluent
Is flowmeter calibrated annually?
Is flowmeter operating properly?
Does flowmeter monitor continuously?
Does flowmeter record flow?
Does flowmeter appear to monitor accurately?
Comment: The effluent flowmeter was calibrated this
Standby Power
Is automatically activated standby power available?
Is generator tested weekly by interrupting primary power source?
Is generator operable?
Does generator have adequate fuel?
Comment: No comment.
Treatment Barscreen
Is it free of excessive debris?
sarina by Delta
Is disposal of screenings in compliance?
Are the bars spaced properly?
Is the unit in good condition?
Comment: Influent flows through the manual bar screen to the aerated
cleaned as needed and debris disposed of properly.
Yes No NA NE
❑❑■❑
❑❑■❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
■❑❑❑
ms Environmental.
Yes No NA NE
Yes No NA NE
basin. The barscreen is
■❑❑❑
■❑❑❑
❑❑❑■
■❑❑❑
Treatment Activated Sludge Yes No NA NE
Is the aeration mechanism operable? ❑ ❑ ❑
Is the aeration basin thoroughly mixed? ❑ ❑ ❑
Is the aeration equipment easily accessed? ❑ ❑ ❑
Is Dissolved Oxygen adequate? ❑ ❑ ❑
Are Settleometer results acceptable? ❑ ❑ ❑
Is activated sludge an acceptable color? 0 ❑ ❑ ❑
Comment: Facility treatement consists of a three -train SBR system with anaerobic sedimentation tank and
SAM (surge, anoxic, mix) tanks prior to the SBR tanks. Settleometer (jar) tests, alkalinity strips
and DO monitoring are used for process control.
Treatment Filters
Is the filter media present?
Yes No NA NE
■❑❑❑
Page 4 of 7
Docusign Envelope ID: C56CBF24-3A93-4AB3-8058-3A276328A94C
Permit: WQ0002128 Owner - Facility: Pebble Beach Homeowners' Association Inc
Inspection Date: 08/13/2024 Inspection Type : Compliance Evaluation Reason for Visit: Routine
Is the filter media the correct size and type? ❑ ❑ ❑
Is the air scour operational? ❑ ❑ 0 ❑
Is the scouring acceptable? ❑ ❑ 0 ❑
Is the clear well free of excessive solids? ❑ ❑ ❑
Is the mud well free of excessive solids and filter media? ❑ ❑ ❑
Does backwashing frequency appear adequate? 0 ❑ ❑ ❑
Comment: From the post EQ tank, wastewater flows through dual 72,000 GPD rated cloth, tertiary filters
that automatically backwash when set level is reached.
Treatment Sludge Storage/Treatment Yes No NA NE
Is the aeration operational? ❑ ❑ ❑
Is the aeration pattern even? ❑ ❑ ❑
If required, are Sanitary "Ts" present in tankage? ❑ ❑ 0 ❑
Comment: Waste sludge is transferred form the anaerobic/sedimentation tanks to the digester as needed
and hauled off site by Barnes Environmental approximately twice/month in the summer season
and approximately twice/winter season.
Treatment Disinfection
Is the system working?
Do the fecal coliform results indicate proper disinfection?
Is there adequate detention time (-30 minutes)?
Is the system properly maintained?
If gas, does the cylinder storage appear safe?
Is the fan in the chlorine feed room and storage area operable?
Is the chlorinator accessible?
If tablets, are tablets present?
Are the tablets the proper size and type?
Is contact chamber free of sludge, solids, and growth?
If UV, are extra UV bulbs available?
If UV, is the UV intensity adequate?
# Is it a dual feed system?
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)?
If yes, then is there a Risk Management Plan on site?
If yes, then what is the EPA twelve digit ID Number? (1000- - )
If yes, then when was the RMP last updated?
Comment: The facility has two gravity flow, in -series UV systems, each with six lamps.
Record Keeping
Is a copy of current permit available?
Are monitoring reports present: NDMR?
Yes No NA NE
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
■❑❑❑
❑❑■❑
❑❑■❑
❑❑■❑
❑❑■❑
❑❑■❑
❑❑■❑
■❑❑❑
❑❑❑■
❑❑■❑
❑ ❑ ❑
❑ ❑ ❑
Yes No NA NE
■❑❑❑
❑ ❑ ❑
Page 5 of 7
Docusign Envelope ID: C56CBF24-3A93-4AB3-8058-3A276328A94C
Permit: WQ0002128 Owner - Facility: Pebble Beach Homeowners' Association Inc
Inspection Date: 08/13/2024 Inspection Type : Compliance Evaluation Reason for Visit: Routine
NDAR?
❑
❑ ❑
Are flow rates less than of permitted flow?
0
❑ ❑ ❑
Are flow rates less than of permitted flow?
0
❑ ❑ ❑
Are application rates adhered to?
0
❑ ❑ ❑
Is GW monitoring being conducted, if required (GW-59s submitted)?
0
❑ ❑ ❑
Are all samples analyzed for all required parameters?
0
❑ ❑ ❑
Are there any 2L GW quality violations?
❑
❑ 0 ❑
Is GW-59A certification form completed for facility?
❑
❑ ❑
Is effluent sampled for same parameters as GW?
0
❑ ❑ ❑
Do effluent concentrations exceed GW standards?
❑
❑ 0 ❑
Are annual soil reports available?
❑
❑ 0 ❑
# Are PAN records required?
❑
❑ 0 ❑
# Did last soil report indicate a need for lime?
❑
❑ 0 ❑
If so, has it been applied?
❑
❑ 0 ❑
Are operational logs present?
0
❑ ❑ ❑
Are lab sheets available for review?
0
❑ ❑ ❑
Do lab sheets support data reported on NDMR?
❑
❑ ❑
Do lab sheets support data reported on GW-59s?
❑
❑ ❑
Are Operational and Maintenance records present?
0
❑ ❑ ❑
Were Operational and Maintenance records complete?
0
❑ ❑ ❑
Has permittee been free of public complaints in last 12 months?
0
❑ ❑ ❑
Is a copy of the SOC readily available?
❑
❑ 0 ❑
No treatment units bypassed since last inspection?
0
❑ ❑ ❑
Comment: Operation/maintenance log, daily check sheets, pH bench sheets and calibration records were
available for review and found complete. A review of NDMR/NDAR reports for the permit cycle
show one effluent Total Nitrogen exceedance in 3/23. For GW-59 reports, two Nitrate
exceedances in MW-4 for 3/21 and 11/22: one Nitrate exceedance in MW-2 for 3/23.
End Use -Infiltration
Yes No NA NE
# Is the application High Rate or Low Rate?
High
Rate
Are buffers maintained?
0
❑ ❑ ❑
Are any supply wells within the CB?
❑
❑ ❑
Are any supply wells within 250' of the CB?
❑
❑ ❑
Is municipal water available in the area?
0
❑ ❑ ❑
Are GW monitoring wells required?
0
❑ ❑ ❑
Are GW monitoring wells located properly w/ respect to RB and CB?
0
❑ ❑ ❑
Are GW monitoring wells properly constructed, including screened interval?
❑
❑ ❑
Is a usable green area maintained?
❑
❑ ❑
Page 6 of 7
Docusign Envelope ID: C56CBF24-3A93-4AB3-8058-3A276328A94C
Permit: WQ0002128 Owner - Facility: Pebble Beach Homeowners' Association Inc
Inspection Date: 08/13/2024 Inspection Type : Compliance Evaluation Reason for Visit: Routine
Is the disposal site acceptable?
0
❑ ❑ ❑
Is the distribution equipment acceptable?
0
❑ ❑ ❑
Is the disposal site free of ponding?
0
❑ ❑ ❑
Is the disposal site free of breakout?
0
❑ ❑ ❑
Are the disposal sites free of solids, algae, etc.?
0
❑ ❑ ❑
Do the records show that the fields are properly maintained?
❑
❑ ❑
Are the disposal sites free of vegetation?
0
❑ ❑ ❑
Do any surface water features appear to be adversely impacted by GW discharge?
❑
❑ 0 ❑
No chemicals or rototiller used to eliminate vegetation, solids, algae, etc.?
0
❑ ❑ ❑
Comment: The infiltration fields were in good condition. The Pebble Beach maintenance crew continues to
maintain the fields.