HomeMy WebLinkAboutWQ0010615_CEIARR_20240702
SENT VIA ELECTRONIC MAIL ONLY: NO HARD COPY WILL BE MAILED
July 02, 2024
Michael Lee Mehaffey
Town of Maggie Valley
Email: mmehaffey@maggievalleync.gov
SUBJECT: Compliance Inspection Report
Annual Report Review 2023
Town of Maggie Valley DCAR
Non-discharge Permit No. WQ0010615
Haywood County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Town of Maggie Valley
DCAR on 7/2/2024. This inspection was conducted to verify that the facility is operating in compliance
with the conditions and limitations specified in Non-discharge Permit No. WQ0010615. The findings and
comments noted during this inspection are provided in the enclosed copy of the inspection report
entitled "Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a response to this
inspection report is not required.
If you should have any questions, please do not hesitate to contact Melanie Kemp with the Water
Quality Regional Operations Section in the Asheville Regional Office at 828-296-4500 or via email at
melanie.kemp@deq.nc.gov.
Sincerely,
Melanie Kemp, Environmental Specialist
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS: Compliance Evaluation Inspection Report
Ec: LF
Compliance Inspection Report
Permit:WQ0010615 Effective:08/01/19 Expiration:12/31/24 Owner :Town of Maggie Valley
SOC:
Contact Person:
Region:
County:
Directions to Facility:
Haywood
Asheville
Michael Lee Mehaffey
Effective:Expiration:Facility:Town of Maggie Valley DCAR
5320 Jonathan Creek Rd
Waynesville NC 28785
Title:Phone:828-400-9494
From Asheville: I-40 west to Exit 20 to Hwy 276. Drive south on Hwy 276 for approximately 0.2 miles and take a left on Johnathan's
Creek Rd. The WWTP is at the end of the drive.
Secondary ORC(s):
828-400-9494Phone:27664Certification:Michael Lee MehaffeyPrimary ORC:
System Classifications:
On-Site Representative(s):
Related Permits:
NC0056561 Town of Maggie Valley - Maggie Valley WWTP
Secondary Inspector(s):
Primary Inspector:
Inspection Date:Exit Time:Entry Time:
Phone:
07/02/2024 10:00AM 01:00PM
Melanie Kemp
Facility Status:
Permit Inspection Type:
Reason for Inspection:Inspection Type:
Not CompliantCompliant
Routine
Distribution of Residual Solids (503)
Annual Report Review
Question Areas:
Miscellaneous Questions Record Keeping Treatment
Pathogen and Vector Attraction
(See attachment summary)
Page 1 of 4
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0010615
07/02/2024 Annual Report Review
Town of Maggie Valley
Routine
Inspection Summary:
Melanie Kemp, with the Asheville Regional Office, conducted a review of the Town of Maggie Valley’s 2023 DCAR Annual
Report to determine whether the facility processed and monitored all residuals in compliance with Permit No. WQ0010615.
The Town distributed approximately 160 dry tons of Class A Compost to customers in 2023 for use as an amendment to
pasture/hay fields.
Pathogen Reduction (PR): PR is met via fecal coliform density reduction below 1,000 MPN/g and through Alkaline Treatment
(Alternative 2). The pH remained above 12 SU for a minimum of 72 consecutive hours and remained above 52°C during that
time. Percent total solids is analyzed quarterly and indicates the residuals are air dried to greater 50% before distribution.
Fecal samples are collected quarterly - all results were less than 1,000 MPN/g. It is recommended multiple fecal samples
are collected over a two-week period.
Vector Attraction Reduction (VAR): VAR is met via Alkaline Stabilization (Option 6). Staff record the initial pH after the
addition of lime and then approximately every 22 to 24 hours. Submitted data indicates the pH remains above 12 for over 24
hours. Staff noted no additional lime was added to the piles.
Metals, Nutrients & Pollutants of Concern: Values were below the monthly and ceiling concentration limits for Class A
products. All metals and nutrient parameters were analyzed per section IV.3 of the permit. It should be noted that SAR was
not calculated and reported. The SAR value was 0.64 based on sampling results.
Non-Hazardous Waste Characterization: The non-hazardous waste characterization is required annually. TCLP, corrosivity,
reactivity and ignitibility appear to be complaint with regulatory requirements.
Please note the following issues and correct them in next year’s report:
•The SAR calculation needs to be provided and reported on form RSSF.
•All forms provided were outdated. Please be sure to use the correct, up-to-date reporting forms:
https://edocs.deq.nc.gov/WaterResources/DocView.aspx?dbid=0&id=2089054
Page 2 of 4
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0010615
07/02/2024 Annual Report Review
Town of Maggie Valley
Routine
Type Yes No NA NE
Land Application
Distribution and Marketing
Record Keeping Yes No NA NE
Is GW monitoring being conducted, if required?
Are GW samples from all MWs sampled for all required parameters?
Are there any GW quality violations?
Is GW-59A certification form completed for facility?
Is a copy of current permit on-site?
Are current metals and nutrient analysis available?
Are nutrient and metal loading calculating most limiting parameters?
a. TCLP analysis?
b. SSFA (Standard Soil Fertility Analysis)?
Are PAN balances being maintained?
Are PAN balances within permit limits?
Has land application equipment been calibrated?
Are there pH records for alkaline stabilization?
Are there pH records for the land application site?
Are nutrient/crop removal practices in place?
Do lab sheets support data reported on Residual Analysis Summary?
Are hauling records available?
Are hauling records maintained and up-to-date?
# Has permittee been free of public complaints in last 12 months?
Has application occurred during Seasonal Restriction window?
Note that the SAR value was not calculated and reported. Outdated forms were used for report
submittal. See summary for more details.
Comment:
Pathogen and Vector Attraction Yes No NA NE
a. Fecal coliform SM 9221 E (Class A or B)
Class A, all test must be <1000 MPN/dry gram
Geometric mean of 7 samples per monitoring period for class B<2.0*10E6 CFU/dry gram
Fecal coliform SM 9222 D (Class B only)
Geometric mean of 7 samples per monitoring period for class B<2.0*10E6 CFU/dry gram
b. pH records for alkaline stabilization (Class A)
c. pH records for alkaline stabilization (Class B)
Temperature corrected
Page 3 of 4
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0010615
07/02/2024 Annual Report Review
Town of Maggie Valley
Routine
d. Salmonella (Class A, all test must be < 3MPN/4 gram day)
e. Time/Temp on:
Digester (MCRT)
Compost
Class A lime stabilization
f. Volatile Solids Calculations
g. Bench-top Aerobic/Anaerobic digestion results
PR Alternative 2 is utilized.Comment:
Treatment Yes No NA NE
Check all that apply
Aerobic Digestion
Anaerobic Digestion
Alkaline Pasteurization (Class A)
Alkaline Stabilization (Class B)
Compost
Drying Beds
Other
VAR Option 6 is utilized.Comment:
Page 4 of 4
Annual Report Review Class A Distribution Permit No. WQ00_________
Reporting Period: ___________
Permit Details:
• Is 503 OR 257
• Maximum Dry Tons Per Year: ________
• Monitoring Frequency for TCLP: ________
• Monitoring Frequency for Residuals Analysis: ________
• Monitoring Frequency for Pathogen & Vector Attraction Reduction: ________
1. Class A Annual Distribution and Marketing/Surface Disposal Certification Form
• Was a certification form submitted? Yes No
• Was distribution conducted during the reported period? Yes No
• How many dry tons were produced and distributed? ________
• Were the distributions with the permitted amount? ________
• Were recipient’s information listed? ________
• Did it indicate compliance? Yes No
• Was form complete? Yes No
• Was it signed by the appropriate people? Yes No
2. Monitoring
• Were the analyses conducted at the required frequency? Yes No
• Was an analyses taken for each source that was distributed? Yes No
• Were the metals analyses reported on the Residual Sampling Summary Form? Yes No
• Were the results reported in mg/kg? Yes No
• Were the pH’s 6.0 or greater for each residual sample? Yes No
• Were the heavy metals within ceiling concentration permit limits? Yes No
o Were the lab analyses attached? Yes No
• Were all the required parameters tested? Yes No
• Was TCLP analysis conducted? Yes No
• Were the TLCP contaminants within regulatory limits? Yes No
• Was a corrosivity, ignitability, and reactivity analysis conducted? Yes No
10615
2023
300
annually
annually
annually
160
yes
yes
Comments: Missing SAR value and calculations (0.64)
3. Pathogen and Vector Attraction Reduction
• Was a signed copy of the Pathogen and Vector Attraction Reduction Form submitted? Yes No
• Did the form indicate the period of coverage, the residual class, and the pathogen reduction alternative
and the vector attraction reduction option used? Yes No
• Was the appropriate documentation to show pathogen and vector attraction reduction included in the
report? Yes No
• Was pathogen and vector attraction reduction demonstrated according to 40 CFR Part 503?Yes No
Class A Pathogen Review
To be Class A, residuals shall meet either fecal Coliform density or salmonella density.
Fecal Coliform density
· Was the sampling conducted at the required frequency? Yes No
· Were multiple samples taken? Yes No
· Was each sample less than 1000 MPN/gram of total solids? Yes No
OR
Salmonella density
· Was the sampling conducted at the required frequency? Yes No
· Were multiple samples taken? Yes No
· Was each sample less than 3 MPN/4 grams of total solids? Yes No
To be Class A, residuals shall meet one of the following alternatives:
Alternative 1 – Time/Temperature
· Were the residuals maintained for correct time and temperature? Yes No
· Were logs submitted showing time and temperature? Yes No
· Were temperatures within range for complete time period? Yes No
Alternative 2 – Alkaline Treatment
· Were logs submitted showing time and temperature? Yes No
· Was the pH raised to 12 or greater and maintained for 72 hours or longer? Yes No
· Was the temperature 52°C (126°F) for 12 hours or longer while the pH was 12 or greater?
Yes No
· Were logs submitted showing time and pH? Yes No
· Was the temperature corrected to 25°C (77°F)? Yes No
Alternative 5 – Process To Further Reduce Pathogens
PFRP Composting
· Were the within-vessel method or static aerated pile methods used? Yes No
· Was the residuals temperature maintained at 55°C (131°F) or higher for three consecutive days or
longer in the within-vessel method or static aerated pile method? Yes No
OR
· Was the windrow composting method used? Yes No
· Was the residuals temperature maintained at 55°C or higher for 15 consecutive days or longer in the
windrow method, and the windrow turned a minimum of five times during this time? Yes No
PFRP Heat Drying
· Was the residuals dried by direct or indirect contact with hot gases and the moisture content of
residuals reduced to 10% or lower? Yes No
· Did the temperature of the residuals or the of the wet bulb temperature of the gas in contact with the
residuals as the residuals leave the dryer exceed 80°C (176°F)? Yes No
Comment: Old Pathogen and Vector Attraction Reduction Form was used. Need to use form PVRF 503 (12/2006).
Vector Attraction Reduction Review
• Was the sampling conducted at the required frequency? Yes No
Option 1 – 38% Volatile Solids Reduction
· Was there 38% reduction? Yes No
· Were lab sheets/calculations in report? Yes No
· Was the reduction on volatile solids (not total solids)? Yes No
· Were the samples taken at beginning of digestion process and before application (Inspection)?
Yes No
· Were calculations correct? Yes No
Option 2 – 40-Day Bench Scale Test
· Were residuals from anaerobically digested treatment (Inspection)? Yes No
· Were residuals anaerobically digested in lab? Yes No
· Was the test run for 40 days? Yes No
· Was the test done between 30°C (86°F) and 37°C (99°F)? Yes No
· Was the reduction of on volatile solids (not total solids)? Yes No
· Was the reduction less than 17%? Yes No
· Were lab sheets/calculations in report? Yes No
· Were calculations correct? Yes No
Option 3 – 30-Day Bench Scale Test
· Were residuals from aerobically digested treatment (Inspection)? Yes No
· Were residuals aerobically digested in lab? Yes No
· Were residuals 2% or less total solids? Yes No
· If not 2% total solids, was the test ran on a sample diluted to 2% with unchlorinated effluent?
Yes No
· Was the test run for 30 days? Yes No
· Was the test done at 20°C (68°F)? Yes No
· Was the reduction of on volatile solids (not total solids)? Yes No
· Was the reduction less than 15%? Yes No
· Were lab sheets/calculations in report? Yes No
· Were calculations correct? Yes No
Option 4 – Specific Oxygen Uptake Rate (SOUR)
· Were residuals form aerobically digested treatment (Inspection)? Yes No
· Were residuals 2% or less total solids (dry weight basis) (not diluted)? Yes No
· Was the test done between 10°C (50°F) and 30°C (86°F)? Yes No
· Was the temperature corrected to 20°C (68°F)? Yes No
· Was the SOUR equal to or less than 1.5 mg of oxygen per hour per gram of total residual solids (dry
weight basis)? Yes No
· Was the sampling holding time two hours? Yes No
· Was the test started within 15 minutes of sampling or aeration maintained? Yes No
Option 5 – 14-Day Aerobic Process
· Were the residuals from aerobically digested treatment (Inspection)? Yes No
· Were the residuals treated for 14 days? Yes No
· Was the residuals temperature higher than 40°C (104°F) for a 14-day period? Yes No
· Was the average residuals temperature higher than 45°C (113°F)? Yes No
Option 6 – Alkaline Stabilization
· Was the pH of the residuals raised to 12 or higher by the addition of alkali? Yes No
· Did the pH of residuals remain at 12 or higher for two hours without the addition of more alkali?
Yes No
· Did the pH of residuals remain at 11.5 or higher for an additional twenty-two hours without the
addition of more alkali? Yes No
· Was the pH corrected to 25°C (77°F)? Yes No
Option 7 – Drying of Stabilized Residuals
· Does the residuals contain any unstabilized residuals? Yes No
· Were the residuals mixed with any other materials? Yes No
· Were the residuals dried up to 75% total solids? Yes No
Option 8 – Drying of Unstabilized Residuals
· Were the residuals mixed with any other materials? Yes No
· Were the residuals dried to 90% total solids? Yes No
Option 9/10 – Injection/Incorporation
· Was there any significant amount of residuals on land surface one hour after injection (Inspection)?
Yes No
· Was injection done on pasture or hay field? Yes No
· Was injection done at time that crop was growing? Yes No
· If Class A with respect to pathogen, were residuals injected with eight hours after discharge from
pathogen treatment? Yes No
· Was incorporation done six hours after application (Inspection)? Yes No
4. General
• Was the report in the proper format? Yes No
• Was the annual report complete? Yes No
• Was the report submitted on time? Yes No
Pollutant Limits
Pollutant Ceiling
Concentration
Below
Limit
Cumulative
Pollutant
Loading Rate
Below
Limit
Arsenic 75 41
Cadmium 85 39
Copper 4300 1500
Lead 840 300
Mercury 57 17
Molybdenum 75 N/A
Nickel 420 420
Selenium 100 100
Zinc 7500 2800
TCLP
Parameter Below
Limit
Parameter Below
Limit
Parameter Below
Limit
Arsenic (5.0) 1,4-Dichlorobenzene (7.5) Nitrobenzene (2.0)
Barium (100.0) 1,2-Dichloroethane (0.5) Pentachlorophenol (100.0)
Benzene (0.5) 1,1-Dichloroethylene (0.7) Pyridine (5.0)
Cadmium (1.0) 2,4-Dinitrotoluene (0.13) Selenium (5.0)
Carbon tetrachloride (0.5) Endrin (0.02) Silver (5.0)
Chlorodane (0.03) Hepatachlor (and its
epoxide) (0.008)
Tetrachloroethylene (0.7)
Chlorobenzene (100.0) Hexachlorobenzene (0.13) Toxaphene (0.5)
Chloroform (6.0) Hexachlorobutadiene (0.5) Trichloroethylene (0.5)
Chromium (5.0) Hexachloroethane (3.0) 2,4,5-Trichlorophenol
(400.0)
m-Cresol (200.0) Lead (5.0) 2,4,6-Trichlorophenol (2.0)
o-Cresol (200.0) Lindane (0.4) 2,4,5-TP (Silvex) (1.0)
p-Cresol (200.0) Mercury (0.2) Vinyl Chloride (0.2)
Cresol (200.0) Methoxychlor (10.0)
2,4-D (10.0) Methyl ethyl Ketone (200.0)
Residuals Analysis
Parameter Analyzed For Parameter Analyzed For Parameter Analyzed For
Aluminum Mercury Potassium
Ammonia-
Nitrogen
Molybdenum Selenium
Arsenic Nickel Sodium
Cadmium Nitrate-
Nitrite
Nitrogen
SAR
Calcium % TS TKN
Copper pH Zinc
Lead Phosphorus
Magnesium PAN
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
n
y
y