Loading...
HomeMy WebLinkAboutNC0006220_Compliance Evaluation Inspection_20240813ROY COOPER Governor ELIZABETH S. BISER Secretary RICHARD E. ROGERS, JR. Director Alex Anderson, Director of Water Resources City of Kannapolis 401 Laureate Way Kannapolis, NC 28081 SUBJECT: Compliance Evaluation Inspection City of Kannapolis WTP NPDES Permit No. NC00)6220 Rowan County Dear Mr. Anderson: NORTH CAROLINA Environmental Quality August 13, 2024 Enclosed is a copy of the Compliance Evaluation Inspection (CEI) Report for the inspection conducted at the subject facility on July 31, 2024, by Mr. Wes Bell of this Office. This Office would like to thank all water plant staff for their assistance and cooperation that was provided throughout this inspection. Should you have any questions concerning this report, please do not hesitate to contact Mr. Bell at (704) 235-2192 or at wes.bell(a,deq.nc. gov. Sincerely, DocuSigned by: A�•�Guw N N l-ft F161 FB69A2D84A3... Andrew H. Pitner, P.G. Regional Supervisor Water Quality Regional Operations Section Mooresville Regional Office Division of Water Resources, NCDEQ Enclosure: Inspection Report Cc: Alex Anderson, City of Kannapolis (via eCopy) Gerald Faulkner, City of Kannapolis (via eCopy) Natalie Curry, City of Kannapolis (via eCopy) NPDES Program Files - Laserfiche el- DEQ�� North Carolina Department of Environmental quality I Divisionof Water Resources Mooresville Regional Office 1 610 East Center Avenue, Suite 301 1 Mooresville, North Carolina 28115 704.6631699 United States Environmental Protection Agency Form Approved. EPA Washington, D.C. 20460 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN 1 2 u 3 I NC0006220 111 121 24/07/31 I17 18 LC] I 19 I s I 20L] 21111I I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I r6 Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved ------------------- 67 2.0 701d I 71 I„ I 72 I r., I 71 I 74 79 I I I I I I I80 L—I ty L-1 I I Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) 12:43PM 24/07/31 19/06/01 Kannapolis WTP 1353 Pump Sta Rd Exit Time/Date Permit Expiration Date Kannapolis NC 28081 02:30PM 24/07/31 23/10/31 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Natalie Curry/ORC// Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Mike Legg,PO Box 1199 Kannapolis NC 280811199//704-980-4200/ No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit 0 Flow Measurement Operations & Maintenar Records/Reports Self -Monitoring Progran 0 Sludge Handling Dispo: Facility Site Review Effluent/Receiving Wate Laboratory Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date Wes Bell signed by: DWR/MRO WQ/704-235-2192/ 8/13/2024 Be& E�Docu`,','�96D90=437 ... MnlAyReviewer Agency/Office/Phone and Fax Numbers Date Signature of MPr�F16,FBHAMUAI. Andrew Pi"�� H P WR/MRO WQ/704-663-1699 Ext.2180/ 8/13/2024 . EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page# NPDES yr/mo/day Inspection Type NC0006220 I11 12I 24/07/31 117 18 i c i Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) Page# Permit: NC0006220 Owner -Facility: Kannapolis WTP Inspection Date: 07/31/2024 Inspection Type: Compliance Evaluation Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new ■ ❑ ❑ ❑ application? Is the facility as described in the permit? ■ ❑ ❑ ❑ # Are there any special conditions for the permit? ■ ❑ ❑ ❑ Is access to the plant site restricted to the general public? ■ ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? ■ ❑ ❑ ❑ Comment: The Division received facility's permit renewal documentation on 7/5/2023. The last compliance evaluation inspection at this facility was performed by DWR staff on 10/8/2020. Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? ■ ❑ ❑ ❑ Is all required information readily available, complete and current? ■ ❑ ❑ ❑ Are all records maintained for 3 years (lab. reg. required 5 years)? ■ ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? ■ ❑ ❑ ❑ Is the chain -of -custody complete? ■ ❑ ❑ ❑ Dates, times and location of sampling ■ Name of individual performing the sampling ■ Results of analysis and calibration ■ Dates of analysis ■ Name of person performing analyses ■ Transported COCs ■ Are DMRs complete: do they include all permit parameters? ■ ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ ■ ❑ (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified ❑ ❑ ■ ❑ operator on each shift? Is the ORC visitation log available and current? ■ ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? ■ ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility ■ ❑ ❑ ❑ classification? Is a copy of the current NPDES permit available on site? ■ ❑ ❑ ❑ Facility has copy of previous year's Annual Report on file for review? ❑ ❑ ■ ❑ Page# 3 Permit: NC0006220 Inspection Date: 07/31/2024 Owner -Facility: Kannapolis WTP Inspection Type: Compliance Evaluation Record Keeping Yes No NA NE Comment: The records reviewed durinq the inspection were organized and well maintained. Discharge monitoring reports (eDMRs) were reviewed for the period July 2023 through June 2024. Effluent chronic toxicity failures were reported in July 2023 and April 2024. Note: Effluent chronic toxicity tests are monitor only. The ORC must ensure to maintain a copy of all operation and maintenance records including flow meter calibrations, chemical receipt/usage (dechlorination), sludge removal, etc. that pertain to the NPDES treatment system. The ORC and staff must ensure that a 10-day minimum is between all twice per month effluent sampling parameters (PH, total residual chlorine and TSS). Laboratory Yes No NA NE Are field parameters performed by certified personnel or laboratory? 0 ❑ ❑ ❑ Are all other parameters(excluding field parameters) performed by a certified lab? 0 ❑ ❑ ❑ # Is the facility using a contract lab? 0 ❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 ❑ ❑ 0 ❑ degrees Celsius)? Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ ❑ ■ ❑ Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑ ❑ 0 ❑ Comment: Effluent field analyses (pH and total residual chlorine) are performed under the City's field laboratory certification #5387. Pace Analytical Services and ETT (toxicity) have also been contracted to provide analytical support. Facility staff must ensure to report all future effluent total residual chlorine (TRC) values down to the lowest standard verified on the TRC meter (20 ug/L). Any effluent TRC results below 20 ug/L must be reported as <20 ug/L. Effluent Sampling Is composite sampling flow proportional? Is sample collected below all treatment units? Is proper volume collected? Is the tubing clean? # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)? Is the facility sampling performed as required by the permit (frequency, sampling type representative)? Comment: The subject permit requires effluent grab samples. Yes No NA NE ❑ ❑ ■ ❑ ■ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ■ ❑ ■ ❑ ❑ ❑ Upstream / Downstream Sampling Yes No NA NE Is the facility sampling performed as required by the permit (frequency, sampling type, 0 ❑ ❑ ❑ and sampling location)? Comment: Page# 4 Permit: NC0006220 Inspection Date: 07/31/2024 Upstream / Downstream Sampling Owner -Facility: Kannapolis WTP Inspection Type: Compliance Evaluation Yes No NA NE Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: The wastewater treatment facility appeared to be properly operated and well maintained. Equalization Basins Is the basin aerated? Is the basin free of bypass lines or structures to the natural environment? Is the basin free of excessive grease? Are all pumps present? Are all pumps operable? Are float controls operable? Are audible and visual alarms operable? # Is basin size/volume adequate? Yes No NA NE ❑ ❑ ■ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Comment: The equalization basin is equipped with an overflow outlet into the receiving stream. The facility staff would dechlorinate the waste stream and perform sampling in accordance with the subject permit if this emergency condition occurs. Secondary Clarifier Yes No NA NE Is the clarifier free of black and odorous wastewater? 0 ❑ ❑ ❑ Is the site free of excessive buildup of solids in center well of circular clarifier? 0 ❑ ❑ ❑ Are weirs level? 0 ❑ ❑ ❑ Is the site free of weir blockage? ■ ❑ ❑ ❑ Is the site free of evidence of short-circuiting? 0 ❑ ❑ ❑ Is scum removal adequate? 0 ❑ ❑ ❑ Is the site free of excessive floating sludge? 0 ❑ ❑ ❑ Is the drive unit operational? ■ ❑ ❑ ❑ Is the return rate acceptable (low turbulence)? ❑ ❑ 0 ❑ Is the overflow clear of excessive solids/pin floc? 0 ❑ ❑ ❑ Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth) 0 ❑ ❑ ❑ Comment: Page# 5 Permit: NC0006220 Inspection Date: 07/31/2024 Pumps-RAS-WAS Are pumps in place? Are pumps operational? Are there adequate spare parts and supplies on site? Owner -Facility: Kannapolis WTP Inspection Type: Compliance Evaluation Comment: The clarifier pumps convey the settled sludge to the storage lagoon. Flow Measurement - Effluent # Is flow meter used for reporting? Is flow meter calibrated annually? Is the flow meter operational? (If units are separated) Does the chart recorder match the flow meter? Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ ❑ ❑ ❑ ■ Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ ❑ ❑ ■ ❑ Comment: The flow meter is calibrated annually and was last calibrated on3/6/20/24 by Expert Services International, LLC. De -chlorination Type of system ? Is the feed ratio proportional to chlorine amount (1 to 1)? Is storage appropriate for cylinders? # Is de -chlorination substance stored away from chlorine containers? Are the tablets the proper size and type? Comment: Aqueous sodium thiosulfate is added for dechlorination. Are tablet de -chlorinators operational? Number of tubes in use? Comment: Yes No NA NE Liquid ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? 0 ❑ ❑ ❑ Are the receiving water free of foam other than trace amounts and other debris? ■ ❑ ❑ ❑ If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ ❑ Comment: The facility was not discharging at the time of the inspection: however, the treated wastewater in the clarifier appeared clear with no floatable solids or foam. Fish were also observed in the clarifier trouah. Lagoons Type of lagoons? Yes No NA NE Facultative Page# 6 Permit: NC0006220 Owner - Facility: Kannapolis WTP Inspection Date: 07/31/2024 Inspection Type: Compliance Evaluation Lagoons Yes No NA NE # Number of lagoons in operation at time of visit? 1 Are lagoons operated in? # Is a re -circulation line present? ❑ ❑ 0 ❑ Is lagoon free of excessive floating materials? 0 ❑ ❑ ❑ # Are baffles between ponds or effluent baffles adjustable? ❑ ❑ 0 ❑ Are dike slopes clear of woody vegetation? ❑ ❑ 0 ❑ Are weeds controlled around the edge of the lagoon? 0 ❑ ❑ ❑ Are dikes free of seepage? ❑ ❑ 0 ❑ Are dikes free of erosion? ❑ ❑ 0 ❑ Are dikes free of burrowing animals? ❑ ❑ 0 ❑ # Has the sludge blanket in the lagoon (s) been measured periodically in multiple ❑ ❑ ■ ❑ locations? # If excessive algae is present, has barley straw been used to help control the growth? ❑ ❑ 0 ❑ Is the lagoon surface free of weeds? 0 ❑ ❑ ❑ Is the lagoon free of short circuiting? 0 ❑ ❑ ❑ Comment: The sludge lagoon effluent decants into the sanitary sewer system to the WSACC/Rocky River WWTP for final treatment/disposal. The City is a permitted facility under WSACC's Industrial Pretreatment Program. Sludge was last removed from the lagoon approximately three years ago. Page# 7