SENT VIA ELECTRONIC MAIL ONLY: NO HARD COPY WILL BE MAILED
August 07, 2024
Stacy Adcock
Carolina Water Service Inc of North Carolina
Email: james.adcock@nexuswg.com
SUBJECT: Compliance Inspection Report
Fairfield Sapphire Valley WWTP
NPDES WW Permit No. NC0022985
Jackson County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Fairfield Sapphire Valley
WWTP on 7/23/2024. This inspection was conducted to verify that the facility is operating in
compliance with the conditions and limitations specified in NPDES WW Permit No. NC0022985. The
findings and comments noted during this inspection are provided in the enclosed copy of the inspection
report entitled "Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a response to this
inspection report is not required.
If you should have any questions, please do not hesitate to contact Mikal Willmer with the Water
Quality Regional Operations Section in the Asheville Regional Office at 828-296-4500 or via email at
mikal.willmer@deq.nc.gov.
Sincerely,
Daniel Boss, Assistant Regional Supervisor
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS: Inspection Report
Docusign Envelope ID: 41432680-6A73-42A7-B04D-981EC0C1388E
EPA
United States Environmental Protection Agency
Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 N 52 NC0022985 24/07/23 C S31112171819 20
21 66
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
N67707172 73 74 75 80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Fairfield Sapphire Valley WWTP
3500 US Hwy 64 W
Sapphire NC 28774
Entry Time/Date Permit Effective Date
Exit Time/Date Permit Expiration Date
09:00AM 24/07/23 23/04/01
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
James Stacy Adcock/ORC/828-230-4809/
Other Facility Data
12:30PM 24/07/23 27/08/31
Name, Address of Responsible Official/Title/Phone and Fax Number
Drake Robert, /Regulatory Compliance Manager//Contacted
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self-Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date
Richard Eguino DWR/ARO WQ/828-296-4500/
Mikal Willmer DWR/ARO WQ/828-296-4686/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
Daniel J Boss DWR/ARO WQ/828-296-4658/
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#1
Docusign Envelope ID: 41432680-6A73-42A7-B04D-981EC0C1388E
8/8/2024
8/9/2024
8/9/2024
NPDES yr/mo/day
24/07/23
Inspection Type
C3111218
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Mikal Willmer and Richard Eguino, with the Asheville Regional Office, conducted a Compliance
Evaluation Inspection of the Fairfield Sapphire Valley WWTP on July 23, 2024. This inspection was
conducted to determine whether the facility is being operated and maintained in compliance with
NPDES Permit # NC0022985. Stacy Adcock and Alex Hutchins, with Carolina Water Service (CWS),
were present and assisted in the inspection.
Overall, the facility appeared to be operated and maintained in compliance with NPDES Permit
#NC0022985, but the treatment plants continue to show signs of age-related wear. At the time of the
inspection, the two 0.075 MGD plants (#1 & #2) were temporarily offline for repairs. Plant #3, rated at
0.125 MGD, was online. Because of the age of the treatment plants, CWS is in the process of
assessing costs for a new facility and the best option for maintaining treatment during construction
due to the limited footprint.
Bar Screen: the screen is cleaned daily.
Aeration basin: staff attempt to keep the DO around 2.5 mg/L and pH around 6. Airlines run through
the catwalk and cannot be easily repaired when there are leaks. The scum suction is manually
turned on as needed. Some dense foam remaining from filamentous bacteria.
Secondary Clarifier: some bulking in clarifier due to filamentous bacteria. The sludge blanket was
approximately 3.5’ out of 15’. Noticeable pin floc throughout the water column. ORC reported they
have wasted and are trying several additives to aid in removing the filamentous bacteria and improve
settling. Weirs are cleaned regularly during the summer months to reduce algal growth. Staff
field-check the secondary effluent and final effluent ammonia to determine if adjustments are needed.
Solids Management: Solids are hauled from the digester by ACL Pumping and are typically brought
to Brevard or Rosman WWTP. Approximately four loads a month.
Settling Ponds: Two of the three ponds were in use at the time of the inspection. Secondary effluent
was flowing into the middle pond, chlorine contact chamber and then into the final settling pond
before being discharged. Duckweed was covering the surface of the third settling pond; however, a
PVC baffle near the pond effluent seems to prevent the duckweed from discharging through the
dechlorinator and effluent weir.
Chlorine/Dechlor: Chlorine is dosed at a set amount. The hypochlorite container is stored in a
building between the settling ponds. Dechlorination tablets are stored behind the building. Staff have
added a third dechlor tube just upstream of the effluent weir to ensure adequate chlorine removal.
Staff report they have not experienced issues with BOD demand due to the increased dechlor tabs.
Effluent: The ORC reported the weir overtops when the creek level rises during flood events, due to
the proximity to the stream and size of the effluent channel. This prevents accurate effluent flow
measurements during these events. This is being assessed during the planning for the facility
upgrade.
Effluent Sampler: Facility utilizes a portable sampler. Tubing is covered from the sampler to the
sampling location. The sampler is filled with ice during sample collection. Temperatures are checked
when samples are poured.
NC0022985 17 (Cont.)
Page#2
Docusign Envelope ID: 41432680-6A73-42A7-B04D-981EC0C1388E
Permit:NC0022985
Inspection Date:07/23/2024
Owner - Facility:
Inspection Type:
Fairfield Sapphire Valley WWTP
Compliance Evaluation
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain-of-custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Annual average flows are less than 200,000 gallons. See summary for
recommendations.
Comment:
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
DO, pH, setteable solids, sludge judge and NH3.Comment:
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Page#3
Docusign Envelope ID: 41432680-6A73-42A7-B04D-981EC0C1388E
Permit:NC0022985
Inspection Date:07/23/2024
Owner - Facility:
Inspection Type:
Fairfield Sapphire Valley WWTP
Compliance Evaluation
Permit Yes No NA NE
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Comment:
Bar Screens Yes No NA NE
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Manual bar screen and comminutor.Comment:
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Is the basin free of dead spots?
Are surface aerators and mixers operational?
Are the diffusers operational?
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin’s surface?
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0 mg/l)
Some foaming due to filamentous see summary for details.Comment:
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Page#4
Docusign Envelope ID: 41432680-6A73-42A7-B04D-981EC0C1388E
Permit:NC0022985
Inspection Date:07/23/2024
Owner - Facility:
Inspection Type:
Fairfield Sapphire Valley WWTP
Compliance Evaluation
Secondary Clarifier Yes No NA NE
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately ¼ of the sidewall depth)
Some filamentous affecting settling within the clarifier. Pin floc throughout the water
column. See summary for details.
Comment:
Aerobic Digester Yes No NA NE
Is the capacity adequate?
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
# Is tankage available for properly waste sludge?
Sludge holding tank was settling during the inspection.Comment:
Lagoons Yes No NA NE
Type of lagoons?
# Number of lagoons in operation at time of visit?2
Are lagoons operated in?Series
# Is a re-circulation line present?
Is lagoon free of excessive floating materials?
# Are baffles between ponds or effluent baffles adjustable?
Are dike slopes clear of woody vegetation?
Are weeds controlled around the edge of the lagoon?
Are dikes free of seepage?
Are dikes free of erosion?
Are dikes free of burrowing animals?
# Has the sludge blanket in the lagoon (s) been measured periodically in multiple
locations?
# If excessive algae is present, has barley straw been used to help control the growth?
Is the lagoon surface free of weeds?
Is the lagoon free of short circuiting?
Page#5
Docusign Envelope ID: 41432680-6A73-42A7-B04D-981EC0C1388E
Permit:NC0022985
Inspection Date:07/23/2024
Owner - Facility:
Inspection Type:
Fairfield Sapphire Valley WWTP
Compliance Evaluation
Lagoons Yes No NA NE
There are three settling ponds in series. See summary for details.Comment:
Disinfection-Liquid Yes No NA NE
Is there adequate reserve supply of disinfectant?
(Sodium Hypochlorite) Is pump feed system operational?
Is bulk storage tank containment area adequate? (free of leaks/open drains)
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de-chlorination?
Comment:
De-chlorination Yes No NA NE
Type of system ?Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de-chlorination substance stored away from chlorine containers?
Comment:
Are the tablets the proper size and type?
Are tablet de-chlorinators operational?
Number of tubes in use?3
Comment:
Flow Measurement - Effluent Yes No NA NE
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Facility utilizes their SCADA system for reporting and maintains a chart recorder. Flow
meter last calibrated on 1/5/24 by ISI.
Comment:
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
Page#6
Docusign Envelope ID: 41432680-6A73-42A7-B04D-981EC0C1388E
Permit:NC0022985
Inspection Date:07/23/2024
Owner - Facility:
Inspection Type:
Fairfield Sapphire Valley WWTP
Compliance Evaluation
Effluent Pipe Yes No NA NE
If effluent (diffuser pipes are required) are they operating properly?
Comment:
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Facility utilizes a portable sampler.Comment:
Standby Power Yes No NA NE
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up
power?
Is the generator fuel level monitored?
A portable generator is located at the WWTP and extra fuel is maintained onsite.Comment:
Page#7