HomeMy WebLinkAboutNC0038687_Compliance Evaluation Inspection_20240807
SENT VIA ELECTRONIC MAIL ONLY: NO HARD COPY WILL BE MAILED
August 08, 2024
Patricia Kennedy
Singing Waters Camping Resort
Email: gurjit@litsanleandro.com
SUBJECT: Compliance Inspection Report
Singing Waters Camping Resort
NPDES WW Permit No. NC0038687
Jackson County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Singing Waters Camping
Resort on 7/24/2024. This inspection was conducted to verify that the facility is operating in compliance
with the conditions and limitations specified in NPDES WW Permit No. NC0038687. The findings and
comments noted during this inspection are provided in the enclosed copy of the inspection report
entitled "Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a response to this
inspection report is not required.
If you should have any questions, please do not hesitate to contact Mikal Willmer with the Water
Quality Regional Operations Section in the Asheville Regional Office at 828-296-4500 or via email at
mikal.willmer@deq.nc.gov.
Sincerely,
Daniel Boss, Assistant Regional Supervisor
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS: Inspection Report
Ec: LF
Docusign Envelope ID: F074EC73-6533-4196-B775-D9FAE519C733
EPA
United States Environmental Protection Agency
Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 N 52 NC0038687 24/07/24 C S31112171819 20
21 66
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
N67707172 73 74 75 80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Singing Waters Camping Resort
1006 Trout Creek Rd
Tuckasegee NC 28783
Entry Time/Date Permit Effective Date
Exit Time/Date Permit Expiration Date
09:30AM 24/07/24 24/02/01
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Alva Gray Wike/ORC/828-586-5588/
Other Facility Data
10:30AM 24/07/24 28/10/31
Name, Address of Responsible Official/Title/Phone and Fax Number
Ken Dinger, //828-421-1282/Contacted
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self-Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date
Richard Eguino DWR/ARO WQ/828-296-4500/
Mikal Willmer DWR/ARO WQ/828-296-4686/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
Daniel J Boss DWR/ARO WQ/828-296-4658/
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#1
Docusign Envelope ID: F074EC73-6533-4196-B775-D9FAE519C733
8/8/2024
8/9/2024
8/9/2024
NPDES yr/mo/day
24/07/24
Inspection Type
C3111218
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Mikal Willmer and Richard Eguino, with the Asheville Regional Office, conducted a compliance
evaluation inspection of the Singing Waters Campground WWTP on July 25, 2024. This inspection
was conducted to determine whether the facility is being operated and maintained in compliance with
NPDES permit #NC0038687. Gray Wike, ORC Environmental Inc., was present and assisted in the
inspection.
Overall, the facility appeared to be maintained in compliance with Permit #NC0038687. This is a small
package plant that services a campground with RV sites and cabins seasonally from May to
November. The ORC, Mr. Wike, reported most maintenance is handled by Singing Waters personnel
unless they request help from Environmental Inc.
Influent Lift station: There is a small influent pump at the head of the package plant that appears to
be float activated. The ORC indicated he does not check this pump. DWR recommends the ORC
verify operability of the pump and float on occasion since there does not appear to be an audible or
visual alarm. The pump appeared to be operable at the time of the inspection.
Manual Bar Screen: A coarse manual bar screen is located immediately downstream of where the
influent discharges into the package plant. No major obstructions or debris noted on the screen. Mr.
Wike reported Singing Waters has posted signs within the bathrooms regarding what not to flush but
has had some minor issues with rags.
Aeration Basin (AB): ORC reports an old timer controls the blower motors for the diffusers and limits
his ability to adjust air into the facility. Additionally, due to the facilities proximity to the RV and cabin
sites, Signing Waters staff have requested these motors remain off during the evening hours. At the
time of the inspection the blowers were on, and the DO was reading 6.99 mg/L in the AB. No noted
dead spots or obvious leaks within the airline noted.
Clarifier: Hopper style secondary clarifier approximately 12 feet deep. The facility has minimal solids
due to low flows. Mr. Wike stated he has not had to remove solids from the clarifier since taking over
operation of the facility. The sludge blanket was approximately 1’ out of 11’. The plant does not have
a sludge holding tank due to limited flow and solids.
Chlorinator: one of the two tubes was in use at the time of the inspection. Effluent from the chlorinator
flows into the chlorine contact chamber, which has a baffled wall for additional settling before
discharging to the dechlorinator.
Dechlor Chamber: Two of the tubes were in use and several more dechlor tabs were placed in the
chamber. Recommend ORC continue to monitor the effluent results to ensure the number of dechlor
tabs is not adversely affecting BOD results for the facility.
Effluent Pipe: the area around the outfall was being maintained and the ORC did not report any
issues with flow backing up into the facility when the creek level rises.
NC0038687 17 (Cont.)
Page#2
Docusign Envelope ID: F074EC73-6533-4196-B775-D9FAE519C733
Permit:NC0038687
Inspection Date:07/24/2024
Owner - Facility:
Inspection Type:
Singing Waters Camping Resort
Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
DOComment:
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Comment:
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain-of-custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Page#3
Docusign Envelope ID: F074EC73-6533-4196-B775-D9FAE519C733
Permit:NC0038687
Inspection Date:07/24/2024
Owner - Facility:
Inspection Type:
Singing Waters Camping Resort
Compliance Evaluation
Record Keeping Yes No NA NE
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Comment:
Bar Screens Yes No NA NE
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Comment:
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Is the basin free of dead spots?
Are surface aerators and mixers operational?
Are the diffusers operational?
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin’s surface?
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0 mg/l)
Comment:
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Page#4
Docusign Envelope ID: F074EC73-6533-4196-B775-D9FAE519C733
Permit:NC0038687
Inspection Date:07/24/2024
Owner - Facility:
Inspection Type:
Singing Waters Camping Resort
Compliance Evaluation
Secondary Clarifier Yes No NA NE
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately ¼ of the sidewall depth)
Comment:
Disinfection-Tablet Yes No NA NE
Are tablet chlorinators operational?
Are the tablets the proper size and type?
Number of tubes in use?1
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de-chlorination?
Comment:
De-chlorination Yes No NA NE
Type of system ?Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de-chlorination substance stored away from chlorine containers?
Comment:
Are the tablets the proper size and type?
Are tablet de-chlorinators operational?
Number of tubes in use?2
Comment:
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment:
Page#5
Docusign Envelope ID: F074EC73-6533-4196-B775-D9FAE519C733
Permit:NC0038687
Inspection Date:07/24/2024
Owner - Facility:
Inspection Type:
Singing Waters Camping Resort
Compliance Evaluation
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Permit requires grab samples only.Comment:
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type,
and sampling location)?
Temperature required weekly. US 50 feet from the outfall and 100 feet DS from the
outfall.
Comment:
Page#6