August 2, 2024
Scott Webber, Town Manager
Town of Spindale
PO Box 186
Spindale, NC 28160
Subject: Notice of Violation
NOV-2024-PC-0468
Compliance Inspection
Town of Spindale
NPDES Permit No. NCO020664
Rutherford County
Dear Mr. Webber:
The North Carolina Division of Water Resources conducted an inspection of the Town of
Spindale facility on July 23, 2024. This inspection was conducted to verify that the facility is
operating in compliance with the conditions and limitations specified in NPDES WW Permit No.
NC0020664. The findings and comments noted during this inspection are provided in the
enclosed copy of the inspection report entitled " Compliance Inspection Report".
The main area of concern observed during the inspection is that Clarifier number #3 has been
continually out of service for over 5 years, which does not allow the facility to operate at it's
permitted flow of 3 MGD.
Please note that Part II, Section C, Condition 2 of your permit requires that, "the Permittee shall
at all times properly operate and maintain all facilities and systems of treatment and control (and
related appurtenances) which are installed or used by the Permittee to achieve compliance with
the conditions of this permit.".
Please be advised that this letter is a Notice of Violation. You are requested to respond to this
Notice in writing within thirty (30) days of receipt indicating your Plan of Action to ensure
future compliance. This Plan of Action should include a timeline within which the items will be
adequately addressed. Failure to respond and/or failure to resolve the violations could subject
you for further action by the Division of Water Resources.
,�EQi�l NW Carvl3na f]rpaRmrnt of Env] ronmcwsl QuaYty i] vision of Water Resources
& 9WA1c Rrgicoal Qflict' 12090 t15. Ftghwav 70 1 Swenrtanpa. North Garoins 28776
o�a..r, !l"2iS.l96.+ISUU
Docusign Envelope ID: F1FFC3B0-E286-4D1B-9369-2D481258682E
The report should be self-explanatory; however, should you have any questions concerning this
report, please do not hesitate to contact Ori Tuvia at (704) 235-2190, or at ori.tuvia(cdeq.nc.gov.
Sincerely,
Docu Signed by:
Va�,it,�, �°jbSS
E397192DABFB4FF...
by Daniel Boss, Assistant Regional Supervisor
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
Attachments: Compliance Inspection Report
Cc: Central Files w/ attachment (Laserfiche)
Guy O'Connor, ORC (E-copy)
Docusign Envelope ID: F1 FFC3BO-E286-4D1 B-9369-2D481258682E
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NCO020664 I11 121 24/07/23 I17 18I � I 19 I s I 201 I
211IIIII 111111III II III III1 I I IIIII IIIIIIIII II r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
2.0 701d I 71 I„ I 72 I r., I 71 I 74 79 I I I I I I I80
L—I ty L-1 I I
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES Dermit Number)
10:OOAM 24/07/23
20/07/01
Spindale WWTP
Ecology St
Exit Time/Date
Permit Expiration Date
Spindale NC 28160
11:45AM 24/07/23
24/07/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Guy Peter O'Connor/ORC/704-434-2261/
Sibyl Canipe Brotherton/ORC//
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Guy O'Connor,327 Ecology St Spindale NC 28160//828-286-3407/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Sludge Handling Dispo: Facility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
DocuSigned by:
OriATuvia DWR/NPDES WW Permitting Unit/704-663-1699/ 8/1/2024
CC i
66057A2DE017498...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
DocuSigned by:
Daniel J Boss DWR/ARO WQ/828-296-4658/ 8/1/2024
Fyauut,�, �°jbSS
`trait a�uH�tr�snrr..
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
Docusign Envelope ID: F1 FFC3B0-E286-4D1 B-9369-2D481258682E
NPDES yr/mo/day Inspection Type (Cont.)
NCO020664 I11 12I 24/07/23 117 18 i c i
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Ori Tuvia, Alex Brown and Eric Anne visited the site on July 23, 2024 and met with ORC Guy
O'Conner and BORC Sybil Brotherton.
Overall, the facility is well -maintained and operated. All paperwork was organized and easily
accessible. The main area of concern is that Clarifier number #3 has been continually out of service
due to maintenance issue for over 5 years, which does not allow the facility to operate at it's
permitted flow of 3 MGD.
Bar Screen: The facility is still experiencing pass through into the plant from the manual bar screen of
the septage dump station and the mechanical bar screen due to the bars being spaced too far apart
this project will be applied for once financing is secured.
Page#
Docusign Envelope ID: F1 FFC3B0-E286-4D1 B-9369-2D481258682E
Permit: NCO020664 Owner -Facility: Spindale WWTP
Inspection Date: 07/23/2024 Inspection Type: Compliance Evaluation
Permit
Yes
No
NA
NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
■
❑
❑
❑
application?
Is the facility as described in the permit?
■
❑
❑
❑
# Are there any special conditions for the permit?
■
❑
❑
❑
Is access to the plant site restricted to the general public?
■
❑
❑
❑
Is the inspector granted access to all areas for inspection?
■
❑
❑
❑
Comment: The facility's permit has expired, however, the facility has appliied for permit
renwall
within the time alloted. Currently the permit under a compliance schedule per
Part I,
Section A. (4.) of their NPDES permit for Silver and Copper effluent limits.
Record Keeping
Yes
No
NA
NE
Are records kept and maintained as required by the permit?
■
❑
❑
❑
Is all required information readily available, complete and current?
■
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
❑
❑
❑
■
Are analytical results consistent with data reported on DMRs?
■
❑
❑
❑
Is the chain -of -custody complete?
■
❑
❑
❑
Dates, times and location of sampling
■
Name of individual performing the sampling
■
Results of analysis and calibration
■
Dates of analysis
■
Name of person performing analyses
■
Transported COCs
■
Are DMRs complete: do they include all permit parameters?
■
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
❑
■
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
❑
❑
■
❑
operator on each shift?
Is the ORC visitation log available and current?
■
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
■
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility
■
❑
❑
❑
classification?
Is a copy of the current NPDES permit available on site?
■
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
❑
■
Page# 3
Docusign Envelope ID: F1 FFC3B0-E286-4D1 B-9369-2D481258682E
Permit: NCO020664 Owner -Facility: Spindale WWTP
Inspection Date: 07/23/2024 Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Comment: The records reviewed durinq the inspection were organized and well maintained.
In-depth operation and maintenance records including process control measurements
were being documented and maintained on -site. Discharge monitoring reports
(eDMRs) ORC log and calibration logs were reviewed for the period April 2024 through
June 2024.
Flow Measurement - Influent
Yes
No
NA
NE
# Is flow meter used for reporting?
❑
0
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
❑
Comment: The influent flow meter is not used for reporting. The influent flow meter was last
calibrated on March 6, 2024 by Laboratory Instrument Service.
Laboratory
Yes
No
NA NE
Are field parameters performed by certified personnel or laboratory?
■
❑
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab?
0
❑
❑
❑
# Is the facility using a contract lab?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
■
❑
❑
❑
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
■
❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
❑
■
❑
Comment:
Influent Sampling
Yes
No
NA
NE
# Is composite sampling flow proportional?
0
❑
❑
❑
Is sample collected above side streams?
0
❑
❑
❑
Is proper volume collected?
❑
❑
❑
Is the tubing clean?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
■
❑
❑
❑
degrees Celsius)?
Is sampling performed according to the permit?
0
❑
❑
❑
Comment: The subject permit requires influent BOD and TSS composite samples.
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? 0 ❑ ❑ ❑
Page# 4
Docusign Envelope ID: F1 FFC3B0-E286-4D1 B-9369-2D481258682E
Permit: NCO020664 Owner -Facility: Spindale WWTP
Inspection Date: 07/23/2024 Inspection Type: Compliance Evaluation
Effluent Sampling
Yes
No
NA
NE
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
0
❑
❑
❑
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
❑
❑
❑
representative)?
Comment: The subject permit requires composite and grab effluent samples. Aliquat sample
was
taken duing the inspection and was withinn acceptable range.
Upstream / Downstream Sampling
Yes
No
NA
NE
Is the facility sampling performed as required by the permit (frequency, sampling type,
0
❑
❑
❑
and sampling location)?
Comment:
Operations & Maintenance
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Yes No NA NE
❑ ■ ❑ ❑
❑ ❑ ❑
Comment: Process controls analyzed include DO,
PH, MLSS, SVI, settleable solids, and a sludge
fudge. Clarifier number #3 has been continually out of service due to maintenance
issue for over 5 years
Bar Screens
Yes
No
NA NE
Type of bar screen
a.Manual
❑
b.Mechanical
Are the bars adequately screening debris?
0
❑
❑
❑
Is the screen free of excessive debris?
■
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Comment:
Grit Removal Yes No NA NE
Type of grit removal
a.Manual ❑
Page# 5
Docusign Envelope ID: F1 FFC3B0-E286-4D1 B-9369-2D481258682E
Permit: NCO020664
Inspection Date: 07/23/2024
Owner -Facility: Spindale WWTP
Inspection Type: Compliance Evaluation
Grit Removal
b.Mechanical
Is the grit free of excessive organic matter?
Is the grit free of excessive odor?
# Is disposal of grit in compliance?
Comment: Lime is added as needed during grit removal to increase pH. Grit
wheelbarrows and is then disposed of in dumpsters.
Equalization Basins
Is the basin aerated?
Is the basin free of bypass lines or structures to the natural environment?
Is the basin free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Are audible and visual alarms operable?
# Is basin size/volume adequate?
into
Yes
No
NA
NE
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
Yes
No
NA
NE
•
❑
❑
❑
•
❑
❑
❑
❑
❑
❑
■
■
❑
❑
❑
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
■
❑
❑
❑
Comment: The EQ basin is only utilized during wet weather and is fully operational. Flow is
diverted to the EQ basin as needed and the EQ basin is pumped out to the aeration
basin once influent flow lowers. At the time of the inspection the EQ basin was empty
and not in use due to dry weather.
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system
Diffused
Is the basin free of dead spots?
■
❑
❑
❑
Are surface aerators and mixers operational?
❑
❑
■
❑
Are the diffusers operational?
E
❑
❑
❑
Is the foam the proper color for the treatment process?
0
❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0
❑
❑
❑
Is the DO level acceptable?
0
❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
0
❑
❑
❑
Comment: At the time of the inspection, the south basin was the only aeration basin in operation.
The south aeration basin has four
zones with diffusers - each zone has a permanent DO meter.
Page# 6
Docusign Envelope ID: F1 FFC3B0-E286-4D1 B-9369-2D481258682E
Permit: NCO020664 Owner -Facility: Spindale WWTP
Inspection Date: 07/23/2024 Inspection Type: Compliance Evaluation
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
Yes
No
NA
NE
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
Comment: Flow is split between clarifiers #1 and #2, the clarifiers are in need of maintenance
however, they cannot be taken off-line for repair due to the 3rd clarifier being
continuously out of service. Clarifier #3 has still not been refurbished there during the
inspection it appeared to have excessive vegetation growing in it, inoperable pumps,
rusting drive units and require extensive repairs. With the clarifier being out of service,
the ORC, indicated that the facility can not treat it's permitted flow of 3 MGD, and has
difficulty maintaining maintenance schedule for clarifiers 1 and 2.
Pumps-RAS-WAS
Yes
No
NA NE
Are pumps in place?
0
❑
❑
❑
Are pumps operational?
0
❑
❑
❑
Are there adequate spare parts and supplies on site?
0
❑
❑
❑
Comment: RAS pumps are requarly cleaned out. There is a spare impellar
and motor on -site as a
backup.
Disinfection -Gas
Yes
No
NA
NE
Are cylinders secured adequately?
0
❑
❑
❑
Are cylinders protected from direct sunlight?
■
❑
❑
❑
Is there adequate reserve supply of disinfectant?
0
❑
❑
❑
Is the level of chlorine residual acceptable?
■
❑
❑
❑
Is the contact chamber free of growth, or sludge buildup?
■
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
❑
❑
❑
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No.
❑
❑
❑
7782-50-5)?
If yes, then is there a Risk Management Plan on site?
❑
❑
❑
Page# 7
Docusign Envelope ID: F1 FFC3B0-E286-4D1 B-9369-2D481258682E
Permit: NCO020664 Owner -Facility: Spindale WWTP
Inspection Date: 07/23/2024 Inspection Type: Compliance Evaluation
Disinfection -Gas Yes No NA NE
If yes, then what is the EPA twelve digit ID Number? (1000- - )
If yes, then when was the RMP last updated?
Comment: There are two chlorine contact basins, but
De -chlorination
Type of system ?
Is the feed ratio proportional to chlorine amount (1 to 1)?
one is currently in use due to low flow.
Is storage appropriate for cylinders?
# Is de -chlorination substance stored away from chlorine containers?
Are the tablets the proper size and type?
Comment: Cylinders sit outside of the chemical feed rooms under a roof.
Are tablet de -chlorinators operational?
Number of tubes in use?
Comment:
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Yes No NA NE
Gas
❑ ❑ ❑ ■
■ ❑ ❑ ❑
❑ ■ ❑ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
Yes No NA NE
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ❑ ■
Comment: The effluent flow meter was last calibrated on March 6, 2024 by Laboratory Instrument
Service.
Effluent Pipe
Yes
No
NA
NE
Is right of way to the outfall properly maintained?
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
0
❑
Comment: The effluent pipe is approximately two miles away from the facility. Staff have a
sampling manhole down by the river. Mr. O'Connor indicated that the effluent pipe is
checked weekly and the right of way is properly maintained. The discharge from the
facility can be re -aerated if needed.
Aerobic Digester
Is the capacity adequate?
Is the mixing adequate?
Yes No NA NE
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Page# 8
Docusign Envelope ID: F1 FFC3B0-E286-4D1 B-9369-2D481258682E
Permit: NCO020664 Owner -Facility: Spindale WWTP
Inspection Date: 07/23/2024 Inspection Type: Compliance Evaluation
Aerobic Digester
Yes No NA NE
Is the site free of excessive foaming in the tank?
0
❑
❑
❑
# Is the odor acceptable?
■
❑
❑
❑
# Is tankage available for properly waste sludge?
0
❑
❑
❑
Comment: There are two aerobic digesters available on -site. Decant from the digesters goes to
the aeration basin. One digester is wasted at a time. Spindale holds a Class B land
application permit (WQ0001953) and contracts US Biosolids for land application
events.
Standby Power
Yes
No
NA
NE
Is automatically activated standby power available?
0
❑
❑
❑
Is the generator tested by interrupting primary power source?
❑
❑
❑
Is the generator tested under load?
■
❑
❑
❑
Was generator tested & operational during the inspection?
■
❑
❑
❑
Do the generator(s) have adequate capacity to operate the entire wastewater site?
❑
❑
❑
Is there an emergency agreement with a fuel vendor for extended run on back-up
❑
❑
❑
■
power?
Is the generator fuel level monitored?
❑
❑
❑
Comment: The generator automatically exercises once per week and runs under load every
couple months. The manufacturer maintains the generator semi-annually,
the fuel is
checked once a month.
Page# 9