HomeMy WebLinkAboutWQ0018992_Compliance Evaluation Inspection_20240730 Docusign Envelope ID:80C275DC-5270-4D52-BB17-EE9938DE52B4
ROY COOPER
Governor
ELIZABETH S.BISER
Secretary
RICHARD E.ROGERS,JR. NORTH CAROLINA
Director Environmental Quality
July 30, 2024
Terry Barbour
A Place at the Beach - Atlantic Beach Inc DBA Southwinds Condo Assoc
PO Box 818
Atlantic Beach, NC 28512-0818
SUBJECT: Compliance Inspection Report
Southwinds WWTP
Non-discharge Permit No. WQ0018992
Carteret County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Southwinds WWTP on
7/19/2024. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in Non-discharge Permit No. WQ0018992. The findings and
comments noted during this inspection are provided in the enclosed copy of the inspection report
entitled "Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a response to this
inspection report is not required.
If you should have any questions, please do not hesitate to contact Michael Meilinger with the Water
Quality Regional Operations Section in the Wilmington Regional Office at 910-796-7215 or via email at
michael.meilinger@deq.nc.gov.
Sincerely,
DocuSigned by:
64448728F481494...
Morella Sanchez-King, Regional Supervisor
Water Quality Regional Operations Section
Wilmington Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS
Cc: WQS Wilmington Regional Office - Enforcement File
NON-DISCHARGE Compliance/Enforcement Unit - Enforcement File
ce..�.m.E..,.D:Q�� North Carolina Department of Envl—ental Quality I Division of Water Resources
Wilmington Regional office 1127 Cardinal Drive Extension I Wllmin9t0m North Carolina 28405
910.796.7215
Docusign Envelope ID:80C275DC-5270-4D52-BB17-EE9938DE52B4
Compliance Inspection Report
Permit:WQ0018992 Effective: 10/01/20 Expiration: 11/30/26 Owner: A Place at the Beach-Atlantic Beach Inc DBA
Southwinds Condo Assoc
SOC: Effective: Expiration: Facility: Southwinds WWTP
County: Carteret 2008 E Fort Macon Rd
Region: Wilmington
Atlantic Beach NC 28512
Contact Person:Terry Barbour Title: Property Manager Phone: 252-247-2318
Directions to Facility:
Highway 70 E (Arendell Street)in Morehead City, R onto Atlantic Beach Bridge/Causeway SR1182, L onto East Fort Macon Road
System Classifications: SI, WW2,
Primary ORC: Donald P Omara Certification: 22801 Phone:252-247-9167
Secondary ORC(s):
On-Site Representative(s):
Related Permits:
Inspection Date: 07/19/2024 Entry Time 10:10AM Exit Time: 12:OOPM
Primary Inspector:Michael J Meilinger Phone: 704-235-2183
Secondary Inspector(s):
Reason for Inspection: Routine Inspection Type: Compliance Evaluation
Permit Inspection Type: High Rate Infiltration
Facility Status: Compliant ❑ Not Compliant
Question Areas:
Treatment Flow Measurement-Effluent Treatment Flow Measurement-Influent Miscellaneous Questions
Treatment Flow Measurement-Water Treatment Treatment Barscreen
Use Records
Treatment Filters Record Keeping Treatment Activated Sludge
Treatment Influent Pump Station Treatment Clarifiers Treatment Disinfection
End Use-Infiltration Treatment Flow Measurement Treatment Return pumps
Standby Power Wells
(See attachment summary)
Page 1 of 7
Docusign Envelope ID:80C275DC-5270-4D52-BB17-EE9938DE52B4
Permit: WQ0018992 Owner-Facility:A Place at the Beach-Atlantic Beach Inc DBA Southwinds Condo Assoc
Inspection Date: 07/19/2024 Inspection Type:Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
A routine compliance inspection of the Southwinds WWTF was conducted on July 19, 2024. The purpose of the evaluation
was to verify that the facility is operating in compliance with the conditions and limitations specified in Permit WQ0018992.
Don and Karrie O'Mara were presnt during the inspection.
The extended aeration treatment plant with a high-rate infiltration, drip irrigation system is permitted for 43,200 GPD. The
2023-2024 flow averaged —3,000 GPD during the winter season and —15,000 GPD in the summer.
The plant does not have a chlorine contact chamber and disinfection contact time takes place in the dosing tank before it is
discharged to the drip irrigation fields. EQ tank and plant upgrade were completed since last inspection.
A file review since the last inspection in July 15, 2022 shows no effluent violations and several incidences of slight elevation
of TDS levels in MW#1 and MW#3, and elevated results for Nitrogen, Nitrate Total.
The facility is compliant with Non-Discharge Permit WQ0018992. Please review the comment sections of the inspection
report for more details.
Page 2 of 7
Docusign Envelope ID:80C275DC-5270-4D52-BB17-EE9938DE52B4
Permit: WQ0018992 Owner-Facility:A Place at the Beach-Atlantic Beach Inc DBA Southwinds Condo Assoc
Inspection Date: 07/19/2024 Inspection Type:Compliance Evaluation Reason for Visit: Routine
Type Yes No NA NE
Reuse(Quality) ❑
Lagoon Spray, LR ❑
Single Family Spray, LR ❑
Activated Sludge Spray, LR ❑
Activated Sludge Spray, HR ❑
Activated Sludge Drip, LR ❑
Single Family Drip ❑
Recycle/Reuse ❑
Infiltration System
Treatment Yes No NA NE
Are Treatment facilities consistent with those outlined in the current permit? 0 ❑ ❑ ❑
Do all treatment units appear to be operational? (if no, note below.) 0 ❑ ❑ ❑
Comment: No comment.
Treatment Influent Pump Station Yes No NA NE
Is the pump station free of bypass lines or structures? 0 ❑ ❑ ❑
Is the general housekeeping acceptable? ❑ ❑ ❑
Are all pumps present? ❑ ❑ ❑
Are all pumps operable? ❑ ❑ ❑
Are floats/controls operable? ❑ ❑ ❑
Are audio and visual alarms available? 0 ❑ ❑ ❑
Are audio and visual alarms operational? ❑ ❑ ❑
#Are SCADA/Telemetry alarms required? ❑ ❑ ❑
Are SCADA/Telemetry available? ❑ ❑ ❑
Are SCADA/Telemetry operational? ❑ ❑ 0 ❑
Comment: The influent pump station and plant is located at the entrance of the condo development. The
high level alarm is connected to a telemetry system which notifies the ORC by cell phone.
Treatment Flow Measurement-Influent Yes No NA NE
Is flowmeter calibrated annually? ❑ ❑ 0 ❑
Is flowmeter operating properly? ❑ ❑ 0 ❑
Does flowmeter monitor continuously? ❑ ❑ 0 ❑
Does flowmeter record flow? ❑ ❑ 0 ❑
Does flowmeter appear to monitor accurately? ❑ ❑ 0 ❑
Comment:
Page 3 of 7
Docusign Envelope ID:80C275DC-5270-4D52-BB17-EE9938DE52B4
Permit: WQ0018992 Owner-Facility:A Place at the Beach-Atlantic Beach Inc DBA Southwinds Condo Assoc
Inspection Date: 07/19/2024 Inspection Type:Compliance Evaluation Reason for Visit: Routine
Treatment Flow Measurement-Water Use Records Yes No NA NE
Is water use metered? ❑ ❑ 0 ❑
Are the daily average values properly calculated? ❑ ❑ 0 ❑
Comment:
Treatment Flow Measurement-Effluent Yes No NA NE
Is flowmeter calibrated annually? ❑ ❑ ❑
Is flowmeter operating properly? ❑ ❑ ❑
Does flowmeter monitor continuously? ❑ ❑ ❑
Does flowmeter record flow? ❑ ❑ ❑
Does flowmeter appear to monitor accurately? N ❑ ❑ ❑
Comment: The Flow meter was calibrated May 15, 2024, by Delta Systems Envionmental.
Standby Power Yes No NA NE
Is automatically activated standby power available? 0 ❑ ❑ ❑
Is generator tested weekly by interrupting primary power source? 0 ❑ ❑ ❑
Is generator operable? 0 ❑ ❑ ❑
Does generator have adequate fuel? 0 ❑ ❑ ❑
Comment: No comment.
Treatment Barscreen Yes No NA NE
Is it free of excessive debris? ❑ ❑ ❑
Is disposal of screenings in compliance? ❑ ❑ ❑
Are the bars spaced properly? ❑ ❑ ❑
Is the unit in good condition? ❑ ❑ ❑
Comment:
Treatment Activated Sludge Yes No NA NE
Is the aeration mechanism operable? ❑ ❑ ❑
Is the aeration basin thoroughly mixed? ❑ ❑ ❑
Is the aeration equipment easily accessed? ❑ ❑ ❑
Is Dissolved Oxygen adequate? ❑ ❑ ❑
Are Settleometer results acceptable? ❑ ❑ ❑
Is activated sludge an acceptable color? 0 ❑ ❑ ❑
Comment:
Treatment Clarifiers Yes No NA NE
Are the weirs level? ❑ ❑ ❑
Are the weirs free of solids and algae? ❑ ❑ ❑
Is the scum removal system operational? ❑ ❑ ❑
Page 4 of 7
Docusign Envelope ID:80C275DC-5270-4D52-BB17-EE9938DE52B4
Permit: WQ0018992 Owner-Facility:A Place at the Beach-Atlantic Beach Inc DBA Southwinds Condo Assoc
Inspection Date: 07/19/2024 Inspection Type:Compliance Evaluation Reason for Visit: Routine
Is the scum removal system accessible? ❑ ❑ ❑
Is the sludge blanket at an acceptable level? ❑ ❑ ❑
Is the effluent from the clarifier free of excessive solids? 0 ❑ ❑ ❑
Comment: No comment.
Treatment Return pumps Yes No NA NE
Are they in place? 0 ❑ ❑ ❑
Are they operational? 0 ❑ ❑ ❑
Comment:
Treatment Filters Yes No NA NE
Is the filter media present? ❑ ❑ ❑
Is the filter media the correct size and type? ❑ ❑ ❑
Is the air scour operational? ❑ ❑ ❑
Is the scouring acceptable? ❑ ❑ ❑
Is the clear well free of excessive solids? ❑ ❑ ❑
Is the mud well free of excessive solids and filter media? ❑ ❑ ❑
Does backwashing frequency appear adequate? 0 ❑ ❑ ❑
Comment: The filters consist of a course screen. Staff backwashes units manually when accumulation of
solids reaches -1 inch.
Treatment Disinfection Yes No NA NE
Is the system working? ❑ ❑ ❑
Do the fecal coliform results indicate proper disinfection? ❑ ❑ ❑
Is there adequate detention time(>=30 minutes)? ❑ ❑ ❑
Is the system properly maintained? ❑ ❑ ❑
If gas, does the cylinder storage appear safe? ❑ ❑ ❑
Is the fan in the chlorine feed room and storage area operable? ❑ ❑ ❑
Is the chlorinator accessible? ❑ ❑ ❑
If tablets, are tablets present? ❑ ❑ ❑
Are the tablets the proper size and type? ❑ ❑ ❑
Is contact chamber free of sludge, solids, and growth? ❑ ❑ ❑
If UV, are extra UV bulbs available? ❑ ❑ ❑
If UV, is the UV intensity adequate? ❑ ❑ ❑
# Is it a dual feed system? ❑ ❑ ❑
Does the Stationary Source have more than 2500 Ibs of Chlorine(CAS No. 7782-50-5)? ❑ ❑ ❑
If yes,then is there a Risk Management Plan on site? ❑ ❑ ❑
If yes,then what is the EPA twelve digit ID Number? (1 000- - )
If yes,then when was the RMP last updated?
Page 5 of 7
Docusign Envelope ID:80C275DC-5270-4D52-BB17-EE9938DE52B4
Permit: WQ0018992 Owner-Facility:A Place at the Beach-Atlantic Beach Inc DBA Southwinds Condo Assoc
Inspection Date: 07/19/2024 Inspection Type:Compliance Evaluation Reason for Visit: Routine
Comment: The plant does not have a chlorine contact chamber. Effluent from the chlorinator flows directly
into the dosing tank. This design is challenging for staff to allow enough contact time before
discharging to the infiltration fields. A review of fecal results shows that the disinfection process
is adequate.
Record Keeping Yes No NA NE
Is a copy of current permit available? 0 ❑ ❑ ❑
Are monitoring reports present: NDMR? ❑ ❑ ❑
NDAR? ❑ ❑ ❑
Are flow rates less than of permitted flow? ❑ ❑ ❑
Are flow rates less than of permitted flow? ❑ ❑ ❑
Are application rates adhered to? ❑ ❑ ❑
Is GW monitoring being conducted, if required (GW-59s submitted)? ❑ ❑ ❑
Are all samples analyzed for all required parameters? ❑ ❑ ❑
Are there any 2L GW quality violations? ❑ ❑ ❑
Is GW-59A certification form completed for facility? ❑ ❑ ❑
Is effluent sampled for same parameters as GW? ❑ ❑ ❑
Do effluent concentrations exceed GW standards? ❑ ❑ ❑
Are annual soil reports available? ❑ ❑ ❑
#Are PAN records required? ❑ ❑ ❑
#Did last soil report indicate a need for lime? ❑ ❑ ❑
If so, has it been applied? ❑ ❑ ❑
Are operational logs present? ❑ ❑ ❑
Are lab sheets available for review? ❑ ❑ ❑
Do lab sheets support data reported on NDMR? ❑ ❑ ❑
Do lab sheets support data reported on GW-59s? ❑ ❑ ❑
Are Operational and Maintenance records present? ❑ ❑ ❑
Were Operational and Maintenance records complete? ❑ ❑ ❑
Has permittee been free of public complaints in last 12 months? ❑ ❑ 0 ❑
Is a copy of the SOC readily available? ❑ ❑ 0 ❑
No treatment units bypassed since last inspection? 0 ❑ ❑ ❑
Comment: A review of records since the last inspection in 2022 shows a slight elevation in TDS for MW#1
and MW#3, the Nitrogen, Nitrate Totals in MW#3 have slight elevations, but facility is in a
barrier island environment. There have been no effluent violations.
End Use-Infiltration Yes No NA NE
# Is the application High Rate or Low Rate? High Rate
Are buffers maintained? 0 ❑ ❑ ❑
Are any supply wells within the CB? ❑ ❑ ❑
Are any supply wells within 250' of the CB? ❑ ❑ ❑
Page 6 of 7
Docusign Envelope ID:80C275DC-5270-4D52-BB17-EE9938DE52B4
Permit: WQ0018992 Owner-Facility:A Place at the Beach-Atlantic Beach Inc DBA Southwinds Condo Assoc
Inspection Date: 07/19/2024 Inspection Type:Compliance Evaluation Reason for Visit: Routine
Is municipal water available in the area? 0 ❑ ❑ ❑
Are GW monitoring wells required? 0 ❑ ❑ ❑
Are GW monitoring wells located properly w/respect to RB and CB? 0 ❑ ❑ ❑
Are GW monitoring wells properly constructed, including screened interval? ❑ ❑ ❑
Is a usable green area maintained? 0 ❑ ❑ ❑
Is the disposal site acceptable? 0 ❑ ❑ ❑
Is the distribution equipment acceptable? 0 ❑ ❑ ❑
Is the disposal site free of ponding? 0 ❑ ❑ ❑
Is the disposal site free of breakout? 0 ❑ ❑ ❑
Are the disposal sites free of solids, algae, etc.? 0 ❑ ❑ ❑
Do the records show that the fields are properly maintained? 0 ❑ ❑ ❑
Are the disposal sites free of vegetation? ❑ 0 ❑ ❑
Do any surface water features appear to be adversely impacted by GW discharge? ❑ ❑ 0 ❑
No chemicals or rototiller used to eliminate vegetation, solids, algae, etc.? 0 ❑ ❑ ❑
Comment: The drip fields are covered in a landscaping cloth with rubber mulch to prevent vegetation
growth. Public access is restricted by a rope security fence and posted signs.
Page 7 of 7