HomeMy WebLinkAboutNCG550199_Compliance Evaluation Inspection_20170913 ROY COOPER
2 + G'averaor
f
MICHAEL S. REGAN
Sccmtnr;,
Water Resources
S.JAY I liwl RMAN
ENVIRONMENTAL QUALM F3freCta1•
September 13, 2017 gECEWEDINC®E01DW�
David Heroux SEP 1 S 2017
145 Forestdale Drive Water Quality
Reidsville, NC 27320 Pe
rrnitt►ng
SUBJECT: Compliance Evaluation Inspection Report
Certificate of Coverage NCG550199 under NPDES General Permit NCG550000
Facility Located at 145 Forestdale Drive, Reidsville, Rockingham County gect►on
Dear Mr. Heroux:
On September 8, 2017, Paul DiMatteo of the Division of Water Resources ("Division"), Winston-Salem
Regional Office conducted a Compliance Evaluation Inspection of the above referenced wastewater treatment
system. The Division is required to inspect these types of systems at least every 5 years. An inspection
summary follows and an inspection report is attached for your records.
Site Review
The system consists of a septic tank, subsurface sand filter, chlorinator, and outfall, with final disposal
to an unnamed tributary of Town Creek. No sewage malfunction was observed at the sand filters or at the
septic tank. You said that the septic tank was last pumped about 3 years ago.The outfall was unable to be
located. Please note that the Permit (copy attached) requires a visual review of the outfall to be conducted
twice per year.
There were no chlorine tablets present in the chlorinator. Please obtain and use chlorine tablets that
are rated for wastewater treatment, not tablets that are rated for pool use.The chlorinator should be
inspected weekly to ensure there is an adequate supply of tablets.
Please not also that our system indicates that the annual fee in the amount of$60 is overdue.
Documentation & Monitoring Review
A review of documentation was not conducted at the time of inspection. We would also like to remind
you to conduct and document the following:
- Effluent monitoring must be performed as required in the permit.
- All system components must be maintained at all times and in good working order.
- Inspect the septic tank and secondary tanks at least yearly to determine if solids must be removed.
- Pump the septic tank every 5 years, or when the solids level is found to be more than 1/3 of the
liquid depth in any compartment, whichever is greater. All tanks should be emptied of their
State of North Carolina I Environmental Quality I Water Resources
450 West Hanes Mill Road,Suite 300,Winston-Salem,NC 27105
'30Z'114 noon
contents whenever any of the tanks meet this requirement.
- Contents removed from septic tanks shall be disposed of at a location and in a manner compliant
with all local and state regulations._ . .._ _
- Inspect the outfall location at least twice per year to ensure that no visible solids or other obvious
evidence of system malfunctioning is observed.
- Inspect the tablet chlorinator (if applicable) at least weekly to ensure there is an adequate supply
of tablets for continuous & proper operation.Tablets used-for chlorination must be labeled for
wastewater use.
- Any monitoring data obtained shall be retained onsite for a minimum of 5 years.
- Additional requirements as stated in NCG550000.
There were no significant issues noted during the inspection; therefore, a response to this report is not
required.
Thank you for your cooperation in this matter. If you should have any questions, please do not hesitate
to contact Paul DiMatteo at 336-776-9691 or our office at 336-776-9800.
Sincerely,
c c/
fO'/Sherri V. Knight, P.E., Regional Supervisor
Water Quality Regional Operations Section
Winston-Salem Regional Office
Division of Water Resources, NCDEQ
Enclosures— Inspection Report and Summary, Copy of NPDES Permit
Cc: WQS Winston-Salem Regional Office
NPDES Unit, 16,174Nia llSer+�ci a Center,,
State of North Carolina I Environmental Quality I Water Resources
450 West Hanes Mill Road,Suite 300,Winston-Salem,NC 27105
336-776-9800
•
United States Environmental Protection Agency Form Approved.
EPA .-. - Washington,D.C.20460 • -OMB No.2040-0057
Water Compliance Inspection Report Approval expires 8-31-98
Section'A:National Data System Coding(i.e.,PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 E 2 �5 3 I NCG550199 I11 12 I 17/09/08 117 18 19 I c I 20 LJ
21 I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I r6
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA -Reserved-
67I I 70 I I 71 I I 72 L,J I 731 I 174 75I I I I I I I 180
I.� • Section B:Facility Data J
Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date
POTW name and NPDES permit Number) 01:10PM 17/09/08 13/08/01
145 Forestdale Drive
Exit Time/Date Permit Expiration Date
• 145 Forestdale Dr
01:25PM 17/09/08 18/07/31
Reidsville NC 27320 •
Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data
///
Name,Address of Responsible Official/Title/Phone and Fax Number ' -' - ' -
Contacted
David Heroux,145 Forstdale Dr Mebane NC 27302//336-552-8791/
No
Section C:Areas Evaluated During Inspection(Check only those areas evaluated)
Permit Facility Site Review
Section D:Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
•
Name(s)and Signature(s)of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Paul DiMatteo WSRO WQ//336-776-9691/
71)
4 C
clIt2In
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
,( / /i.i 117
EPA Form 3560-3(Rev 9-94)Previous editions are obsolete.
•
Page# 1
NPDES yr/mo/day Inspection Type (Cont.) 1
31 NCG550199 I11 121 17/09/08 17- 18 12 I
Section D:Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
Site Review
The system consists of a septic tank,subsurface sand filter, chlorinator, and outfall,with final
disposal to an unnamed tributary of Town Creek. No sewage malfunction was observed at the sand
filters or at the septic tank.You said that the septic tank was last pumped about 3 years ago.The
outfall was unable to be located. Please note that the Permit(copy attached)requires a visual review of
the outfall to be conducted twice per year.
There were no chlorine tablets present in the chlorinator. Please obtain and use chlorine tablets
that are rated for wastewater treatment, not tablets that are rated for pool use.The chlorinator should
be inspected weekly to ensure there is an adequate supply of tablets.
Documentation& Monitoring Review
A review of documentation was not conducted at the time of inspection.We would also like to
remind you to conduct and document the following:
- Effluent monitoring must be performed as required in the permit.
- All system components must be maintained at all times and in good working order.
- Inspect the septic tank and secondary tanks at least yearly to determine if solids must be removed.
- Pump the septic tank every 5 years, or when the solids level is found to be more than 1/3 of the
liquid depth in any compartment,whichever is greater.All tanks should be emptied of their contents
whenever any of the tanks meet this requirement.
Contents removed from septic tanks shall be disposed of at a location and in a manner
compliant with all local and state regulations.
- Inspect the outfall location at least twice per year to ensure that no visible solids or other obvious
evidence of system malfunctioning is observed.
- Inspect the tablet chlorinator(if applicable)at least weekly to ensure there is an adequate supply of
tablets for continuous&proper operation.Tablets used for chlorination must be labeled for wastewater
use.
- Any monitoring data obtained shall be retained onsite for a minimum of 5 years.
- Additional requirements as stated in NCG55OOOO.
Page# 2
Permit: NCG550199 Owner-Facility: 145 Forestdale Drive
- Inspection Date: 09/08/2017 Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ I ❑
application?
Is the facility as described in the permit? • ❑ ❑ ❑
#Are there any special conditions for the permit? ❑ • ❑ ❑
Is access to the plant site restricted to the general public? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? • ❑ ❑ ❑
Comment: Could not locate the outfall.
•
• Page# 3