Loading...
HomeMy WebLinkAboutWQCS00293_CEI Letter and Report 2024_20240718 Docusign Envelope ID:C90047FA-7973-4C80-A486-67484CA08CFB 11 to n�tF,•46 ROl COOPER �. Gnsthanr .• MICHAELS. REGAN Sk•�r t•tcrr• ��'^� LINDA CULPEPPER NORTH CAROL1NA Uir-�crar Environmental Quality July 18, 2024 Ms. Shannon Becker Aqua North Carolina Inc. Governor's Club Collection System 202 Mackenan Drive Cary, NC 27511 Subject: Compliance Evaluation Inspection Govenor's Club Collection System WWCS Permit WQCS00293 Chatham County Dear Ms. Becker: On July 10, 2024, Donald Smith, and Myles Parker from the NC Division of Water Resources - Raleigh Regional Office (RRO) conducted an inspection of the Governor's Club wastewater collection system to evaluate compliance with the operation and maintenance of the subject wastewater collection system permit. The cooperation and assistance of Wesley Bishop, Ashely Kilinger, and Roy Lyons during the inspection were greatly appreciated. Records indicate the wastewater collection system consists of approximately 4,023 feet of gravity sewer, approximately 21.4 miles of force main, more than 780 simplex pump stations, 8 duplex pump stations, and no high priority sewer lines. The subject permit is effective from May 24, 2018, until January 31, 2025, and is subject to specific conditions and limitations. The items below show what conditions were noted during the inspection: 1. Reported Sanitary Sewer Overflows. During the period of January 1, 2022, and July 9, 2024, there were 3 SSOs from the Governor's Club collection system with a combined estimated volume of 2,750 gallons, of which 2,650 gallons reached surface water. The SSOs during this period, resulted in this office issuing the following notices. No fish kills were reported because of the SSO events. Reported Sanitary Sewer Overflows Notice Issued by Division of Water Resources-RRO April 7,2022 [Notice of Violation October 26,2023 Notice of Violation April 24,2024 Notice of Deficiency D���� Not th CuroUna Dcp:wtmesu of Cnvironmrnt:d Quali?} Uivi�ion of`,'�'atcr Rcsuurcrs 1 —' Raleigh Regional office I :)doo Barren Drive I Raldoh.North Carolina 27(A)ct Docusign Envelope ID C90047FA-79734C80-A466-67484CA08CFB Permittee,WQCS00293 July 18,2024 2. Fats, Oils and Grease Program. Aqua North Carolina Incorporated, hereinafter referred to as PERMITTEE, has developed and implements an educational fats, oils and grease program that includes at least bi-annual distribution of educational material targeted at both residential and non-residential users. The PERMITTEE has also developed and implements an enforceable FOG program for non-residential users. 3. Capital Improvement Plan. The PERMITTEE establishes and manages funding for wastewater collection system infrastructure maintenance and repair. Funds are determined and based on the regulatory oversight of the NC Utilities Commission. 4. Contingency Plan for Pump Failure. The PERMITTEE maintains a contingency plan for collection system and pump failure for the simplex and duplex lift stations. Contracted services are available to assist with pumping and hauling if needed. Some pump stations (ie: Clubhouse PS) has bypass pump connection for mobile pump connection. Each duplex lift station has generator connections for emergency backup power. Three mobile generators are available to serve the 8 lift stations. 5. Pump Stations Inspected. The following pump stations were visited and inspected. a) Walker Wood Lift Station • (2) submersible pumps • At the time of the inspection, the wet well and float controls were clean and clear of excessive grease and debris. • High-Level Alarm (audible/visual) was tested and was functional during the inspection. • Omni-site telemetry was operational and high-level alarm testing was received through a smart phone by text and a phone call. • Lift station will facilitate the connection of a portable generator. • An upstream gravity line manhole was inspected and found to be free of blockage and greasedebris accumulation. b) East Church Lift Station • (2) submersible pumps 6 At the time of the inspection, the wet well and float controls were clean and clear of excessive grease and debris. • High-Level Alarm (audible.'visual) was tested and was functional during the inspection. • Omni-site telemetry was operational and high-level alarm testing was received through a smart phone by text and a phone call. • Lift station will facilitate the connection of a portable generator. c) Club House Lift Station • (2) submersible pumps • At the time of the inspection, the wet well and float controls were clean and clear of excessive grease and debris. Page 2 of 5 Docusign Envelope ID:C90047FA-7973-4C80-A486-67484CA08CFB Pennittee,WQCS00293 July 19,2024 • High-Level Alarm (audible.'visual) was tested and was functional during the inspection. • Omni-site telemetry was operational and high-level alarm testing was received through a smart phone by text and a phone call. • Lift station will facilitate the connection of a portable generator. • Lift station has a by-pass pumping connection for a portable pump. d) South Entrance Lift Station • (2) submersible pumps • At the time of the inspection, the wet well and float controls were clean and clear of excessive grease and debris. • High-Level Alarm (audible.'visual) was tested and was functional during the inspection. • Omni-site telemetry was operational and high-level alarm testing was received through a smart phone by text and a phone call. • Lift station will facilitate the connection of a portable generator. e) 10424 Stone Road Simplex Lift Station • (1) submersible grinder pumps • Wet-well and control cabinet are located beside the house and was accessible. • Simplex system included a high level audible-visual alann. PERMITTEE is responsible for maintenance and repair of simplex pump systems. • Homeowners have appropriate contact information to report system problems or alarm conditions. f) Force Main Air Release Valve (ARV)— Morehead Drive • ARV was inspected and found to be operational and the isolation valve in the open position. No evidence of leaks was found during the inspection. 6. Pump Station Signage. Each pump station has signage clearly and conspicuously posted that identifies the pump station, provides an emergency 24-hour contact telephone number(s), and provides instructions for notification if the visual alarm illuminates and:'or the audible alarm sounds, or if an emergency is apparent. 7. Pump Station Restricted Access. The pump station sites, equipment and components were observed to have restricted access. All wet-well and control panels were pad locked and secured. 8. Pump Stations Automatic Polling Feature. The pump stations are equipped with Omni- Site telemetry'SCADA that allow the PERMITTEE routine contact with the pump station from an electronic device(laptop phone) to check the operational status of the communication system. During the inspection, the Omni-Site telcmetryfSCADA acknowledged the alarms when the high-water float was activated. Page 3 of 5 Docusign Envelope ID:C90047FA-7973-4C80-A4B6-67484CA08CFB Permittee,WQCS00293 July 18,2024 9. Pump Station High Water Alarms. The pump stations are equipped with audible and visual high water alarms. During the inspection, these alarms functioned properly. The operator received the high-water alarm remotely to their smart phone. 10. Pump Station Inspection Program. The PERMITTEE has developed and implements a weekly routine inspection of each pump station that includes the following maintenance activities: cleaning and removing debris from the pump station area and wet well; inspecting all valves; inspecting pumps and other mechanical equipment; and verifying the proper operation of the alarms, telemetry system and auxiliary equipment. The inspector reviewed the inspection logs of the pump stations visited and observed adequate entries of the date and time of the operator's inspection, observations made, and any maintenance, repairs, or corrective actions taken. Service Link work order system is utilized for managing and recording system operation and maintenance tasks. 11. Designated Operators. The PERMITTEE wastewater collection system is classified as a Class-2 system. The Division of Water Resources does not currently have a designated certified Operator in Responsible Charge (ORC) listed for the Governor's Club wastewater collection system. Seven (7)back-up ORCs are on record that include Larry Wayne Alford, Alan Drew Bailey, Steven Glen Johnson, Kenneth Leslie Langston, Calvin Maurice Leach, Christopher A. McDonald, and Aldon Ratliff. In accordance with Section 11 (L)of your permit, "Upon classification of the collection st�steni by the Water Polhition Control System Operators Certification Commission (WPCSOCQ. the Pernittee shall designate and employ a certff ed operator to be in responsible charge (ORC) and one or more certified operator(s) to be back-tip ORC(s)of the facilities in accordance with 15A NCAC 8G.0204". Provide the NC Division of Water Resources a completed ORC designation form (attached) naming a properly certified operator as ORC for the Governor's Club Wastewater Collection System and your permit. The Governor's Club collection system is non-compliant without a properly designated ORC. 12. Cleaning Sewer Lines.The PERMITTEE has developed and implements a program for cleaning the sewer lines. As required by Section 11.8 of the subject permit, at least 100'o of the wastewater collection system should be cleaned each year. Preventative cleaning is not required for sewer lines less than five years old, unless an inspection reveals the need for cleaning. Mr. Bishop provided a record during the inspection that approximately 700 feet or 17-percent of sewer line were cleaned in calendar year 2023. 13. Spill Response Action Plan. The PERMITTEE has developed and maintains a Spill Response Action Plan that includes 24-hour contact numbers, response time (within 60 minutes), equipment list and spare parts inventory, access to cleaning equipment, access to construction crews, sources of emergency funds, site sanitation and cleanup materials, and post-SSO assessment. The Pennittee utilizes contracted services to assist in sewer spill cleanup and major infrastructure repair. 14. SSO Records. The PERMITTEE has maintained adequate records pertaining to SSOs and sewer complaints for the three-year period ending May 2024. The last reportable SSO occurred on April 24, 2024. According to Mr. Bishop, no non-reportable SSOs Page 4 of 5 Docusign Envelope ID:C90047FA-7973-4C80-A4B6-67484CA08CFB Permittee, WQCS00293 July 18,2024 occurred for the last three years. The inspector reminded Mr. Bishop that all SSOs whether reportable on non-reportable should be documented and recorded as required in Section III (2.)of the permit. 15. Comprehensive Sewer Map. The PERMITTEE maintains an up-to-date comprehensive GIS based map of its sewer collection system. The map includes pipe size, pipe material, pipe location, Flow direction, approximate pipe age, number of active service taps, and each pump station identification, location and capacity. 16. Inspection of High Priority Lines. The PERMITTEE does not list in the permit or have high priority lines associated with their system. According to Mr. Bishop, the system does not include any aerial lines, siphons, or pipelines that run perpendicular to streams that are or may be affected by stream erosion at the time of the inspection. Please provide this office with a written response to items 11 above no later than September 30,2024. The overall condition of the collection system was compliant with the wastewater collection system permit requirements observed on the day of the inspection; however, the system is non-compliant without a designated ORC. Please take note that your collection system permit expires January 31, 2025. Section VI (6.) of your permit requires "The permittee shall file an application for renewal of this permit at least six months prior to the expiration date...". If you have questions or comments about this inspection or the requirements to take corrective action if applicable, please contact Donald Smith at 919-791-4234. Sincerely, [U DacuSigned by a v -SS& f. hattn.tcd 82916E6AS32144F Vanessa E. Manuel, Assistant Regional Supervisor Water Quality Regional Operations Section Raleigh Regional Office Division of Water Resources, NCDEQ Attachment(s): Collection System Inspection Report ORC Designation Form Cc: Laserfiche Page 5 of 5 Docusign Envelope ID:C90047FA-79734C80-A4B6-67484CAOBCFB Compliance Inspection Report Permit:WOCS00293 Effective: 05,`24,'18 Expiration: 01/31/25 Owner: Aqua North Carolina Inc SOC: Effective: Expiration: Facility: Govenors Club Collection System County: Chatham PO Box 2615 Region: Raleigh Chapel Hill NC 27515 Contact Person:Amanda Berger Title: Compliance Manager Phone:919-653-6965 Directions to Facility: System Classifications: CS2, Primary ORC: Roy David Lyons Certification: 1005505 Phone:919-560-5053 Secondary ORC(s): On-Site Representative(s): Related Permits: W00000088 Aqua North Carolina Inc-Governors Club WWTP Inspection Date: C7/10/2024 Entry Time 09:1OAM Exit Time: 12 OOPM Primary Inspector:Donald Smith ozusianedby; 7/18/2024 Phone: 919-791-4234 Secondary Inspector(s): [V�"U 5" 2ED5247FAB47A Myles Parker Docusignedby: 7/19/2024 f at�cr t yl Reason for Inspection: Routine 7' Inspection Type: Collection System Inspect Non Sampling E-PMEWEWIC417 Permit Inspection Type: Collection system management and operation Facility Status: ❑ Compliant E Not Compliant Question Areas: Miscellaneous Questions General Sewer&FOG Ordinances Capital Improvement Plan Map Reporting Requirements Inspections Spill Response Plan Spills Lines Manholes Pump Stations (See attachment summary) Page 1 of 7 Docusign Envelope ID:C90047FA-7973-4C80-A466-67484CA08CFB Permit: WOCS00293 Owner-Facility:Aqua North Carolina Inc Inspection Date: 07/10/2024 Inspection Type:Collection System Inspect Non Sampling Reason for Visit: Routine Inspection Summary: Overall collection system was compliant with observations made during the inspection. ORC designation is required and needed. Collection system program is non-compliant without a designated ORC. Page 2 of 7 Docusign Envelope ID:C90047FA-7973-4C80-A4B6-67484CA08CFB Permit: WOCS00293 Owner-Facility:Aqua North Carolina Inc Inspection Date: 07/10/2024 Inspection Type :Collection System Inspect Non Sampling Reason for Visit: Routine General Yes No NA NE Is there a properly designated primary ORC and at least one back-up of proper grade? ❑ 0 ❑ ❑ Are logs being reviewed by the system management or owner on a regular basis? M ❑ ❑ ❑ #What is that frequency? Weekly #Are there any issues being addressed currently or any in the planning stages? M ❑ ❑ ❑ Is there a specific pump failure plan available for all pump stations? M ❑ ❑ ❑ Does plan indicate if pump parts/new pumps are in spare parts/equipment inventory? ❑ ❑ ❑ Are new/significantly upgraded pump stations equipped with anti-corrosion materials? ❑ ❑ ❑ Does the permittee have a copy of their permit? 0 ❑ ❑ ❑ #Is permit expiring within the next 6 months? 0 ❑ ❑ ❑ If Yes,has the Permittee applied for renewal? ❑ 0 ❑ ❑ Comment: No ORC listed with DWR. Sending a DWR ORC Designation Form. Mr. Bishop indicated that Ashley Kilinger will be designated ORC and will complete and submit form.Chemical degreaser is being fed to help clean force mains. Permit expires January 31, 2025, reminded Mr. Bishop of 6-month application for renewal sumittal. Sewer and FOG Ordinances Yes No NA NE Is Sewer Use Ordinance(SUO)or other Legal Authority available? 00 ❑ ❑ Does it appear that the Sewer Use Ordinance is enforced? No ❑ ❑ Is there a Grease Control Program that legally requires grease control devices? M ❑ ❑ ❑ What is the standard grease trap cleaning requirement in the FOG ordinance? Quarterly Is Grease Control Program enforced via periodic inspections+records review? 0 ❑ ❑ ❑ Is action taken against violators? Cl 0 ❑ ❑ #Have satellite systems adopted an equivalent or more stringent ordinance? M ❑ ❑ ❑ Is grease/sewer education program documented with req'd customer distribution? so ❑ ❑ #Are other types of education tools used like websites, booths, special meetings. etc? ❑ M ❑ ❑ If Yes,what are they?(This can reduce mailing to annual.) Comment: SUO is managed at Corporate level. No enforcement has taken place, clubhouse compliant. Caaital Improvement Plan Yes No NA NE Has a Capital(CIP)or System Improvement Plan been developed and adopted? ❑ ❑ 0 ❑ Is it designated for wastewater only or does it have a dedicated section? ❑ ❑ 0 ❑ Does CIP cover three to five year period of earmarked improvements? ❑ ❑ M ❑ Does CIP include description of project area? ❑ ❑ M ❑ Does CIP include description of existing facilities? ❑ ❑ 0 ❑ Does CIP include known deficiencies? ❑ ❑ M ❑ Does CIP include forecasted future needs? ❑ ❑ M ❑ Page 3 of 7 aoc.js gn Envelope ID:C90047FA-7973-4C80-A466-67484CA08CFB Permit: WQCS00293 Owner-Facility:Aqua North Carolina Inc Inspection Date: 07/10/2024 Inspection Type:Collection System Inspect Non Sampling Reason for Visit: Routine Comment: System improvement is managed under regulations through the NC Utilities Commission. Permittee manages improvements and repairs through annual budget planning. Map Yes No NA NE Is there a overall sewer system map? 0 ❑ ❑ ❑ Does the map include: Pipe Type(GS/FM) 0 ❑ ❑ ❑ Pipe sizes 0 0110 Pipe materials(PVC,DIP,etc) 0 ❑ ❑ ❑ Pipe location 0000 Flow direction 0 ❑ ❑ ❑ Approximate pipe age M ❑ ❑ ❑ Pump station ID, location and capacity 0 ❑ ❑ ❑ # Force main air release valve location&type 0 Cl ❑ ❑ # Location of satellite connections M ❑ ❑ ❑ Is the map being updated for changes/additions within 1 year of activation? 0 ❑ ❑ ❑ Comment: Reporting Requirements Yes No NA NE #Have there been any sewer spills in the past 3 years? 0 ❑ ❑ ❑ If Yes,were they reported to the Division if meeting the reportable criteria? M ❑ ❑ ❑ If applicable, is there documentation of press releases and public notices issued? ❑ ❑ 0 ❑ Is an Annual Wastewater Performance Report being filed with the Division, if required? ❑ ❑ 0 ❑ Is the report being made available to all its sewer customers? ❑ ❑ 0 ❑ # How is it being made available? Comment: System is less than 200,000 gpd average. Inspections Yes No NA NE Are adequate maintenance records maintained? 0 ❑ ❑ ❑ Are pump stations being inspected at the required frequency? 0 ❑ ❑ ❑ #Is at least one complete functionality test conducted weekly per pump station? 0 ❑ ❑ ❑ Is there a system or plan in place to observe the entire system annually? 0 ❑ ❑ Cl Is the annual inspection documented? 0 ❑ ❑ ❑ #Does the system have any high-priority lines/locations? ❑ M ❑ ❑ Are inspections of HPL documented at least every 6 months? ❑ ❑ 0 ❑ Are new lines being added to the HPL list when found or created? ❑ ❑ ❑ Comment: No high priority lines listed in the pernit or known by the operator/permittee. Spill Response Action Plan Yes No NA NE Page 4 of 7 Docusign Envelope ID:C90047FA-79734C80-A466-67484CA08CFB Permit: WOCS00293 Owner-Facility:Aqua North Carolina Inc Inspection Date: 0711012024 Inspection Type:Collection System Inspect Non Sampl ng Reason for Visit: Routine Is a Spill Response Action Plan available? M ❑ ❑ ❑ Is a Spill Response Action Plan available for all personnel? 0 ❑ ❑ ❑ Does the plan include: 24-hour contact numbers N ❑ ❑ ❑ Response time ■ ❑ ❑ ❑ Equipment list and spare parts inventory M ❑ ❑ ❑ Access to cleaning equipment 0 ❑ ❑ ❑ Access to construction crews,contractors,and/or engineers 0 ❑ ❑ ❑ Source of emergency funds 0 ❑ ❑ ❑ Site sanitation and cleanup materials 0 ❑ ❑ ❑ Post-overflow/spill assessment 0 ❑ ❑ ❑ Does the Permittee appear to respond within 2 hours of first knowledge of a spill? 0 ❑ ❑ ❑ Comment: 60 minute response time illIRLS Yes No NA NE Is system free of known points of bypass? so ❑ ❑ If No,describe type of bypass and location Are all spills or sewer related issues/complaints documented? ■ ❑ ❑ ❑ #Are there repeated overflows/problems(2 or more in 12 months)at same location? E ❑ ❑ ❑ #If Yes,is there a corrective action plan? E ❑ ❑ ❑ Comment: Two spills were associated with one location with the same event. Lines/Right-of-Ways/Aerial Lines Yes No NA NE Please list the Lines/Right of Ways/Aerial Lines Inspected: Gravity and force main lines associated with roadways and maintianed right-of-ways. Observed maintained shoulders and medians throught neighborhood/service area. Are right-of-ways/easements maintained for full width for access by staff/equipment? E ❑ ❑ ❑ If No,give details on temporary access: Is maintenance documented? ❑ ❑ ❑ Are gravity sewer cleaning records available? E ❑ ❑ ❑ Has at least 10%of lines older than 5 yrs been cleaned annually? E ❑ ❑ ❑ Were all areas/lines inspected free of issues? N ❑ ❑ ❑ Comment: Majority of right-of-way maintenance conducted by landscaping maintenance or homeowners. Manholes Yes No NA NE Please list the Manholes Inspected: Inspected manhole at Walker Falls Road upstream of Walker Wood Pump Station. Are manholes accessible? ❑ ❑ ❑ #Are manhole covers/vents above grade? E ❑ ❑ ❑ Are manholes free of visible signs of overflow? N ❑ ❑ ❑ Page 5 of 7 Docusign Envelope ID: C90047FA-7973-4C80-A4B6-67484CAi.8C=B Permit: WQCS00293 Owner-Facility:Aqua North Carolina Inc Inspection Date: 07/10/2024 Inspection Type Collection System inspect Non Sampling Reason for Visit: Routine Are manholes free of sinkholes and depressions? 0 ❑ ❑ ❑ Are manhole covers present? M ❑ ❑ ❑ #Are manholes properly seated? 0 ❑ ❑ ❑ #Are manholes in good condition? 0 ❑ ❑ ❑ #Are inverts in good condition? 0 ❑ ❑ Cl Is flow unrestricted in manholes? 0 ❑ ❑ ❑ Are manholes free of excessive amounts of grease? M ❑ ❑ ❑ Are manholes free of excessive roots? 0 ❑ ❑ ❑ Are manholes free of excessive sand? M ❑ ❑ ❑ Are manhole vents screened? ❑ ❑ M ❑ Are vents free of submergence? 0 Cl ❑ ❑ Are manholes free of bypass structures or pipes? M ❑ ❑ ❑ Comment: Very small gravity service area -4,023 feet of gravity sewer in the system. Pump Stations Yes No NA NE Please list the Pump Stations Inspected: Walker Woods, East Church, Clubhouse,South Enterance #Number of duplex or larger pump stations in system #Number of vacuum stations in system #Number of simplex pump stations in system #Number of simplex pump stations in system serving more than one building 0 How many pump/vacuum stations have: # A two-way"auto polling"communication system(SCADA)installed? 8 # A simple one-way telemetry/communication system(auto-dialer)installed? 0 For pump stations inspected: Are they secure with restricted access? 0111111 Were they free of by-pass structures/pipes? 0 ❑ ❑ ❑ Were wet wells free of excessive grease/debris? M ❑ ❑ ❑ # Do they all have telemetry installed? 0 ❑ ❑ ❑ Is the communication system functional? M ❑ ❑ ❑ Is a 24-hour notification sign posted? M ❑ ❑ ❑ Does the sign include: Owner Name? ❑ ❑ ❑ Pump station identifier? ❑ ❑ ❑ # Address? M ❑ ❑ ❑ Instructions for notification? 0 ❑ ❑ ❑ 24-hour emergency contact numbers? 0 ❑ ❑ ❑ Page 6 of 7 Docusign Envelope 10:C90047FA-7973-4C80-A4B6-67484CAOBCFB Permit: WQCS00293 Owner-Facility:Aqua North Carolina Inc Inspection Date: 07/10/2024 Inspection Type:Collection System Inspect Non Sampling Reason for Visit: Routine Are audio and visual alarms present? 0 Cl ❑ ❑ Are audio and visual alarms operable? M ❑ ❑ ❑ #Is there a backup generator or bypass pump connected? ❑ M ❑ ❑ If tested during inspection,did it function properly? ❑ ❑ 0 ❑ Is the back-up system tested at least bi-annually under normal operating conditions? M ❑ ❑ ❑ #Does it have a dedicated connection for a portable generator? 0 ❑ ❑ ❑ #Is the owner relying on portable units in the event of a power outage? 0 ❑ ❑ ❑ #If Yes, is there a distribution plan? 0 ❑ ❑ ❑ If Yes,what resources(Units/StaffAtehicies/etc)are included in Plan? 3 mobile generators available.Generators would be rotated where needed to maintain system.With homes being on simplex systems most power outages result in lower flows to the duplex lift stations.Contracted services are also available if needed for generators or pump and haul operations. #Does Permittee have the approved percentage of replacement simplex pumps? M ❑ ❑ ❑ Is recordkeeping of pump station inspection and maintenance program adequate? M ❑ ❑ ❑ Do pump station logs include at a minimum: Inside and outside cleaning and debris removal? 0 ❑ ❑ ❑ Inspecting and exercising all valves? 0 ❑ ❑ ❑ Inspecting and lubricating pumps and other equipment? 0 Cl ❑ ❑ Inspecting alarms,telemetry and auxiliary equipment? 0 ❑ ❑ ❑ Comment: Page 7 of 7 Docusign Envelope ID:C90047FA-7973-4C80-A4B6-67484CA08CFB Water Pollution Control System OPERATOR IN RESPONSIBLE CHARGE (ORC) Designation Form NCAC 15A 8G .0201 TAB to Navigate Farm Facility Name: Permit# Facility Type/Classification: Select Facility Grade: Select SUBMIT A SEPARATE FORM FOR EACH CLASSIFICATION Permittee Owner/Officer Name: Email Address: Permittee Signature: Date: ORC Full Name: Work Phone: Email Address: Certificate Type: Select Certificate Grade: Select Certificate#: Signature: Effective Date: certify that!agree to my designation as the Operator in Responsible Charge for the facility noted. I understand and will abide by the rules and regulations pertaining to the responsibilities of the ORC as set forth in ISA NCAC 08G.0104 and failing to do so can result in Disciplinary Actions by the WPCSOCC" Backup ORC Full Name: Work Phone: Certificate Type: Select Certificate Grade: Select Certificate#: Signature: Effective Date: "l certify that I agree to my designation as the Operator in Responsible Charge for the facility noted. l understand and►tell abide by the rules and regulations pertaining to the responsibilities of the ORC as set forth in 1 SA NCAC 08G.0204 and failing to do so can result in Disciplinary Actions by the WPCSOCC" Backup ORC Full Name: Work Phone: Certificate Type: Select Certificate Grade: Select Certificate#: Signature: Effective Date: "7 certify that I agree to my designation as the Operator in Responsible Charge for the facility noted. 1 understand and will abide by the rules and regulations pertaining to the responsibilities of the ORC as set forth in I5A NCAC 08G.0204 and foiling to do so con result in Disciplinary Actions by the WPCSOCC" Email this form to:certadmin@deq.nc.gov AND Send to your DEQ Regional Office(send to your contact or find emails here:www.deq.nc.gov/about/contact/regional-offices or fax using this drop down list: Choose DWR Regional Office that has coverage of this facility. Use the 2nd page only if you need to list additional Backups. Revised 0212024 aocusign Envelope ID.C90047FA-7973-4C80-A4B6-67484CA08CFB Facility Name: Permit#: Backup ORC Full Name: Work Phone: Certificate Type: Select Certificate Grade: Select Certificate#: Signature: Effective Date: "l certify that l agree to my designation as the Operator in Responsible Charge for the facility noted. l understand and will abide by the rules and regulations pertaining to the responsibilities of the ORC as set forth in ISA NCAC 08G 0204 and failing to do so can result in Disciplinary Actions by the WPCSOCC" Backup ORC Full Name: Work Phone: Certificate Type: Select Certificate Grade: Select Certificate#: Signature: Effective Date: "I certify that 1 agree to my designation as the Operator in Responstbh-Charge for the facrlity noted i understand and will abide by the rules and regulations pertaining to the responsibilities of the ORC asset forth in 15A NCAC 08G.0204 and failing to do so can result in Duciphnory Actions by the WPCSOCC" Backup ORC Full Name: Work Phone: Certificate Type: Select Certificate Grade: Select Certificate#: Signature: __.. Effective Date: certify that l agree to my designation as the Operator in Responsible Charge for the facility noted 1 understand and will abide by the rules and regulations pertaining to the responsibilities of the ORC as set forth in 15A NCAC 08G.0204 and failing to do so can result in Disciplinary Actions by the WPCSOCC- Backup ORC Full Name: Work Phone: Certificate Type: Select Certificate Grade: Select Certificate#: Signature: Effective Date: "t certify that 1 agree to my designation as the Operator in Responsible Charge for the facility noted. 1 understand and will abide by the rules and regulations pertaining to the responsibilities of the ORC asset forth in 15A NCAC 08G.0204 and failing to do so can result in Disciplinary Actions by the WPCSOCC" Revised 02/2024