HomeMy WebLinkAboutNCG500272_Weyerhaeuser_Nr_Company_CEI_Letter_20240702ROY COOPER
Governor
ELIZABETH S. BISER
Secretary
RICHARD E. ROGERS, JR.
Director
Weyerhaeuser Nr Company
Attn: Ross Gardner, Mill Manager
524 Pride Way
Elkin, NC 28621-8517
NORTH CAROLINA
Environmental Quality
July 2, 2024
SUBJECT: Compliance Evaluation Inspection
Weyerhaeuser Nr Company Elkin Facility
General NPDES Discharge Permit Number NCG500000
Certificate of Coverage Number NCG500272
Surry County
Dear Mr. Gardner:
On June 19th, 2024, Ron Boone and Michael Gearran of the Winston-Salem Regional Office of
the NC Division of Water Resources conducted a compliance evaluation inspection at the
Weyerhaeuser Nr Company Elkin facility. The inspection reviewed Weyerhaeuser's compliance
status with regards to their certificate of coverage, NCG500272, under NC General NPDES
Discharge permit NCG500000. The assistance of Dennis Atkinson and Savannah Dibby was greatly
appreciated.
It was determined during the inspection that Weyerhaeuser is non -compliant with the permit for
the following:
AREA OF NON-COMPLIANCE
Analyzing Total Residual Chlorine (TRC) in effluent without the proper field laboratory
certification.
Please inform Mr. Boone of your plans to rectify the violation above, i.e. either obtaining a field
lab certification from the state or having your contract lab, who has its own certification for
running TRC, take the samples from this point forward.
North Carolina Department of Environmental Quality I Division of Water Resources
Winston-Salem Regional Office 1 450 W. Hanes Mill Rd, Suite 300 I Winston-Salem, North Carolina 27105
NoanicaaouNn
336.776.9800
Please feel free to contact Mr. Boone at any time by phone at 336-776-9690, or by email at
ron.boone@deq.nc.gov, if you have any questions or concerns about this letter or its
requirements.
Attachments:
Water Compliance Inspection Report
NORTH CAROLINAD E Q
oeo+ro�.m m F,mro���w n�si�
Sincerely,
DocuSigned by:
OD2D3CE3F167456...
Jennifer F. Graznak, Assistant Regional Supervisor
Water Quality Regional Operations Section
Winston-Salem Regional Office
Division of Water Resources, NCDEQ
North Carolina Department of Environmental Quality I Division of Water Resources
Winston-Salem Regional Office 1 450 W. Hanes Mill Rd, Suite 300 1 Winston-Salem, North Carolina 27105
336.776.9800
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 2 u 3 I NCG500272 111 121 24/06/19 I17 18 I C I 19 I s I 20L]
21111I I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
I 72 I ni I 73 � I 74 79 I I I I I I I80
70 I I 71 I LL -1 I I
LJ
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
12:45PM 24/06/19
20/12/18
Elkin facility
524 Pride Way
Exit Time/Date
Permit Expiration Date
Elkin NC 28621
01:45PM 24/06/19
25/11/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Dennis Atkinson,524 Pride Way Elkin NC 286218517//336-244-7911/3365266437
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Ron Boone Docusigned by: DWR/WSRO WQ/336-776-9690/
Michael Gearrenosti�� �oa.�& DWR/WSRO WQ/336-776-9800/ 7/3/2024
B20F8DD5F2A3460...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
FDocusigned by: DWR/WSRO 336-776-9695 7/3/2024
�. ✓J
6
EPA Form 3 65 0ONRevTNJ� revious editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NCG500272 I11 12I 24/06/19 117 18 ici cJ
(Cont.)
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On June 19th, 2024, Ron Boone and Michael Gearran, of the Winston-Salem Regional Office of the
NC Division of Water Resources, conducted a compliance evaluation inspection at the Weyerhaeuser
Nr Company Elkin facility. The inspection reviewed Weyerhaeuser's compliance status with regards to
their discharge certificate of coverage, NCG500272, under NC General NPDES Discharge permit
NCG500000. The assistance of Dennis Atkinson and Savannah Dibby was greatly appreciated. It was
determined, during the inspection, that Weyerhaeuser is non -compliant with the permit. Inspection
findings are summarized below.
The facility discharges cooling tower blowdown at a rate of 200 gallons per hour, or 3.3 gallons per
minute. Normally, the blowdown occurs automatically and the wastewater goes to the facility's
wastewater treatment system. There are times, however, when the operators manually initiate the
blowdown process. In this case the wastewater comes out of a hose at the base of the cooling towers
and flows onto the asphalt. It then travels across the ground about 250 feet where it then flows into
the first of two in -series stormwater ponds. The stormwater ponds discharge directly into the Yadkin
River. Flow volume is estimated based on the typical amount of wastewater produced by a normal
blowdown cycle.
The facility uses municipal water from the Town of Elkin for its cooling towers. As required by the
permit, Mr. Atkinson measures Total Residual Chlorine (TRC) at the discharge point of the final
stormwater pond. However, Weyerhaeuser does not have field parameter certification for TRC. You
must have a certified lab test TRC within 15 minutes of sample collection for the results to be
considered valid. Mr. Atkinson stated they are currently using Waypoint Labs, out of Charlotte, NC, to
run the Chemical Oxygen Demand (COD) samples so he will also have them run the TRC samples.
Alternatively, you may apply for certification to run this test yourself. Mr. Boone has provided Mr.
Atkinson with the information needed to apply for laboratory certification to test the TRC.
Mr. Atkinson provided sampling results dating back to 2012 and there are no exceedances of any of
the required parameter limits.
AREAS OF NON-COMPLIANCE
- Testing for TRC in the effluent without the proper laboratory certification.
Please inform Mr. Boone of your plans to rectify the violation above, i.e. either by obtaining a field lab
certification from the state or having your contract lab, who has its own certification for running TRC,
take the samples from this point forward.
Please feel free to contact Mr. Boone at any time by phone at 336-776-9690, or by email at
ron.boone@deq.nc.gov, if you have any questions or concerns about this letter or its requirements.
Page#
Permit: NCG500272
Inspection Date: 06/19/2024
Owner -Facility: Elkin facility
Inspection Type: Compliance Evaluation
Permit
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Comment: Please refer to the inspection summary section of this report.
Yes No NA NE
❑ ❑ ■ ❑
■ ❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
■ ❑ ❑ ❑
Page# 3