July 9, 2024
SUBJECT: Compliance Evaluation Inspections
Community Water Treatment Plants Owned by Aqua North Carolina, Inc.,
& Operated Under General NPDES Permit #: NCG590000
Surry County
On June 20th, 2024, Ron Boone and Michael Gearran, of the Winston-Salem Regional Office of
the NC Division of Water Resources, conducted compliance evaluation inspections at the
following facilities owned and operated by Aqua North Carolina, Inc. The assistance of the
Operator in Responsible Charge (ORC), Billy Young, was greatly appreciated. All seven facilities
are located in Surry County. The inspections were conducted in the following order:
Facility Name
Discharge Certificate of
Coverage Number
Reeves Woods Subdivision Well #2
NCG590031
Bannertown Hills Subdivision — Well #2
NCG590027
Hillcrest Subdivision — Well #3
NCG590026
The Hollows Subdivision
NCG590030
Windgate Subdivision —#1
NCG590025
Snow Hill Subdivision
NCG590029
Mitchell Bluff Subdivision Well #1
NCG590024
Several compliance issues were noted at each facility as detailed below:
1. Reeves Woods — NCG590031:
a. Keep dechlorination tablets in tubes at all times;
b. Keep copy of field lab certification on site at all times;
c. Keep copy of the plant's certificate of coverage on site at all times;
d. Repair the broken dechlor tube; and,
e. Outfall location unknown.
North Carolina Department of Environmental Quality I Division of Water Resources
Winston-Salem Regional Office 1 450 W. Hanes Mill Rd, Suite 300 I Winston-Salem, North Carolina 27105
NoanicaaouNn
oep.m.m or em�nmen� Qualm,
336.776.9800
2. Bannertown Hills — NCG590027:
a. Keep copy of field lab certification on site at all times; and,
b. Keep copy of the plant's certificate of coverage on site at all times.
3. Hillcrest Subdivision — NCG590026:
a. Keep copy of field lab certification on site at all times; and,
b. Keep copy of the plant's certificate of coverage on site at all times.
4. The Hollows — NCG590030:
a. Keep dechlorination tablets in tubes at all times;
b. Keep copy of field lab certification on site at all times;
c. Keep copy of the plant's certificate of coverage on site at all times;
d. Repair the broken dechlor tubes; and,
e. Outfall location unknown.
S. Windgate — NCG590025:
a. Keep dechlorination tablets in tubes at all times;
b. Keep copy of field lab certification on site at all times; and,
c. Keep copy of the plant's certificate of coverage on site at all times;
6. Snow Hill — NCG590029:
a. Keep copy of field lab certification on site at all times;
b. Keep copy of the plant's certificate of coverage on site at all times; and,
c. Outfall location unknown.
7. Mitchell Bluff — NCG590024:
a. Keep copy of field lab certification on site at all times;
b. Keep copy of the plant's certificate of coverage on site at all times; and,
c. Outfall location unknown.
NORTH CAROLINAD � ��
oeo+ro�.m m F,mro���w n�si�
North Carolina Department of Environmental Quality I Division of Water Resources
Winston-Salem Regional Office 1 450 W. Hanes Mill Rd, Suite 300 1 Winston-Salem, North Carolina 27105
336.776.9800
The issues noted above represent non-compliance with the NCG590000 general permit and
should be corrected as soon as possible. Please contact Mr. Boone by phone at 336-776-9690 or
by email at ron.boone@deg.ncgov if you have any questions or concerns about the inspections,
this letter or its requirements.
Sincerely,
DocuSigned by:
OD2D3CE3F1 B7456...
Jennifer F. Graznak, Assistant Regional Supervisor
Water Quality Regional Operations Section
Winston-Salem Regional Office
Division of Water Resources, NCDEQ
Attachments:
1. Reeves Woods Subdivision Well #2, NCG590031, Water Compliance Inspection Report
2. Bannertown Hills Subdivision — Well #2, NCG590027, Water Compliance Inspection Report
3. Hillcrest Subdivision — Well #3, NCG590026, Water Compliance Inspection Report
4. The Hollows Subdivision, NCG590030, Water Compliance Inspection Report
5. Windgate Subdivision — #1, NCG590025, Water Compliance Inspection Report
6. Snow Hill Subdivision, NCG590029, Water Compliance Inspection Report
7. Mitchell Bluff Subdivision Well #1, NCG590024, Water Compliance Inspection Report
NORTH CAROLINAD E Q
oeo+ro�.m m F,mro���w n�si�
North Carolina Department of Environmental Quality I Division of Water Resources
Winston-Salem Regional Office 1 450 W. Hanes Mill Rd, Suite 300 1 Winston-Salem, North Carolina 27105
336.776.9800
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NCG590025 111 121 24/06/20 I17 18 I C I 19 I s I 20L]
21111I I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
I 72 I ni I 71 I 74 79 I I I I I I I80
701 I 71 I LL -1 I I
LJ
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES Dermit Number)
12:OOPM 24/06/20
19/10/01
Windgate Subdivision - #1
266 Simpson Rd
Exit Time/Date
Permit Expiration Date
Dobson NC 27017
12:15PM 24/06/20
24/07/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Not Required/ORC/919-707-9190/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Gary Moseley,4163 Sinclair St Denver NC 280376447//704-489-9404/7044899409
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Facility Site Review Effluent/Receiving Wate Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Ron Boone Docusigned by: DWR/WSRO WQ/336-776-9690/ 7/8/2024
Michael Gearrenosti�� Baar�� DWR/WSRO WQ/336-776-9800/
B20F8DD5F2A3460...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
Docusigned by:
'6mt-�DwR/WSRo 336-776-9695 7/9/2024--4-
"- fi?d j�167456 .
EPA Form 3560-3 Rev �J revious editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NCG590025 I11 12I 24/06/20 117 18 i c i
(Cont.)
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On June 20th, 2024, Ron Boone and Michael Gearran of the Winston-Salem Regional Office of the
NC Division of Water Resources conducted a compliance evaluation inspection of the Windgate
Subdivision - #1 and its discharge certificate of coverage, NCG590030, under the General NPDES
discharge permit NCG590000. The assistance and cooperation of the operator, Billy Young, was
greatly appreciated.
The inspection findings are detailed below:
a. Flow is calculated using flow restrictors (flow rate * time);
b. Facility has five green sand filters;
c. Each filter backwashes separately;
d. Backwash occurs once for every set amount of treated water, but will backwash every seven days
regardless of how much has been treated;
e. Sodium hypochlorite used for disinfection;
f. Sodium sulfite tablets used for dechlorination;
g. Water operator is responsible for adding dechlorination tablets because he is at the facility
much more frequently than the wastewater operator;
h. Four of four dechlorination tubes were in use at the time of the inspection;
i. Dechlorination tubes were nearly empty at the time of the inspection — the wastewater operator
returned to the facility post -inspection and added more tablets;
j. Total Residual Chlorine (TRC) samples collected from discharge of dechlorination contact
chamber;
k. Location of outfall is known;
I. Operations & Maintenance (O&M) and Visitation Logs were readily available, complete and
current;
m. Laboratory records and DMR records were reviewed post -inspection and no errors or
discrepancies were noted;
n. Facility uses Aqua's field laboratory certification #5035;
o. Field lab certification not on site;
p. Certificate of coverage not on site; and,
q. Site well secured and clean.
a. Keep dechlorination tablets in tubes at all times;
b. Keep copy of field lab certification on site at all times; and,
c. Keep copy of the plant's certificate of coverage on site at all times;
Please feel free to contact Mr. Boone at any time by phone at 336-776-9690, or by email at
ron.boone@deq.nc.gov, if you have any questions or concerns about this letter or the inspection.
Page#
Permit: NCG590025 Owner -Facility: windgate Subdivision - #1
Inspection Date: 06/20/2024 Inspection Type: Compliance Evaluation
Permit
Yes
No
NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
■
❑
application?
Is the facility as described in the permit?
■
❑
❑
❑
# Are there any special conditions for the permit?
❑
■
❑
❑
Is access to the plant site restricted to the general public?
■
❑
❑
❑
Is the inspector granted access to all areas for inspection?
■
❑
❑
❑
Comment: Please refer to the inspection summary section of this report.
Record Keeping
Yes
No
NA
NE
Are records kept and maintained as required by the permit?
❑
■
❑
❑
Is all required information readily available, complete and current?
❑
■
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
■
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
■
❑
❑
❑
Is the chain -of -custody complete?
■
❑
❑
❑
Dates, times and location of sampling
■
Name of individual performing the sampling
■
Results of analysis and calibration
■
Dates of analysis
■
Name of person performing analyses
■
Transported COCs
■
Are DMRs complete: do they include all permit parameters?
■
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
■
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
❑
❑
■
❑
operator on each shift?
Is the ORC visitation log available and current?
■
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
■
❑
Is the backup operator certified at one grade less or greater than the facility
❑
❑
■
❑
classification?
Is a copy of the current NPDES permit available on site?
❑
■
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
■
❑
Comment: Certificate of coverage and field lab cert are not on site.
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory? ■ ❑ ❑ ❑
Page# 3
Permit: NCG590025
Inspection Date: 06/20/2024
Laboratory
Owner -Facility: windgate Subdivision - #1
Inspection Type: Compliance Evaluation
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Comment: Please refer to the inspection summary section of this report.
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Comment: All samples are grab samples.
Upstream / Downstream Sampling
Is the facility sampling performed as required by the permit (frequency, sampling type,
and sampling location)?
Comment: All samples are grab samples.
De -chlorination
Type of system ?
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de -chlorination substance stored away from chlorine containers?
Are the tablets the proper size and type?
Comment: Please refer to the inspection summary section of this report.
Are tablet de -chlorinators operational?
Number of tubes in use?
Yes No NA NE
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
Yes No NA NE
❑ ❑ ■ ❑
❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
❑ ❑ ❑ ■
❑ ❑ ❑ ■
Yes No NA NE
■ ❑ ❑ ❑
Yes No NA NE
Tablet
❑
■
❑
❑
❑
❑
■
❑
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
4
Page# 4
Permit: NCG590025
Inspection Date: 06/20/2024
Owner -Facility: windgate Subdivision - #1
Inspection Type: Compliance Evaluation
De -chlorination Yes No NA NE
Comment: Tubes were low on dechlorination tablets. The wastewater operator returned to the
facility post -inspection to add more tablets.
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment: Flow is calculated using flow restrictors (flow rate * time);
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment: Please refer to the inspection summary section of this report.
Operations & Maintenance
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: Please refer to the inspection summary section of this report.
Yes
No
NA
NE
■
❑
❑
❑
❑
■
❑
❑
■
❑
❑
❑
❑
❑
■
❑
Yes
No
NA
NE
•
❑
❑
❑
•
❑
❑
❑
❑
❑
■
❑
Yes No NA NE
■ ❑ ❑ ❑
❑ ■ ❑ ❑
Page# 5