HomeMy WebLinkAboutWQ0000962_Notice of Deficiency_20240717 July 17, 2024 Delivered electronically via email to: cecusin@culp.com Chad Cusin, Plant Manager Culp, Inc 7209 Hwy 158 E Stokesdale, NC 27357 SUBJECT: NOTICE OF DEFICIENCY Tracking Number: NOD-2024-PC-0119 Permit No. WQ0000962 Culp Ticking CLRS Guilford County Dear Mr. Cusin: On June 28, 2024, Division of Water Resources staff Kristen Potwora conducted a scheduled routine compliance inspection at Culp Ticking CLRS. Chad Cusin (Plant Manager) and Barry Bryant (ORC) were present for the entire inspection. A review of available records, the treatment facility, and the groundwater monitoring wells was completed. This review reflected non-compliance with the subject permit. DWR requested effluent sampling reports for 2023 and 2024, the operation and maintenance plan, and the spill plan on 7/5/2024 from Chad Cusin. These items were received by DWR on 7/8/24. The following deficiencies were noted: 1. Per Permit Condition III.7 “a protective vegetative cover shall be established and maintained on all berms, pipe runs, erosion control areas, surface water diversions, and earth embankments….” At the time of inspection, little to no living vegetation was present on the earthen berm surrounding the concreate containment structure. This was mentioned in the last compliance evaluation letter sent to the facility on May 11, 2022. Please continue to make efforts to establish a vegetative cover on this earthen berm. 2. Permit Condition II.3 states “Groundwater monitoring wells shall be constructed in accordance with 15A NCAC 02C .0108, and any other jurisdictional laws and regulations pertaining to well construction.” The following items were noted during the inspection. a) Mr. Bryant was able to move the Monitoring Well 2 casing back and forth with applied pressure indicating the concrete footer was no longer in contact with the ground surface and the well casing could be damaged. Mr. Cusin informed DWR that he recemented the well, however DWR recommends that a certified well installer inspect and confirm that the casing between the footer and ground is still in good condition and make the necessary repairs to ensure the integrity of the well is maintained. b) Three out of the five monitoring wells did not have identification plates, which is required by 15A NCAC 02C .0108 (p). MW4 had an identification plate, but it was corroded to the point that the information is no longer legible and needs to be replaced. MW6 had an identification plate, however it did not have all the required information on it. DWR requires the permittee to clearly label all wells and install well identification plates using the nomenclature from Attachment C. Send a photo of the identification plates and labels for each well once they are installed. Please refer to the enclosed inspection report for additional comments and observations. If you have any questions, please contact Kristen Potwora at the letterhead address, the phone number, 336-776-9697, or by email at jenny.graznak@deq.nc.gov or kristen.potwora@deq.nc.gov. Sincerely, Jennifer F. Graznak, Assistant Regional Supervisor Water Quality Regional Operations Section Division of Water Resources, NCDEQ-WSRO Enc: Inspection Report CC: Guilford County Environmental Health (electronic copy) Compliance Inspection Report Permit:WQ0000962 Effective:12/01/21 Expiration:04/30/28 Owner :Culp, Inc SOC: Contact Person: Region: County: Directions to Facility: Guilford Winston-Salem Teresa Huffman Effective:Expiration:Facility:Culp Ticking CLRS 7209 US 158 E Stokesdale NC 27357 Title:Phone:336-888-6266Vice President From downtown Winston-Salem, take NC 158 East approximately 22 miles to Stokedale. Continue on NC 158 for approximately 2 more miles. Facility is on the right at address #7209. Secondary ORC(s): Phone:Certification:Primary ORC: System Classifications: On-Site Representative(s): Related Permits: Secondary Inspector(s): Primary Inspector: Inspection Date:Exit Time:Entry Time: Phone: 06/28/2024 11:00AM 11:45AM Kristen Potwora 336-776-9800 Facility Status: Permit Inspection Type: Reason for Inspection:Inspection Type: Not CompliantCompliant Routine Closed-Loop Recycle Compliance Evaluation Question Areas: Miscellaneous Questions Record Keeping Storage Wells (See attachment summary) Page 1 of 4 Inspection Date: Permit: Inspection Type : Owner - Facility: Reason for Visit: WQ0000962 06/28/2024 Compliance Evaluation Culp, Inc Routine Inspection Summary: On June 28, 2024, Division of Water Resources staff Kristen Potwora conducted a scheduled routine compliance inspection at Culp Ticking CLRS. Chad Cusin (Plant Manager) and Barry Bryant (ORC) were present for the entire inspection. A review of available records, the treatment facility and the groundwater monitoring wells was completed. This review reflected non-compliance with the subject permit. DWR requested effluent sampling reports for 2023 and 2024, the operation and maintenance plan and the spill plan on 7/5/2024 from Chad Cusin. These items were received by DWR on 7/8/24. The following deficiencies were noted: 1.Per Permit Condition III.7 “a protective vegetative cover shall be established and maintained on all berms, pipe runs, erosion control areas, surface water diversions, and earth embankments….” At the time of inspection, little to no living vegetation was present on the earthen berm surrounding the concreate containment structure. This was mentioned in the last compliance evaluation letter sent to the facility on May 11, 2022. Please continue to make efforts to establish a vegetative cover on this earthen berm. 2.Permit Condition II.3 states “Groundwater monitoring wells shall be constructed in accordance with 15A NCAC 02C .0108, and any other jurisdictional laws and regulations pertaining to well construction.” The following items were noted during the inspection. a)Mr. Bryant was able to move the Monitoring Well 2 casing back and forth with applied pressure indicating the concrete footer was no longer in contact with the ground surface and the well casing could be damaged. Mr. Cusin informed DWR that the recemented the well, however DWR recommends that a certified well installer confirms that the casing between the footer and ground is still in good condition and make the necessary repairs to ensure the integrity of the well is maintained. b)Three out of the five monitoring wells did not have identification plates, which is required by 15A NCAC 02C .0108 (p). MW4 had an identification plate, but it was corroded to the point that the information is no longer legible and needs to be replaced. MW6 had an identification plate, however it did not have all the required information on it. DWR requires the permittee to clearly label all wells and install well identification plates using the nomenclature from Attachment C. Send a photo of the identification plates and labels for each well once they are installed. Observations: •Monitoring Well 4 had high TDS, Cl, Fe and Mn for 11/2022, 3/2023 and 3/2024 GW-59 reports. Fe and Mn were high in the 7/2023 and 11/2023 GW-59 reports. •Monitoring Well 5 had high TDS, Cl, Fe and Mn for 3/2024 GW-59 reports. •Monitoring Well 2, 3, 5 and 6 had high Fe and Mn for 7/2022, 11/2022, 3/2023, 7/2023 and 11/2023 GW-59 reports. •MW4 and MW5 had vegetation growing around the concrete footer making it difficult to find the well. Mr. Cusin sent photos to DWR of the mowed monitoring wells on 7/8/24. •TDS, Mn and Fe were high in the results for the Recycle Stream Grab (effluent) for the 2023 samples. •Shamrock removes 19 tons of residuals every 1-2 weeks, according to facility records. Page 2 of 4 Inspection Date: Permit: Inspection Type : Owner - Facility: Reason for Visit: WQ0000962 06/28/2024 Compliance Evaluation Culp, Inc Routine Type Yes No NA NE Reuse (Quality) Infiltration System Lagoon Spray, LR Single Family Spray, LR Activated Sludge Spray, LR Activated Sludge Drip, LR Activated Sludge Spray, HR Single Family Drip Recycle/Reuse Record Keeping Yes No NA NE Is a copy of current permit available? Are monitoring reports present: NDMR? NDAR? Are flow rates less than of permitted flow? Are flow rates less than of permitted flow? Are application rates adhered to? Is GW monitoring being conducted, if required (GW-59s submitted)? Are all samples analyzed for all required parameters? Are there any 2L GW quality violations? Is GW-59A certification form completed for facility? Is effluent sampled for same parameters as GW? Do effluent concentrations exceed GW standards? Are annual soil reports available? # Are PAN records required? # Did last soil report indicate a need for lime? If so, has it been applied? Are operational logs present? Are lab sheets available for review? Do lab sheets support data reported on NDMR? Do lab sheets support data reported on GW-59s? Are Operational and Maintenance records present? Were Operational and Maintenance records complete? Has permittee been free of public complaints in last 12 months? Is a copy of the SOC readily available? Page 3 of 4 Inspection Date: Permit: Inspection Type : Owner - Facility: Reason for Visit: WQ0000962 06/28/2024 Compliance Evaluation Culp, Inc Routine No treatment units bypassed since last inspection? Comment: Page 4 of 4