HomeMy WebLinkAboutNC0020737_Response to Notice_20240627From:
Lee Bailev
To:
Bell, Wes
Cc:
Pitner, Andrew
Subject:
[External] Notice of Violation response
Date:
Thursday, June 27, 2024 9:37:11 AM
Attachments:
innaae001.png
CAUTION: External email. Do not click links or open attachments unless verified. Report suspicious emails with the
Report Message button located on your Outlook menu bar on the Home tab.
Dear Mr. Wes Bell:
On April 18th 2024 Pilot Creek WWTP had a C12 reading of 507.6 due to S02 not feeding to the
Effluent stream. Contractors onsite requested #3 system be pumped down to inspect a vault that
had a pipe we were wanting to use to feed Effluent water to the Belt Press after #1 system was
taken out of service. The S02 suction line was feeding from #3 chlorine contact chamber and had
not been switched to pull from #4 chlorine contact chamber for pump suction line. The operator
checking during rounds did not notice the Sulfur was not feeding, Effluent samples were collected
and during C12 test the Lab tech notified the staff that the C12 reading was too high and we had a
problem. S02 system was checked and the pump was found to be hot and not feeding S02, so the
operators found the valves were not switched to feed suction to the pump from #4 CCC. Valves were
switched and the pump was primed and S02 was being fed to the Effluent minutes after the Effluent
tests had been performed by the Lab. The corrective action is that every operator has been shown
where the S02 valves are located, and now the valves are checked prior to any switch over of the
S02 system. The employee that did rounds that morning was written up, and has since resigned.
Lee, 3 aV,ey
Lee Bailey
ORC/Supervisor
City of Kings Mountain
200 Potts Creek Rd.
Kings Mountain, INC 28086
(704)739-7131
lee.bailey@cityofkm.com
ats
*ti - Wq17
KINGS MOUNTAIN
ICihFbs iiOilM7Al�i
— NORTH CAROLINA —
Z"rLy. mod,