HomeMy WebLinkAboutNC0024201_Includes permit, permit renewal application, and historical information_20061231Michael F. Easley, Governor
April 27, 2006
Dear Permittee:
>
2.
An Equal Opportunity/Affirmative Action Employer - 50% Recycled/10% Post Consumer Paper
Your NPDES permit for a municipally owned/operated WWTP expires on March 31, 2007. This notice is
being sent to explain the requirements for your permit renewal application.
R.D. Brown
Roanoke Rapids Sanitary District
P.O. Box 308
Roanoke Rapids, NC 27870
Federal (40 CFR 122) and state (15A NCAC 2H.0105(e)) regulations require that permit renewal
applications be filed at least 180 days prior to expiration of the current permit. Your renewal application is
due to the Division postmarked no later than October 2, 2006. Failure to apply for renewal by the
appropriate deadline may result in a civil penalty assessment or other enforcement activity at the discretion
of the Director.
1617 Mail Service Center, Raleigh, North Carolina 27699-1617
512 North Salisbury Street, Raleigh, North Carolina 27604
Phone: 919 733-5083 / FAX 919 733-0719 / Internet: h2o.enr.state.nc.us
>
>
>
>
>
William G. Ross, Jr., Secretary
Alan W. Klimek, P.E., Director
SUBJECT: Advance Notice of Renewal Application Requirements
Permit NC0024201
Roanoke Rapids WWTP
Conduct four toxicity tests for an organism other than Ceriodaphnia and submit results with
your renewal application. The tests should be conducted quarterly, with samples collected on the
same day as your current toxicity test. Call the Aquatic Toxicology Unit at (919) 733-2136 for
guidance in conducting the additional tests.
NCDENR
North Carolina Department of Environment and Natural Resources
Division of Water Quality
You are receiving this advance notice because your facility has a permitted flow at or above 1
MGD, or the subject facility receives industrial [pretreatment] waste water. If either of these
criteria no longer applies, contact the NPDES Unit before submitting a renewal application.
NorthCarolinaNaturally
The U.S. EPA revised and expanded the application requirements for municipal permits, effective August 1,
2001. EPA form 2A is attached to this Notice, and must be used for your permit renewal application. The
new application requirements mandate additional effluent testing:
1. Conduct three Priority Pollutant Analyses (PPAs) and submit results with your renewal
application. Collect samples for the PPAs in conjunction with sampling for your current
quarterly toxicity test. The new PPA requirements differ from previous versions. Each PPA
must include:
Analyses for all total recoverable metals listed in Part D of form 2A. This includes metals
that are not normally monitored through your NPDES permit.
Analyses for total phenolic compounds and hardness.
Analyses for all of the volatile organic compounds listed in Part D.
Analyses for all of the acid-extractable compounds listed in Part D.
Analyses for all base-neutral compounds listed in Part D.
Analyses for Total Mercury must be performed using EPA Method 1631.
Sincerely,
o
o
o
o
Use the checkhst below to complete your renewal package. The checkhst identifies the items you
must submit with the permit renewal application. If all wastewater discharge has ceased at this facility and
you wish to rescind this permit, please contact me. My telephone number, fax number and e-mail address
are hsted at the bottom of the previous page.
tice for Permit NC0024201
Halifax County
Page 2
Send the completed renewal package to:
Mrs. Carolyn Bryant
NC DENR / DWQ / Point Source Branch
1617 Mail Service Center
Raleigh, NC 27699-1617
cc: Central Files
Raleigh Regional Office, Water Quality Section
NPDES File
Charles H. Weaver, Jr.
NPDES Unit
If any wastewater discharge will occur after the current permit expires, this NPDES permit must be
renewed. Discharge of waste water without a valid permit would violate Federal and North Carolina law.
Unpermitted discharges of wastewater could result in assessment of civil penalties of up to $25,000 per day.
The pollutant and toxicity scans described above must accompany your permit renewal application,
or any major permit modification request. The Division cannot draft your permit without the additional
data. Any data submitted cannot be over 4 Yz years old, and must account for seasonal variation
(samples cannot be collected during the same season each year if collected over multiple years). If your
permit already contains a requirement for an annual effluent pollutant scan, additional scans are not
required [provided you have conducted at least 3 scans prior to submitting your application].
The following items are REQUIRED for all renewal packages:
A cover letter requesting renewal of the permit and documenting any changes at the facility since
issuance of the last permit. Submit one signed original and two copies.
The completed EPA Form 2A application (copy attached), signed by the permittee or an Authorized
Representative. Submit one signed original and two copies.
If an Authorized Representative (such as a consulting engineer or environmental consultant) prepares
the renewal package, written documentation must be provided showing the authority delegated to the
Authorized Representative (see Part II.B.ll.b of the existing NPDES permit).
A narrative description of the sludge management plan for the facility. Describe how sludge (or other
sohds) generated during wastewater treatment are handled and disposed. If your facility has no such
plan (or the permitted facility does not generate any sohds), explain this in writing. Submit one signed
original and two copies. This information can be included in the cover letter.
Michael F. Easley, Governor
April 3, 2006
Dear Mr. Brown:
C
cc:
An Equal Opportunity/Affirmative Action Employer - 50% Recycled/10% Post Consumer Paper
Mr. Daniel Brown, CEO
Roanoke Rapids Sanitary District
P.O. Box 308
Roanoke Rapids, NC 27870
Central Files
Greta Glover, Roanoke Rapids Sanitary District
Daryl Merritt, Pretreatment Unit
Christopher Wu, RRO
Raleigh, NC 27699-1617
Raleigh. NC 27604
Phone (919) 733-5083
FAX (919)733-0059
Alan W. Klimek, P.E. Director
Division of Water Quality
NC DWQ/PERCS Unit 1617 Mail Service Center
Internet: h2o.enr,state.nc.us/Pretreat/index.html 512 N. Salisbury St.
Subject: Pretreatment Annual Report Review
Roanoke Rapids Sanitary District
Halifax County
NPDES Number: NC0024201
Sincerely,
One
NorthCarolina-----------Naturally
Customer Service
1-877-623-6748
William G. Ross Jr., Secretary
North Carolina Depanment of Environment and Natural Resources
Christopher Wu
Environmental Specialist
The Central and Regional Offices have reviewed the Pretreatment Annual Report (PAR)
covering January through December 2005. This PAR was received on February 27, 2006.
The PAR is considered complete and satisfies the requirements of 15A NCAC 2H .0908(b) and
the Comprehensive Guidance for North Carolina Pretreatment Programs.
1005
Thank you for your continued cooperation with the Pretreatment Program. If you have any
questions or comments, please contact Daryl Merritt at (919) 733-5083 ext. 554 [email:
daryl.merritt@ncmail.net].
Michael F. Easley, Governor
>
|v'C
CERTIFIED MAIL
May 19, 2006
SUBJECT:
Dear Ms. Glover:
Sincerely,
Attachments
cc:
An Equal Opportunity/Affirmative Action Employer - 50% Recycled/10% Post Consumer Paper
This decertification may be appealed to the N.C. Office of Administrative Hearings in accordance
with Chapter 150B of the General Statutes.
The results your laboratory reported on evaluation samples for the above parameter(s) are shown on
our letter dated May 8, 2006 (copy attached). These results lie outside the acceptable variation limit from the
true value set forth as acceptable in the Laboratory Certification Regulation 15A NCAC 2H .0803(4).
Please be advised that under provisions of Regulations 15A NCAC 2H .0807 (b) (1) and the powers
duly delegated to me, a sixty day parameter decertification notice is hereby issued to the Roanoke Rapids,
Roanoke River WWTP laboratory for above parameter(s) effective June 1, 2006. No testing for the above
parameter(s) shall be performed at your laboratory for clients or wastewater treatment plants reporting to this
Department for purposes of State water, wastewater, or groundwater monitoring required under Article 21 of
G.S. 143. Sixty days thereafter you may again apply for parameter recertification as detailed in 15A NCAC
2H .0808 (b) of the regulations.
Also enclosed is a revised certified parameter listing for your certificate which removes the decertified
parameter(s) from your certification.
Edith Henderson
Raleigh Regional Office
James W. Meyer
Certification Branch Manager
Laboratory Section
Alan W. Klimek, P.E. Director
Division of Water Quality
70
Ms. Greta Glover
Roanoke Rapids, Roanoke River WWTP
135 Aqueduct Road
Weldon, NC 27890-
Laboratory Section 1623 Mail Service Center; Raleigh, NC 27699-1623
4405 Reedy Creek Road; Raleigh, NC 27607
Phone (919)733-3908 /FAX (919) 733-2496 /Internet: www.dwqlab.org
Parameter Decertification
RESIDUE TOTAL SM Method 2540 B
..One, _ North Car ^atuu
If you have questions or need additional information concerning this matter, please contact James
W. Meyer telephone (919) 733-3908.
William G. Ross Jr., Secretary
North Carolina Department of Environment and Natural Resources
Attached is our form LC-22 which requests, as a result of this parameter decertification, that certain
information be reported concerning your laboratory and/or clients for whom State required monitoring
analysis are performed. The attached form must be completed and returned within thirty days of the
decertification effective date. Failure to complete and return this form may result in further enforcement
actions.
^7-' Q
sDUJGft
»
DATE: May 19, 2006Roanoke Rapids, Roanoke River WWTPLABORATORY NAME:
CERT #: 70DECERTIFIED PARAMETER(s) RESIDUE TOTAL SM Method 2540 B
LABORATORY TYPE - Municipal/lndustrial
Please respond to the following:
1.
( )Yes( ) No
If yes, enter name of laboratory to be used.
If no, explain:
If necessary, attach additional pages.
Within thirty days of the decertification effective date, Return to:
DateLaboratory Supervisor Signature
LC-22M Rev. 3/00
L
As a result of the above decertification, you are required to furnish information about this wastewater facilities for
whom
state required wastewater monitoring analysis are performed.
Arrangements have been made to have samples for the decertified parameter(s) analyzed by another
certified laboratory.
Municipal or Industrial Laboratories - During any decertification period, the decertified laboratory is required to have
samples analyzed by another certified laboratory and supply the State Laboratory the name of the laboratory to be
used.
DENR/DWQ
Laboratory Section
1623 Mail Service Center
Raleigh, North Carolina 27699-1623
Attn: James W. Meyer
DECERTIFIED LABORATORY REP^^
This certification requires maintance of an acceptable quality assurance program, use of approved methodology, and satisfactory performance on evaluation samples. Laboratories are
subject to civil penalties and/or decertification for infractions as set forth in 15A NCAC 2H.0807.
Lab Name:
Address:
Roanoke Rapids, Roanoke River WWTP
135 Aqueduct Road
Weldon, NC 27890-
Attachment
North Carolina Wastewater/Groundwater Laboratory Certification
Certified Parameters Listing
Certificate Number:
Effective Date:
Expiration Date:
Date of Last Amendment:
70
01/01/2006
12/31/2006
06/01/2006
INORGANICS
BOD
Std Method 5210B
CBOD Std Method 5210B
COD
Hach Method 8000
RESIDUAL CHLORINE
Hach Method 10014 ULR
Hach Method 8167
COLIFORM FECAL
Std Method 9222D (MF)
DISSOLVED OXYGEN
Std Method 4500 O G
AMMONIA NITROGEN
Std Method 4500 NH3 F
OIL & GREASE
Std Method 5520B
pH
Std Method 4500 H B
SW846 Method 9040C
RESIDUE SUSPENDED
Std Method 2540D
TEMPERATURE
Std Method 2550B
VECTOR ATTRACTION REDUCTION
Option 1: Reduction in Volatile Solids
Option 6: Addition of Alkali
Option 7: Moisture Reduction without
Solids
Option 8: Moisture Reduction with Solids
The above named laboratory, having duly met the requirements of 15A NCAC 2H.0800, is hereby certified for the measurement of the parameters listed below.
' CERTIFIED PARAMETERS
Michael F. Easley, Governor
May 8, 2006
SUBJECT: Sixty-Day Parameter Decertification
Dear Ms. Glover:
Not Acceptable459371417353mg/LNSI WP-111
Edith M. Hendersoncc:
An Equal Opportunity/Affnmative Action Employer - 50% Recycled/10% Post Consumer Paper
Contact us immediately at (919) 733-3908 if your records do not agree with ours of if you have
questions.
William G. Ross Jr., Secretary
North Carolina Department of Environment and Natural Resources
Alan W. Klimek, P.E. Director
Division of Water Quality
70
Ms. Greta Glover
Roanoke Rapids, Roanoke River WWTP
135 Aqueduct Road
Weldon, NC 27890-
Laboratory Section 1623 Mail Sendee Center; Raleigh, NC 27699-1623
4405 Reedy Creek Road; Raleigh, NC 27607
Phone (919) 733-3908 / FAX (919) 733-2496 / Internet: www.dwqlab.org
True Value
345
Units
mg/L
Performance
Not Acceptable
Study
NSI WP-109
Parameter
Total Solids SM
254QB
Total Solids SM
2540B
Upper Limit
382
Reported
296
Lower Limit
303
NorthCarolinaNaturally
■ X
Sincerely,
,/7 James W. Meyer V
V Laboratory Section
^/lll I IfJ —— I ■ ■■ ■ ■
The rerun result(s) for the above parameter(s) by your laboratory for the N.C. Department of
Environment and Natural Resources laboratory certification performance evaluation was unsatisfactory and a
sixty-day parameter decertification will be recommended. The results reported and the true values as they
appear in our records are as follows:
This is to notify you that the Laboratory Certification Branch of the Division of Water Quality, Laboratory
Section, is considering recommending a parameter(s) decertification to the Laboratory Section Chief. The
recommendation concerns the above mentioned violation(s). This is not a decertification; it is a notification
of our intent to consider decertification. You will be informed in a separate communication if
decertification is issued.
Michael F. Easley, Governor
June 13, 2006
Subject:
Dear Mr. Brown:
Alan W. Klimek, P.E.
Cc:
An Equal Opportunity/Affirmative Action Employer-50% Recycled/10% Post Consumer Paper
North Carolina Division of Water Quality
Internet: www.ncwaterquality.oiiJ
The Division of Water Quality has received your permit modification request dated May 24, 2006, for the
Roanoke Rapids Wastewater Treatment Plant. Permit modifications requesting the removal of an effluent
parameter from an NPDES permit is considered a major modification to the permit. Such a change, if
implemented, would subject the permit to the same public notice procedures as issuing a new or renewed
permit. In addition, because your facility is classified as a major municipal, any major modifications to
your permit would have to receive concurrent approval from the U.S. Environmental Protection Agency
(EPA). Given the above, and since your permit expires on March 31, 2007, and since the renewal process
is scheduled to begin within the next few months, this office will evaluate your request to remove the
mercury effluent limit during your NPDES permit renewal process. We can, however, at this time reduce
the measurement frequency requirement for the effluent and upstream mercury from weekly to monthly.
Accordingly, we are forwarding herewith the attached modified NPDES permit. Please insert the
attached permit pages into your permit and discard the old ones.
This permit modification is issued pursuant to the requirements of North Carolina General Statute 143-
215.1 and the Memorandum of Agreement between North Carolina and the U.S. EPA dated May 9, 1994
(or as subsequently amended).
As a reminder, your permit renewal application is due to the Division postmarked no later than October 2,
2006, in order to satisfy the conditions of your NPDES permit.
If you have questions regarding any of the above, please feel free to contact Vanessa Manuel at 919/733-
5083, extension 532.
1617 Mail Service Center
512 N. Salisbury St.
William G. Ross, Jr., Secretary
North Carolina Department of Environment and Natural Resources
Phone (919) 733-5083
FAX (919)733-0719
Alan W. Klimek, P.E., Director
Division of Water Quality
Attachments
Central Files
NPDES File
DWQ/SWP Raleigh Regional Office
DWQ/ESS Aquatic Toxicology Unit
EPA Region 4, Roosevelt Childress
R. Danieley Brown, P.E.
Roanoke Rapids Sanitary District
PO Box 308
Roanoke Rapids, NC 27870
Request for Permit Modification
Roanoke Rapids WWTP
NPDES Permit NC0024201
Halifax County
Raleigh, NC 27699-1617
Raleigh, NC 27604
Customer Service
1-877-623-6748
h r
. .One, ,.NorthCarolinaNaturally
Sincerely,
09
>
Permit NC0024201
PERMIT
TO DISCHARGE WASTEWATER UNDER THE
NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM
Roanoke Rapids Sanitary District
is hereby authorized to discharge wastewater from a facility located at the
The permit shall become effective July 1, 2006.
This permit and the authorization to discharge shall expire at midnight on March 31, 2007.
Signed this day June 13, 2006.
STATE OF NORTH CAROLINA
DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES
DIVISION OF WATER QUALITY
In compliance with the provisions of North Carolina General Statute 143-215.1, other lawful standards
and regulations promulgated and adopted by the North Carolina Environmental Management
Commission, and the Federal Water Pollution Control Act, as amended, the
Roanoke Rapids Sanitary District WWTP
135 Aqueduct Road
Weldon
Halifax County
/
/
/Alan W. Klimek, P.E., Director
> Division of Water Quality
By Authority of the Environmental Management Commission
to receiving waters designated as Chockoyotte Creek at the Roanoke River in the Roanoke
River Basin in accordance with effluent limitations, monitoring requirements, and other
conditions set forth in Parts I, II, and III hereof.
Permit NC0024201
EFFLUENT LIMITATIONS
8.34 MGD RecordingFlowContinuous
25.0 mg/L 37.5 mg/L CompositeCBOD, 5-day, 20°C2 Daily
30.0 mg/L 45.0 mg/L Daily CompositeTotal Suspended Solids2
EffluentNH3 as N
Total Residual Chlorine 28 Mg/L Effluent
Fecal Coliform Grab Effluent200/100 ml 400/100 ml
(geometric mean)
Between 6.0 and 9.0 Standard Units Grab Effluent
Grab Effluent
Grab Effluent
Composite Effluent
Effluent
0.868 gg/L
Effluent
EffluentTotal Selenium
EffluentTotal Fluoride
Effluent
U, D
Variable4 Grab U, DTemperature
There shall be no discharge of floating solids or visible foam in other than trace amounts.
A. (3) Effluent Limitations and Monitoring Requirements
(Discharges after outfall relocation)
Beginning July 1, 2006, and lasting until March 31, 2007, the permittee is authorized to discharge
treated wastewater from outfall 001. Such discharges shall be limited and monitored by the permittee
as specified below:
3.
4.
EFFLUENT
CHARACTERISTICS
Monthly
Average
Weekly
Average
Daily
Maximum
Measurement
Frequency
Influent or
Effluent
Influent &
Effluent
Influent &
Effluent
Sample
Type
Chronic Toxicity3
Dissolved Oxygen
Monthly
Monthly
Monthly
Monthly
Monthly
Monthly
Quarterly
Variable4
Composite
Grab
Composite
Grab
Composite
Composite
Composite
Composite
Composite
Grab
Effluent, U
Effluent
pH
Dissolved Oxygen
Temperature
Total Nitrogen
(NO2 + NOa + TKN)
Total Phosphorus
Total Mercury
Total Copper
Total Zinc
Daily
Daily
Daily
Monthly
Daily
Daily
Daily
U: Upstream at 308 Rollingwood Road. D: Downstream at the U.S. 158 crossing at the Roanoke River.
The monthly average effluent CBOD5 and TSS concentrations shall not exceed 15% of the respective influent
value (85% removal).
Chronic Toxicity (Ceriodaphnia) at 1.1 %; January, April, July and October (see condition A. (5)).
Upstream/downstream samples shall be collected 3/Week during June, July, August, September, and 1/Week
during the remaining months of the year. Stream sampling may be discontinued at such times as flow
conditions in the receiving waters or extreme weather conditions will result in substantial risk of injury or
death to persons collecting samples. In such cases, on each day that sampling is discontinued, written
justification for the discontinuance shall be specified in the monitoring report for the month in which the event
occurred. Stream sampling shall be resumed at the first opportunity after the risk period has ceased.
MONITORING REQUIREMENTS
Sample
Location1
Notes:
1.
2.
COUNTY/YREMISE NUMBER
PERMIT NUMBER
DATE
I n
I
FACILITY:
CITY:
COUNTY:
Permit Information that Needs to be Incorporated into Future Permit Revisions:
COMMENTS
Michael F. Easley, Governor
June 20, 2006
SUBJECT: Laboratory Certification Maintenance Inspection
Dear Ms. Glover:
Sincerely,
Enclosure
An Equal Opportunity/Affirmative Action Employer - 50% Recycled/10% Post Consumer Paper
cc: Edith Henderson
Raleigh Regional Office
James W. Meyer
Laboratory Section
William G. Ross Jr., Secretary'
North Carolina Department of Environment and Natural Resources
Alan W. Klimek, P.E. Director
Division of Water Quality
70
Ms. Greta Glover
Roanoke Rapids, Roanoke River WWTP
135 Aqueduct Road
Weldon, NC 27890-
Laboratory Section 1623 Mail Service Center; Raleigh, NC 27699-1623
4405 Reedy Creek Road; Raleigh, NC 27607
Phone (919) 733-3908/FAX (919) 733-2496/Internet: www.dwqlab.org
Enclosed is a report for the inspection performed on, June 6, 2006 by Ms. Edith Henderson.
Where deficiencies are cited in this report, a response is required as well as for all lettered comments
and/or recommendations. Within thirty days of receipt, please supply this office with a written item for
item description of how these deficiencies, comments and/or recommendations were corrected. If the
deficiencies cited in the enclosed report are not corrected, enforcement actions will be recommended.
For certification maintenance, your laboratory must continue to carry out the requirements set forth in
15A NCAC 2H .0800.
NorthCarolinaNaturally
Copies of the checklists completed during the inspection may be requested from this office.
Thank you for your cooperation during the inspection. If you wish to obtain an electronic copy of this
report by email, or if you have questions or need additional information please contact us at 919-733-
3908.
&
J?07roua
On-Site Inspection Report
LABORATORY NAME:Roanoke Rapids, Roanoke River WWTP
ADDRESS:
CERTIFICATE NO:70
NPDES PERMITS:NC0024201
DATE OF INSPECTION:June 6, 2006
TYPE OF INSPECTION:Maintenance
EVALUATOR:Ms. Edith Henderson
Ms. Greta GloverLOCAL PERSON(S) CONTACTED:
INTRODUCTION:I.
II.GENERAL COMMENTS:
This report reflects findings related to on-site inspection and application information
DEFICIENCIES, REQUIREMENTS, COMMENTS AND RECOMMENDATIONS:III.
COD:
to zero the
This laboratory was inspected to verify its compliance with the requirements of 15A NCAC 2H .0800 for
the analysis of environmental samples.
A. COMMENT: The laboratory has each analyst perform a verification of the DR 4000 manufacturers’
pre- programmed calibration.
REQUIREMENT: NCLC policy requires that the concentration of the blank must not exceed 50% of the
LOQ/MQL/PQL. The lab must obtain a signal in which the constituent concentration in reagent water is
2(1.645)s above the mean of blank analyses (Lower Limit of Detection). The constituent concentration
that produces a signal sufficiently greater than the blank, that it can be detected within specified limits,
by good laboratories, during routine operating conditions, is the Limit of Quantitation. Typically it is the
concentration that produces a signal 10s above the reagent water blank signal. In most cases, this
135 Aqueduct Road
Weldon, NC 27890-
addition to
15A NCAC
REQUIREMENT: Each analyst must have there own daily or annual curve unless a pre-programmed
calibration is used. Pre-programmed calibrations must be verified annually with 5 non-zero standards
and a blank. A new calibration verification will need to be performed for each new lot of digestion
solution and each new lot of stock standard a new. Each analysis day, thereafter, include at least one
reagent blank and CCV (NC Policy defines as mid-range check standard same source as calibration
standards), with each digestion batch. In addition, analyze one known standard in
calibration standards each day samples are analyzed to document accuracy. Reference:
2H .0805 (a) (7) (B) and (I); SM 20th Edition 5220D.4C.
B. COMMENT: The laboratory uses a digested blank rather than an undigested blank
spectrophotometer. The laboratory must monitor the absorbance readings of the digested blank to
ensure the contribution to sample absorbance is at a minimum.
Page 2
Total Suspended Solids:
Total Residual Chlorine:
F. COMMENT: The laboratory has each analyst perform a verification of the DR 4000 manufacturers’
pre-programmed calibration.
REQUIREMENT: The analyst must analyze sufficient sample to get at least 1 mg of residue. "If weight of
captured residue is less than 1.0 mg, the sample volume must be increased to provide at least 1 mg of
residue." Ref: Methods for Chemical Analysis of Water and Wastes, Residue, Non-Filterable, Method
160.2
REQUIREMENT: Each analyst must have there own daily or annual curve unless a pre-programmed
calibration is used. Pre-programmed calibrations must be verified annually with 5 non-zero standards
and a blank. Each analysis day, thereafter, include at least one reagent blank and CCV (NC Policy
defines as mid-range check standard same source as calibration standards), with each digestion
batch. In addition, analyze one known standard in addition to calibration standards each day samples
are analyzed to document accuracy. Reference: 15A NCAC 2H .0805 (a) (7) (B) and (I);
C. COMMENT: The laboratory will need to consider increasing the ‘effluent’ sample volume filtered to
ensure an adequate amount of residue is retained on the filter. Otherwise, the reporting limit of the
procedure must be adjusted to account for the decreased filtration volumes.
E. COMMENT: The laboratory must evaluate procedures to determine why blank samples obtain an
appreciable amount of residue on filters. Analyst must ensure filters are washed thoroughly after sample
filtration to remove any dissolved material which would be mis-read as suspended. Procedures for
cooling and desiccating of samples to balance temperatures should be reviewed. When filters are not
allowed to cool sufficiently erroneous readings can be obtained due to the unstable temperatures.
D. COMMENT: Blanks periodically produce negative values which can be an indication filters are
insufficiently washed during the preparation procedure. Washing the filters removes any small fibers that
would otherwise wash from the filter when a volume of water is vacuumed through the filter, therefore
producing a negative result.
requires an absorbance value greater than 0.005 units, preferably greater than 0.010 units. Ref:
Standard Methods, 20th Edition - Method 1010 C. and 1030 C.
REQUIREMENT: Insert disk with wrinkled side up in filtration apparatus. Apply vacuum and wash disk
with three successive 20-mL portions of reagent-grade water. Continue suction to remove all traces of
water; turn vacuum off and discard washings. Reference: SM 20th Edition 2540D 3a.
REQUIREMENT: Dissolved solids are the portion of solids that passes through a filter of 2.0pM
nominal pore size under specified conditions. Suspended solids are the portion retained on the filter.
For samples high in dissolved material thoroughly wash the filter to ensure removal of dissolved
material. Each sample requires close attention to desiccation after drying. Minimize opening desiccator
because moist air enters. Reference: SM 20th Edition 2540A section 1, 2 and 2540D section 1b.
REQUIREMENT: Choose sample volume to yield between 2.5 and 200 mg dried residue. If volume
filtered fails to meet minimum yield, increase sample volume up to 1L. Reference: SM 20th Edition
2540D 3b.
Page 3
IV.PAPER TRAIL INVESTIGATION:
V.CONCLUSIONS:
Report prepared by: Edith Henderson Date: June 15, 2006
This consisted of comparing data reported on DMRs submitted to this Division with the values obtained
on laboratory bench worksheets. No data transcription errors were observed.
Correcting the above cited comments and/or deficiencies will help this lab to produce quality data and
meet certification requirements. Please respond to all lettered comments.
PERFORMANCE ANNUAL REPORT 2006
ROANOKE RAPIDS SANITARY DISTRICT
I.GENERAL INFORMATION
A. Regulated entity: Roanoke Rapids Sanitary District, Collection Systems (C.S.) and
Wastewater Treatment Plant (WWTP)
B.Responsible entity: Roanoke Rapids Sanitary District, Dan Brown, CEO
C.Person in charge/contact
2.
D. Applicable Permit(s)
E. Description of C.S.:
s
1. C.S.: Charles Turner, Operator in Responsible Charge (ORC)
Roanoke Rapids Sanitary District
PO Box 308
Roanoke Rapids, NC 27870
Phone: 252-537-9747
WWTP: Gregg Camp, Operator in Responsible Charge (ORC)
Roanoke Rapids Sanitary District, WWTP
135 Aqueduct Road
Weldon, NC 27890
Phone: 252-536-4884
The system has five sewer lift stations. Two stations are located in the Gaston, NC system.
One of these serves a Northampton County School and the other station pumps all flows
from Northampton County across the NC 48 Bridge crossing the Roanoke River to the
Roanoke River Interceptor. The remaining three pump stations are located within the
Roanoke Rapids system. Two of the stations, Belmont and Poplar Springs, discharge to the
The Roanoke River Interceptor collects wastewater from basins located on the north side of
Roanoke Rapids. The Gaston and Northampton basins are included in this service area. The
Interceptor begins just west of NC 48 in Roanoke Rapids. There are three primary basin
pump stations and one secondary pump station along the route. Pipe sizes for the Interceptor
ranges from 18” to 30”.
The collection system consists of approximately 130 miles of sewer lines. The sewer lines
within Roanoke Rapids, Gaston and all sub-divisions, which connect to the two main
Interceptors, range in size from 8” to 12”. There are two main Interceptors transporting
waste to the WWTP.
The Chockoyotte Creek Interceptor handles the south side of Roanoke Rapids and three sub
divisions, Lake View Park, Greenbriar and Lincoln Heights, outside the Roanoke Rapids city
limits. The Interceptor begins east of Zoo Road. There is one primary basin pump station
along the route. Pipe size ranges from 12” to 30”.
1. C.S.: North Carolina Environmental Management Commission System-wide
Wastewater Collection System Permit No. WQCS00027
2. WWTP: NPDESNC0024201
Land Application (L.A.): WQ0001989
Stormwater (General): NCG110000
II.PERFORMANCE
The performance of the system in 2006 was good.
Roanoke River Interceptor while the Greenbriar Pump Station discharges to the Chockoyotte
Creek Outfall.
Preventive Maintenance of at least four hours a week cleaning sewer mains has also been
a good tool in reducing sewer backups. The use of degreasers in pump stations on a
regular schedule has proven to be very effective in preventing lift station down time.
Also all pumping stations are checked and cleaned a minimum of twice weekly.
-2-
The Fat, Oil and Grease (FOG) program initiated in 1995 has been a good tool in
preventing Sanitary Sewer Overflows (SSO’s).We also have a fulltime employee for the
FOG Program to inspect all records and grease traps. He also educates all restaurants
about grease and how it effects our sewer lines. The use of local newspaper for FOG
program educational ads and the distribution of brochures to restaurants and fast food
businesses have also been effective. Inspection of records and grease traps is an ongoing
measure to prevent SSO’s.
The wastewater treatment plant is rated at 8.34 million gallons per day (MGD). Peak flow is
rated at 12.5 MGD.
During these processes solids are removed from two locations. Primary clarification removes
settleable solids from incoming wastewater to an anaerobic digestion unit. Here the solids, in
the absence of oxygen, receive pH adjustment, mixing, and heating to produce a stabilized
material. Once the solids are stable, excess water is decanted and returned to the plant for
further treatment. The stabilized, thickened solids are treated with lime for odor control then
removed to a holding tank to await land application.
Treatment processes at the wastewater plant include grit and rag removal. This is followed by
primary clarification, trickling filter biological secondary treatment, activated solids
treatment, secondary clarification, final effluent chlorination/dechlorination processes, and
final pH adjustment.
There are two pumping stations in the wastewater plant distributing wastewater into and
through the plant. Of these two pump stations, one has the capacity to pump 20 MGD and the
other 27 MGD respectively. Also, to aid these two pump stations; a storm water pump station
has been installed. This station intercepts rainwater, an unnecessary load to the treatment
plant, and removes it before entry to the plant. It has the capacity to pump 11.5 MGD. In
conjunction to these two pump stations there is one pump station with capacity of 21 MGD to
remove treated flows from the plant in the event of high river levels preventing normal gravity
flow discharge. Various others pumps and mixers are located throughout the plant for process
control.
Secondary clarification removes solids from the activated solids process. Here, solids in the
presence of oxygen, ph control, and mixing, accumulate in excess. They are removed,
chemically stabilized, and added to a holding facility. All stabilized solids are analyzed and
land applied according to their nutrient value, ceiling and accumulative requirements.
A. Description of overall 12 month performance, noting highlights and deficiencies:
1. C.S.:
The Roanoke Rapids Sanitary District’s collection system received its inaugural permit in
2001 under the North Carolina Environmental Management Commission Department of
Environment and Natural Resources system wide wastewater collection system
permitting program.
F. Description of WWTP:
The SC ADA system that monitors all lift station 24 hours
prevented lift station overflows.
a day, 365 days a year has
The permit also contains a daily maximum residual chlorine of 28 micrograms per liter
(ug/l), a weekly mercury maximum of 868 nanograms per liter (ng/l), and ph must be
maintained between 6 and 9.
The increase may be due to significant rainfall amounts the latter half of 2006, resulting
in higher flows as a result ot inflow and infiltration. Also, one of the wastewater plants
non-significant industrial users added an additional shift.
Current plant capacity is 8.34 million gallons per day (MOD) with a peak flow of 12.5
MOD. For 2006 the yearly average low flow was 3.7 MOD with minimum of 2.1 MGD.
The yearly average high flow was 6.0 MGD with a maximum of 9.1 MGD. The yearly
average total flow was 4.5 MGD or 54% of the plant capacity. This is a 8.9% increase
over the previous year.
Under the current permit, the District has a weekly effluent total suspended solids (TSS)
limit of 45 mg/1 and a monthly limit of 30 mg/1. Also a weekly carbonaceous
biochemical oxygen demand (CBOD) limit of 37.5 mg/1 and a monthly limit of 25 mg/1.
The yearly average for TSS was 17.6 mg/1 and CBOD was 4.9 mg/1. Using yearly
average influent values for the same parameters this calculates to a 90.3% and 96.1%
removal rate respectively. The permit requirement is 85%.
In 2006, the District continued to be very active in maintenance issues and concerns. The
WWTP spent in excess of $745,000 on maintenance and repairs to equipment, supplies
and materials necessary to operate equipment and capitalized monies to replace and
upgrade equipment.
Some of the repairs and upgrades in 2006 include the following.
Grit Removal. The back -up grit removal process underwent major repairs. It is critical
for the protection of downstream equipment. On line since the early 1960’s, some of the
original equipment was still in use. The concrete collection area was showing severe
"scabbing” or wear. It was coated with an epoxy system to buildup and protect the
remaining concrete. The sweeper collection mechanism, it’s support structure and work
deck, all made of carbon steel, was rebuilt. Ail parts were replaced with stainless steel.
The deflector plates used to slow the flow of water down to allow grit to settle out, were
also made of carbon steel and had severely deteriorated. They were replaced with
stainless steel. The screw removal system on-line since the early 1980’s was made of
carbon steel and had severely deteriorated as well. A new system, completely fabricated
of stainless steel, was installed. As well, the suction and discharge piping of the screw
removal system was a combination of carbon steel and PVC. The piping was replaced
with stainless steel. The motor which operates the sweeper collection mechanism had
-3 -
In response the District has increased staff, critical parts inventory, equipment inventory,
made plans to better address extreme conditions, upgraded critical equipment, planned
back up or alternative operations, and requested better responsiveness from sub
contractors. Responses are continuous and increasing.
The District is keenly aware of and has been very responsive to increasing environmental
awareness. House Bill 1160, Clean Water Act of 1999, ratified by the North Carolina
General Assembly on July 20th and signed into law July 21st by the governor, has
heightened this awareness. This bill codified as Chapter 329 session laws became
effective October 1999.
2. WWTP:
Overall performance for 2006 was good. There were no NPDES permit limits violations.
(See below) There were no monitoring or reporting violations.
Rotary Distributor Number Two. Installed several years before number one, number two
rotary distributor has a defective bearing that had to be replaced. A crane had to be
rented and the unit completely disassembled. The new bearing was installed, which took
several laborers a couple of days.
Effluent Polymer Project. There has been a polymer feed system located near the
effluent end of the treatment process for several years. It is used for solids washout under
varying conditions. The original system was set up hurriedly in response to tliis
condition and without much thought and preparation. Because this process is of
intermittent use and used only in specific situations, this system had a lot of down time.
-4 -
Rotary Distributor Number One. The existing unit was approximately 25 years old. It
was constructed of carbon and galvanized metal. The environment had deteriorated it
severely. The replacement unit is made entirely of stainless steel and should hold up to
the elements better. Hydraulics through the unit are used to propel it. This is an
electrical cost saving. There are pumps associated with the distributor for use during low
flows or when other operational parameters call for the need. The replacement unit was
designed to operate at lower flows to negate the need for pump assistance under these
circumstances. Increased preventative maintenance scheduling, more frequent arm
flushing and orifice cleaning should maximize the money spent on the distributor in
return of longevity.
Influent Pump Station Pump Controller. This system operates pump sequence and speed
between four pumps. The pumps are 25, 40, and two 60 horsepower. The sequence and
speed depends on the amount of flow coming into the plant. The controller installed in
2006 has a software program which makes the system more reliable and easier to adjust.
Also, the system was designed with a minimum amount of fail points and a maximum
amount of dependability. It has a primary water level sensing device with two
independent back-ups. The system is has battery back-up. In the event of power loss, it
will keep running. If the controller system senses any kind of problem, it will switch to a
back-up controller automatically and provide notification of the change. The entire
system is SCADA compatible. Operational information and alarms are monitored via
computer located in the operations building control room.
been subjected to water submersion and burned up over the years during periods of high
flows. To remedy this situation, the drive mechanism was retrofitted with an extended
sprocket system and chain. This allowed the motor to be relocated above the flood area.
Secondary System. The secondary biological treatment system consists of three 500,000
gallons tanks and two one million gallons tanks. It is the second biological process in the
treatment system. These tanks are routinely drained one at a time and inspected for
repairs. In 2006, these tanks were randomly drained and inspected. One of the 500,000
gallon tanks, aeration basin number two, had some deteriorated flanges. The flanges are
located on pipe work that supports management of the system. A failure during operation
could have been detrimental to overall treatment process. Flanges were ordered and
replaced. The system is back fully operational.
Trickling Filter Isolation Valves. These valves isolate the trickling filters allowing
preventative maintenance or maintenance to be done to the rotary distributors. Before the
valves were replaced, the filters had to be bypassed, pumped around for work to be
performed. Setting the pump up and connecting pipe was very labor intensive and took a
good while to accomplish. Pump rental was expensive, also. When bypass pumping
around a filter for isolation, extreme care had too be taken to avoid a spill. Not only
during the pump time but also in the dismantling of the bypass pump pipe. The
installation of these valves turned a very labor intensive job into a relatively simple one.
It also eliminated the pump rental cost and the chance of spillage. The valves were
stainless steel. They should be more durable and stand up to the environmental
conditions better. To help keep these valves in good operable shape, they are exercised
on a regular basis.
-5 -
12” pump installation. The 12inch pump installed at the head-works of the plant in 2000
remains a valuable tool in preventing spills. In the event of high flows or maintenance
repairs, water can be removed to two abandoned secondary clarifiers. These clarifiers
were taken off-line in the early eighties after plant upgrades. They were originally used
for stabilized biosolids storage. The capacity was increased by extending a wall up from
where the weir overflows were when used as secondary clarifiers. This increased the
storage capacity of the two tanks to 750,000 gallons. After a dedicated biosolids tank
SC A DA (Supervisor Control and Data Acquisition) system work. SC AD A is a
computer-based program. It brings site information into the central operations center.
SCADA is a useful tool by providing monitoring information to be used for more
efficient plant operation. It also brings remote site alarms into the operations center,
which provides better control over plant problems.
Million Gallon Tank (MGT). The million gallon tank (MGT) is used in the biosolids
stabilization process. It stores all stabilized solids until moved out for the land
application process. The tank is constructed of bolted in place, seamed glass lined
panels. It also has a cathode rod floor system to help attract chemistry that would attack
the panels. The manufacturer suggests preventative maintenance inspection on 10 year
intervals. The tank was recently 20 years old and an inspection was scheduled. The
inspection revealed the need for some repairs. All the horizontal and vertical seams
needed to be stripped of old coating, treated with a rust inhibitor, and recoated. Also, the
protective cathode system needed too be replaced. On-site staff was to prepare the tank
by emptying the contents of the tank and doing a general cleaning. Plant staff was also
responsible for renting a crane for placing equipment in and back out of the tank. Staff
also rented a scissor lift to reach all the seams to be repaired. (The tank is nearly 20 feet
tall.) This was followed up with power washing the seams. The manufacturer’s
contractor was hired to complete the seam work and cathodic system installation. Also
repaired was a small leak that had developed along one of the seams. In addition, some
minor dings along the lower outside panels were patched. In all the repair process lasted
approximately three weeks at a cost of about $21,000. This price does not include staff
labor.
When needed, extensive clean up and/or parts replacement was required each time of
need. This was an awkward situation because when running was necessary, it was
needed immediately. To remedy this situation, the entire process was reworked to
provide better, more efficient and more reliable service. The pump and gearbox were
mounted on a horizontal stand. Then a bulk storage tank was added for more chemical
capacity. This setup provided for flooded suction to the pump making it easier to feed to
the pump for dispensing polymer. The bulk tank also had a mixer installed to keep the
polymer from separating and being less effective. Added to the bulk tank as well were
high and low level cutoffs with a level indicator. The high cutoff was to prevent
overfilling and spills. The low level cutoff was to prevent the dispensing pump from
running dry and burning up. A second pump was installed to the process. It is used
strictly for the transfer of the polymer from delivery barrel to the bulk storage tank. The
gearbox on the dispensing pump was reduced to make the pump more efficient. The
dispensing pump was also installed with a coupling system. This along with a back-up
pump minimizes downtime in the event the on-line pump goes down. Finally the
building that houses the system was fitted with a heater for winter time use and a
ventilation system for summer. This setup provided a more environmentally friendly set
up for polymer.
SCADA work continued in 2006. The area of emphasis was the emergency generator
transfer switch and main motor control center. After the installation of a piece of
analyzer equipment in this area, it enabled much information to be monitored via
computer. Work also included improving the monitoring computer located in a control
room. Many graphs and trend charts were added to further help with monitoring the
status of plant site information. The monitoring computer was also reconfigured to make
it more user friendly.
The biosolids land application program ran smoothly in 2006. In the required annual
report to North Carolina division of Water Quality (NCDWQ) and the Environmental
Protection Agency (EPA), there were no deficiencies, spills, or violations. This included
-6-
This flood pump station has a back-up pump valving and pipe work installed independent
of this station. In the event of catastrophic flood pump or flood pump control panel
failure; treated water will continue to be removed from the plant. The pump is capable of
treating 8.5 million gallons per day or about 4 million gallons more than the average daily
flow in 2006. Plant maximum rated capacity is 8.3 million gallons per day. In 2006 the
pump was covered to help keep it protected and in better working condition. Lighting
was provided for nighttime operation. Also, a battery charger was installed to keep the
pump ready for use. The pump is exercised regularly to ensure performance.
Another means of spill control is with a back-up generator. The wastewater plant must
continue to run in the event of power interruptions from the power-supply company.
Power interruption can occur from equipment failure, road accidents, and weather events,
such as ice storms, electrical storms, tornadoes, and hurricanes. AlOOOkilo-watt
generator is on site for events and can supply enough generated power to run the entire
plant. In 2006 power supply was interrupted on 1 occasion for a total of 20 minutes.
With the use of the back-up generator power, 36,110 gallons of wastewater was
prevented from spilling. This along with the wastewater stored in equalization totals
31,546,236 gallons. Again at the average 2006 daily of 4.5 MGD, this would be 7.0 days
of flow.
was constructed, the two abandoned tanks were dedicated to spill containment. Once
stored, wastewater can be returned to the plant with an existing pump station. Some pipe
work has been added to this station and depending on conditions, water could be returned
as the tanks are filled. This further increases holding capacity or downtime, during
maintenance and repairs. In 2006, 5,139,911 gallons of wastewater were stored. Since
setup in 2000, 31,510,120 gallons of wastewater have been prevented from spilling. At
the average flow of 4.5 MGD in 2006, this would be 7.0 days of flow.
The wastewater plant is also equipped with emergency flood pumps. These pumps are
used in the event of high river levels, which prevent normal gravity flow out of the plant.
Without them, treated wastewater would have no way of exiting the plant and
consequently would flood the plant, causing extensive damage and long recovery. These
pumps are maintained and exercised on a regular basis to ensure proper operation for
times of urgency. This station is also equipped with local and remote SCADA high level
alarms. These alarms provide notification in the event of station failure. Enough
notification time is allowed to take remedial action before plant damage occurs. The
alarms are checked on a regular basis as well.
The emergency generator is also used to curtail. The District is under contract with
Dominion Power. From May 16th through September 30th (summer curtailment) and
from December 1 through March 3 lst (winter curtailment), Dominion can request the
wastewater plant to supply its own power for parts of the day during peak demand.
These requests usually come on the hottest days of summer and the coldest days of
winter. Dominion can then send power that the District would normally use to other
places of need. Winter requests are usually from 6am to Ham (5 hours) and summer
from 2pm to 9pm (7 hours). The contract is limited. In the winter requests to curtail are
limited to 13 or 65 hours and summer 19 or 133 hours. In 2006 the wastewater plant was
called to run all 19 times during the summer curtailment. There were no winter calls.
The District does incur the cost of diesel fuel. However, the rate structure the wastewater
plant has because of the contract off sets this cost and provides electrical energy savings.
An added benefit of this program is that it provides a means to exercise the generator.
This keeps the generator in better running condition and exposes any potential problem.
It would be better to find out a problem during a curtailment than an actual power outage.
By having the generator under a contracted quarterly preventive maintenance program
hopefully problems will be minimized or eliminated.
-I -
In 2006, industrial users were required to apply for permit renewal by December 2. Two
significant industrial users and 4 non-significant users applied for renewal. One
significant user did not apply due to a plant closing.
234 stabilization events at 12,750 gallons per event. This is 64% of the days in a year.
The wastewater plant has entered into agreement with area farmers for the use of their
land for biosolids application. The farmers in turn receive the nutrient value, moisture
content, soil remediation, and lime, which is a by-product of ph control in the treatment
process of the biosolids. If necessary, additional lime can be applied. There are 3100
acres, consisting of 128 fields, available in Halifax, Northampton, and Warren Counties.
All acreage was inspected, approved, and permitted by the State of North Carolina.
Using EP A approved treatment processes, 3,412,500 gallons of stabilized biosolids were
safely applied to area lands, consisting of 6 fields and 243 acres, for beneficial reuse.
Cost of this application process was approximately $73,000. Cost of treatment to
stabilize solids is separate. Land that grew fescue, rye, and wheat were applied to. The
amount applied in 2006 is up nearly 17% from the previous year. Charges for application
are based on gallons. In an attempt to save application costs, biosolids are thickened as
much as can possibly be handled. The removed water is returned to the treatment plant.
Also, once biosolids are placed in storage for land application, water is further separated.
This water along with environmental water (rain, snow, etc) is decanted and returned to
the treatment plant. In 2006, 532,548 gallons was decanted, at savings of $15,656.91.
Although 3100 acres of land is permitted and storage of 1,000,000 gallons is available, at
times application is difficult due to weather conditions, crop status, and crop rotation.
Owning land would provide an outlet for these times. In 2004, the District purchased a
suitable land application site. It is located in Northampton County where the District
already has farmer owned land permitted. In 2006, the contract for the biosolids land
application program with the current contract applier was to expire. In an attempt to
obtain the best price for the application process, bid specifications were drawn up. The
bid process attracted four contractors, who submitted bid packages. After analysis, an
award was offered to Synagro, the current contract applier.
Since purchasing the land investment improvements in 2006 occurred to ready the area
for application of biosolids. Some of these improvements are additional fence and
gating, additional rock for access road, weed removal from fence, tree removal from pond
dam, fertilizing, disking, Bermuda sprigging and removal of an abandoned house.
Improvements were in excess of $26,000. Also, the current land application permit was
modified to include this land for biosolids application. As a result of this, a
neighborhood meeting was held in October to introduce and explain the process of
biosolids application.
In 2006 the industrial pretreatment program had oversight of three significant industrial
users. One user has a categorical discharge pipe. Four non-significant industrial users
are permitted to send flow to the wastewater plant. Significant and non-significant status
is determined in part by the volume of flow discharged and the pollutants in the
discharge. The pollutants, carried by certain industrial wastes, determine the categorical
status of an industry. In 2006 there were no significant industrial users in significant
non-compliance; a status based on the number and types of violations of a permit. There
were three violations of permits. There was one pH, and one Oil and Grease violation.
One significant industry was purchased by another company and one significant industry
was closed, ceasing discharge. One non-significant industrial user added another shift to
their work week.
On March 16, 2006, a luncheon workshop was held in order to provide industries with
information regarding the permit renewal applications and permit conditions. The two
significant industrial users and one non-significant user had representatives present. Two
staff members with the Division of Water Quality were also present.
Another testing requirement of the NPDES permit is the annual priority pollutant analysis
(APPA). As indicated, it is an annual test that checks the effluent for conventional and
non-conventional compounds, total recoverable metals, volatile organic compounds,
acid-extractable compounds, and base-neutral compounds. These substances, if found in
sufficient quantity, could be harmful to the wastewater plant, receiving stream, and the
public. To date, no substances have been found in significant quantity to cause harm.
The test is done seasonally over the term of a five year NPDES permit.
The pretreatment annual report (PAR) was submitted to the state pretreatment unit on
February 7, 2006 and was accepted as having met ail criteria required by pretreatment
regulations. A letter of April 3, 2006 was received stating review of the PAR indicates
the report in good order and satisfied the requirements of the North Carolina Pretreatment
Program.
In 2006, money was budgeted to create a new position. Under the pretreatment program,
a pretreatment technician was established to manage the FOG ordinance. In July, the
position was filled. Since then several steps of the ordinance have been put into place.
Site visits of local restaurants began with introduction of the coordinator. The purpose of
the coordinator was explained. Inspections were begun to see if grease interceptors were
in place, installed properly and if regular cleaning with record retention was taking place.
Site drawings of the restaurants were also made. And, a database was started for tracking
all of the visitations and recording all findings. In addition, a public education program
was introduced. Advertisements in the local newspaper and on television were started.
The wastewater plant now has a general storm water permit. It was received through an
application process as required by the North Carolina Division of Water Quality. A
-8-
A requirement of the wastewater plant through its NPDES permit is quarterly chronic
toxicity testing. The test involves using a predetermined amount of effluent along with a
macroscopic organism. Ceriodaphnia are placed in the effluent and must survive and
reproduce for a specific length of time. Results of the test are either pass or fail. A pass
indicates the absence of substances in the effluent which may be harmful or threaten
aquatic life. The wastewater plant has been required to test for chronic toxicity since
April of 1993. To date only one test has received a fail result. This occurred in July
2001. In addition, as a part of permit renewal in 2006, an additional species must be
tested. The waste water plant used fathead minnow. The test was performed seasonally
and the results, all favorable, were submitted with the permit renewal information.
The North Carolina Division of Water Quality Laboratory Section inspected the
laboratory on June 6, 2006. The laboratory is now implementing all recommendations
and comments outlined in the inspection report. A letter dated July 20, 2006, from the
laboratory section, stated all requirements had been met.
In 2006, the wastewater NPDES permit came up for renewal. North Carolina Division of
Water Quality requires specific information and data for analysis in structuring a new
permit. The submittal package is due 180 days before permit expiration. All required
information was submitted in October 2006.
Last year the Sanitary District adopted a Fat, Oil, and Grease (FOG) ordinance. Its
adoption was a direct result of the NPDES permit process which required the
implementation of measures to address sanitary sewer overflows (spills). Fats, oils, and
grease (FOG), if placed in the sanitary collection system can over a period of time build
up and clog pipes causing spills.
The North Carolina Division of Water Quality performed its annual inspection of the
pretreatment program April 27, 2006. A letter of May 2, 2005 was received
complementing the program on the organization, documentation, and time management
instituted within the program.
Permit limit violation
-9-
In part, due to the awareness and training from the safety program, there were no loss
work days in 2006. There were also no reportable incidents or accidents.
requirement of this permit is a written storm water management plan. The plan is used to
evaluate potential pollution sources and to select and implement appropriate methods to
prevent or control the discharge of pollutants to stormwater runoff. As a part of the plan,
semiannual preventative maintenance evaluations and semiannual inspections of site
runoff areas are required.
The District has an emergency response team. The formation of the team arose from
chemicals, chlorine, and sulfur dioxide stored on site. Another factor for its formation
was the lack of any other agency in the immediate area to deal with these chemicals. The
team meets and has drill practices regularly. The team is fully equipped and trained to
handle emergencies which may arise from the use of chlorine and sulfur dioxide.
The Division of Water Quality conducted their annual review of the wastewater plant on
November 14, 2006. A comprehensive site inspection was conducted. The site
inspection went well. The evaluation report received on November 17, 2006 stated the
plant was in compliance. There were no recommendations or corrections. The report
also noted that the wastewater treatment plant had established a sound storm-water
program and was implementing it.
After years of preparation, the District called OSHA and requested consultative
inspections to help maintain a safe work place for its employees. After a series of
inspections from OSHA safety and health officers, the District met all requirements of
compliance by correcting all hazards identified during consultative visits and by
developing an occupational safety and health management system. Once met, the
District was eligible for the SHARP (Safety and Health Achievement Recognition
Program) Award. Again in 2006, the wastewater plant requested an OSHA consultative
inspection. Deficiencies were exposed and corrected. As a result, this year marked the
fifth straight year the waste water plant was in the SHARP Program. With this
achievement, NCDOL (North Carolina Department of Labor) grants exemption from
programmed OSHA compliance inspections for a specified period of time. It is a
compliment to the dedication and continued hard work of the administration and staff It
serves also as a testament to the commitment of the company for the protection of the
employees and surrounding community.
The safety program within the District is very active and assertive in its approach to the
protection of the employees and surrounding citizens. The program consists of a safety
officer, safety committee, incident/accident committee and appeals committee. The
safety officer sets up the monthly safety meetings, coordinates the activities of the safety
committee, keeps up with safety regulations, and many other various safety activities.
The safety committee prepares safety policy programs and updates current ones. They
also do site inspections and produce potential hazard punch lists. The safety committee
and safety officer also keeps up with and prepares for updating regulations and
integrating new regulations of OSHA. The incident/accident committee reviews all
potential accidents and accidents. The appeal committee follows up the safety committee
recommendation at the request of an employee. The attempt is to minimize the
seriousness of an accident and ultimately prevent accidents.
B. By month, list of the number and type of any violations of permit conditions,
environmental regulations, or environmental laws, including (but not limited to):
1. C.S.: None
Monitoring and Reporting Violations
Sanitary Sewers Overflows (SSO)
2. WWTP: N/A
Bypass of Treatment Facility
1.C.S.: N/A
C. Description of any known environmental impact of violations.
D. Description of corrective measures taken to address violations or deficiencies.
- 10-
1.
2.
C.S.: None
WWTP: None
Some of the work done to prevent problems is the identification of potential spill areas.
Once identified, arrangements are made to stop or minimize and contain.
2. WWTP:
There was no (0) reportable bypass of the treatment facility in which more 1000 gallons
of wastewater reached surface waters in 2006.
I. C.S.:
Preventive maintenance cleaning with Jet Vac, 5/16'’ sewer rod with cutters using 3 '/2 HP
sewer rod machine and using TV camera. Manhole repairs and spot line repairs. We also
used BioNomics to clean and TV Outfall G from Roanoke River Outfall to the
wastewater treatment plant. Plus the Roanoke Rapids Sanitary Dist. Crews cleaned &
TV’ed 10 miles of sewerlines. BioNomics inspected M/H’s, TV’ed, and cleaned. Plus
L&J Contractors smoked, TV’ed, cleaned, and did some Pipe Bursting & Point Repairs a
total of 7 miles, making it a total of 17 miles between all 3 companies. We also put our
6’' Silent Pump at Belmont Pumping Station to prevent SSO’s at 4th and laurel Street.
2. WWTP: None
1. C.S.: None
2. WWTP: None
2. WWTP:
The WWTP is very aggressive in reacting to violations and identifying potential
deficiencies. Once identified, plans are made to upgrade or replace potential deficiencies,
which may result in violation. Modifying operations, training operators, laboratory
training, improved equipment, maintenance inventory parts and equipment and raising
awareness is also an on-going and continuous process.
1. C.S.: There were 11 reportable SSO in 2006.
1. 01/14/2006 - Greenbrier Pump Station 480 gallons
2. 02/07/2006 - M/H at end of Downsbrook Dr. 300 gallons
3. 04/17/2006 -400 block of Marshal] and Carolina Street 750 gallons
4. 04/19/2006 - Gail Drive in Greenbrier Subdivision 200 gallons
5. 06/14/2006 - M/H at 4,h and Laurel Street 12,600 gallons
6. 07/05/2006 - M/H at the comer of Laurel and 4lh Street 1,800 gallons
7. 07/13/2006 - M/H at 4lh and Laurel Street 2400 gallons
8. 09/01/2006 - M/H #46 at River Road South 2880 gallons
9. 09/01/2006 - M/H upstream of Belmont Pump Station 3000 gallons
10. 11/16/2006 - M/H upstream of Belmont Pump Station
11.11/16/2006 - River Road South 5400 gallons
-11 -
A valve exercise program is now employed. It keeps valves in good working order. In
the event of routine maintenance, equipment problems, or emergencies, valves used to
address these issues are in a state of readiness.
Isolation valves were installed in 2006 on both trickling filters. Now removing these
units for maintenance and repairs will negate the need for bypass pumps and piping. This
will eliminate the chance for spills while pumping and dismantling after use.
The Stormwater Pollution Prevention Plan (SPPP), implemented in 2006, will be a
valuable tool in identifying deficiencies. It incorporates awareness and training not only
to all plant personnel, but also vendors and contractors. The plan allows for scheduled
identification of deficiencies before they become problems.
There are various alarms throughout the plant site. However, if they malfunction they are
of no value. In an attempt to keep functioning alarms, they are tested on a regular basis.
The rag auger installed a few years ago has a bottom bearing which leaks. The leak is on
top of the concrete pad where it is mounted. The leak could not be stopped. So there was
a deflector shield made and installed to divert the leakage back into the sewer system.
A polymer feed pump station remains on line to help with solids washout at times of high
flows. In 2006, this pump station was rebuilt and completely re-modified. Now this
station is much more user friendly, has more chemical capacity, and is much more
efficient. In addition, operational strategies have been put in place to minimize solids
wash out at times of high flow. And as described in performance section “II”, a 12”
pump is in place to retain flows that might otherwise reach surface water. This setup
continues to be a valuable tool each year in preventing spills. And in retaining high flows
in equalization tanks this helps with solids wash out also.
The Fat, Oil, and Grease (FOG) program, which began as a committee, advanced to an
ordinance, and now has a full-time employee to administer the program. The goal is to
prevent FOG from entering the collection system causing blockage problems resulting in
spills. The wastewater plant will benefit by having less FOG to handle and chemically
treat.
Identifying and eliminating inflow and infiltration (I&I) is an on-going and difficult task.
It is important to stop or minimize to take unnecessary flows off of the treatment plant.
However, it is also important to address because excess I&I can “dilute” incoming waste.
Diluted wastewater makes it more difficult to meet percent removal requirements (85%)
of the plants permit. In 2006, more areas were identified and addressed to help resolve
this problem.
III.NOTIFICATION
IV.
- 12-
Reduce
Recycle
Satisfy
Develop
DateR. Danieley Brown, PE
Chief Executive Officer
A. A condensed, summarized version of this report will accompany the annual water report
which will be distributed to the users and customers of the Roanoke Rapids Sanitary
District via mail. The full report will be available at the main office upon request.
CERTIFICATION
A. I certify under penalty of law that this report is complete and accurate to the best of my
knowledge. I further certify that this report has been made available to the users of the
named system and that those users have been notified of its availability.
lUJ'
November 17, 2006
Dear Mr. Brown:
If you have any questions or comments, please call me at 919-791-4255.
On November 14, 2006 Myrl Nisely of the Raleigh Regional Office conducted an annual
compliance inspection of the Sanitary District WWTP facility. A stormwater compliance inspection
was also carried out. Thanks to Greg Camp and Greta Glover for their assistance.
Raleigh Regional Office
Water Quality Section
cc: RRO/SWP files
Central Files
Mr. R. Danieley Brown, CEO
Roanoke Rapids Sanitary District
P.O. Box 308
Roanoke Rapids, NC 27870
Michael F. Easley, Governor
William G. Ross Jr., Secretary
nvironment and Natural Resources
Alan W. Klimek, P.E. Director
Division of Water Quality
1628 Mail Service Center
Raleigh. NC 27699-1628
phone (919) 791-4200
facsimile (919) 571-4718
Customer Service
1-877-623-6748
Subject: Compliance Evaluation Inspections 11/14/2006
Roanoke Rapids Sanitary District
NPDES Permit No. NC0024201
and Stormwater Permit No. NCG110091
Halifax County
NCDEM
Sincerely,
Myrl A. Nisely *
Environmental Chemist
NC0024201
The plant was in compliance. Findings during the inspection are shown on the attached checklist.
Please note the comments that follow some topics. From this site visit I will prepare a staff report
for input to the pennit writers as they renew the permit.
North Carolir^^^partme^^Ei
NCG110091
The plant has established a sound stormwater program and is implementing it. See the attached
checklist.
CO /|A1 I 1/^
OU ip
EPA
NPDES
12lNCOO242O1
21| | I I I I I
Entry Time/Date Permit Effective Date
03/10/0109:25 AM 06/11/14Roanoke Rapids WWTP
Exit Time/Date Permit Expiration Date135 Aqueduct Rd
Roanoke Rapids NC 27870 07/03/3111:10 AM 06/11/14
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)Other Facility Data
Alan Gregg Camp/ORC/919-536-4884/
Name, Address of Responsible Official/Title/Phone and Fax Number
Flow Measurement Records/Reports
Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date
RRO WQ//919-791-4200/
Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page #1
3l
United States Environmental Protection Agency
Washington, D.C 20460
yr/mo/day
06/11/14
Contacted
No
QA
72 LJ
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Facility Self-Monitoring Evaluation Rating70 u
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Operations & Maintenance
Fac Type
20U
Inspection Type
181£]J17
Myrl Nisely
Signature of Management Q A Reviewer
Inspector
19Ld
Inspection Work Days
671 I 69
—Reserved-----------------------
75l I I I I I I I80
Transaction Code
1 LJ 2 EJ J11
Bl
71 LJ
_______________________________________________Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Remarks
| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |6€
Permit
J Self-Monitoring Program
JE Laboratory
73 LU74
R Danieley Brown,PO Box 308 Roanoke Rapids NC
27870/Z252-537-9137/2525379136
Water Compliance Inspection Report
Section A: National Data System Coding (i.e., PCS)
EPA
NPDES
NCG110091
6?l
Entry Time/Date Permit Effective Date
05/10/1409:25 AM 06/11/14Roanoke Rapids WWTP
Exit Time/Date Permit Expiration Date135 Aqueduct Rd
Roanoke Rapids NC 27870 08/07/3011:10 AM 06/11/14
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Storm Water
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date
RRO WQ//919-791-4200/
I l/lblob
Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page #1
3l
Inspection Work Days
I 69
United States Environmental Protection Agency
Washington, D C 20460
Contacted
No
yr/mo/day
06/11/14
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Remarks
21| | I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I | | I66
QA
72 LJ
Facility Self-Monitoring Evaluation Rating70 u
Inspection Type
18LJ
Fac Type
20U
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
J11
Inspector
19Ld12l
-------Reserved------------------------
75l I I I I I I I8073 LU74
Bl
7U
Transaction Code
1 LJ 2LJ
Water Compliance Inspection Report
Section A: National Data System Coding (i.e., PCS)
R Danieley Brown,PO Box 308 Roanoke Rapids NC
27870/Superintendent/252-537-9137/2525379136
J17
Myrl Wisely
Signature of Management Q A Reviewer
Operations & Maintenance Yes No NA NE
■ Is the plant generally clean with acceptable housekeeping?
Comment:
Yes No NA NERecord Keeping
■ Are records kept and maintained as required by the permit?
■ Is all required information readily available, complete and current?
■ Are all records maintained for 3 years (lab. reg. required 5 years)?
■ OAre analytical results consistent with data reported on DMRs?
■ Is the chain-of-custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
■ Are DMRs complete: do they include all permit parameters?
■ Has the facility submitted its annual compliance report to users and DWQ?
■ (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator on each shift?
■ Is the ORC visitation log available and current?
■ Is the ORC certified at grade equal to or higher than the facility classification?
■ Is the backup operator certified at one grade less or greater than the facility classification?
■ Is a copy of the current NPDES permit available on site?
■ oFacility has copy of previous year's Annual Report on file for review?
Comment:
Permit Yes No NA NE
■ (If the present permit expires in 6 months or less). Has the permittee submitted a new application?
■ Is the facility as described in the permit?
■ # Are there any special conditions for the permit?
■ Is access to the plant site restricted to the general public?
Page #3
Permit: NC0024201
Inspection Date: 11/14/2006
Owner - Facility: Roanoke Rapids VWVTP
Inspection Type: Compliance Evaluation
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settieable Solids, pH, DO, Sludge ■
Judge, and other that are applicable?
Permit: NC0024201
Inspection Date: 11/14/2006
Yes No NA NEPermit
■ 0Is the inspector granted access to all areas for inspection?
New discharge point Latitude 36 26 13, Longitude 77 36 37Comment:
Yes No NA NEBar Screens
Type of bar screen
a.Manual
b.Mechanical
■ Are the bars adequately screening debris?
■ Is the screen free of excessive debris?
■ Is disposal of screening in compliance?
■ Is the unit in good condition?
Yes No NA NEGrit Removal
Type of grit removal
a.Manual
b.Mechanical
■ Is the grit free of excessive organic matter?
■ Is the grit free of excessive odor?
■ o# Is disposal of grit in compliance?
Yes No NA NEPrimary Clarifier
■ Is the clarifier free of black and odorous wastewater?
■ Is the site free of excessive buildup of solids in center well of circular clarifier?
■ Are weirs level?
■ Is the site free of weir blockage?
■ Is the site free of evidence of short-circuiting?
■ Is scum removal adequate?
■ Is the site free of excessive floating sludge?
■ Is the drive unit operational?
Page #4
Owner - Facility: Roanoke Rapids WWTP
Inspection Type: Compliance Evaluation
Comment: An old Detritor scraper grit chamber has been refurbished to provide
backup to the vortex grit unit. This will be added to the description of the plant in the
RRO staff report.
Comment: The mechanical bar screen serves most of the time, but the manual serves
as backup, with modern disposal equipment.
Yes No NA NEPrimary Clarifier
■ Is the sludge blanket level acceptable?
■ Is the sludge blanket level acceptable? (Approximately % of the sidewall depth)
Yes No NA NETrickling Filter
■ Is the filter free of ponding?
■ Is the filter free of leaks at the center column of filter's distribution arms?
■ Is the distribution of flow even from the distribution arms?
■ 0Is the filter free of uneven or discolored growth?
■ 0Is the filter free of sloughing of excessive growth?
■ 0 Are the filter's distribution arms orifices free of clogging?
■ Is the filter free of excessive filter flies, worms or snails?
Comment:The second unit was back in service after recently being refurbished.
Yes No NA NEAnaerobic Digester
Floating coverType of operation:
■ Is the capacity adequate?
■ # Is gas stored on site?
■ Is the digester(s) free of tilting covers?
■ Is the gas burner operational?
■ Is the digester heated?
■ Is the temperature maintained constantly?
■ Is tankage available for properly waste sludge?
Comment:
Aeration Basins Yes No NA NE
Plug flowMode of operation
DiffusedType of aeration system
■ Is the basin free of dead spots?
■ Are surface aerators and mixers operational?
■ Are the diffusers operational?
■ Is the foam the proper color for the treatment process?
Page #5
Owner - Facility: Roanoke Rapids VWVTP
Inspection Type: Compliance Evaluation
Permit: NC0024201
Inspection Date: 11/14/2006
Comment: Underflow is taken to the anaerobic digester, the overflow goes to the
trickling filters.
Permit: NC0024201
Inspection Date: 11/14/2006
Aeration Basins Yes No NA NE
■ Does the foam cover less than 25% of the basin's surface?
■ Is the DO level acceptable?
■Is the DO level acceptable?(1.0 to 3.0 mg/l)
Comment:
Yes No NA NESecondary Clarifier
■ Is the clarifier free of black and odorous wastewater?
■ Is the site free of excessive buildup of solids in center well of circular clarifier?
■ Are weirs level?
■ Is the site free of weir blockage?
■ Is the site free of evidence of short-circuiting?
■ Is scum removal adequate?
■ Is the site free of excessive floating sludge?
■ Is the drive unit operational?
■ Is the return rate acceptable (low turbulence)?
■ Is the overflow clear of excessive solids/pin floc?
■ Is the sludge blanket level acceptable? (Approximately 1/« of the sidewall depth)
Comment:
Yes No NA NEFlow Measurement - Effluent
■ # Is flow meter used for reporting?
■ Is flow meter calibrated annually?
■ Is the flow meter operational?
■ (If units are separated) Does the chart recorder match the flow meter?
Comment:Meter last calibrated 8/9/06
Yes No NA NEEffluent Pipe
■ Is right of way to the outfall properly maintained?
■ Are the receiving water free of foam other than trace amounts and other debris?
■ If effluent (diffuser pipes are required) are they operating properly?
Comment:
Yes No NA NEDrying Beds
■ Is there adequate drying bed space?
Page #6
I
Owner - Facility: Roanoke Rapids WWTP
Inspection Type: Compliance Evaluation
Drying Beds Yes No NA NE
■ Is the sludge distribution on drying beds appropriate?
■ Are the drying beds free of vegetation?
■ # Is the site free of dry sludge remaining in beds?
■ Is the site free of stockpiled sludge?
■ Is the filtrate from sludge drying beds returned to the front of the plant?
■ # Is the sludge disposed of through county landfill?
■ # Is the sludge land applied?
■ (Vacuum filters) Is polymer mixing adequate?
Comment:Clean, well maintained
Pump Station - Effluent Yes No NA NE
Is the pump wetwell free of bypass lines or structures?■
■ Are all pumps present?
■ Are all pumps operable?
■ Are float controls operable?
■ Is SCADA telemetry available and operational?
■ Is audible and visual alarm available and operational?
Disinfection-Gas Yes No NA NE
■ Are cylinders secured adequately?
■ Are cylinders protected from direct sunlight?
Is there adequate reserve supply of disinfectant?■
Is the level of chlorine residual acceptable?■
■ oIs the contact chamber free of grov/th, or sludge buildup?
■ Is there chlorine residual prior to de-chlorination?
Does the Stationary Source have more than 2500 lbs of Chlorine (CAS No. 7782-50-5)?■
If yes, then is there a Risk Management Plan on site?■
If yes, then what is the EPA twelve digit ID Number? (1000-100000063968,)
10/30/2003If yes, then when was the RMP last updated?
Page #7
Permit: NC0024201
Inspection Date: 11/14/2006
Owner - Facility: Roanoke Rapids VWVTP
Inspection Type: Compliance Evaluation
Comment: Backup ("high river”) pumps are exercised monthly. A large mobile diesel
pump has been put on standby in case power is lost to the lift pumps due to failure
inside the control box. On idle this pump can handle the regular flow
Permit: NC0024201
Inspection Date: 11/14/2006
Disinfection-Gas Yes No NA NE
Comment:Plant has a Haz Mat team that trains monthly.
Yes No NA NEDe-chlorination
GasType of system ?
■ Is the feed ratio proportional to chlorine amount (1 to 1)?
■ Is storage appropriate for cylinders?
■ # Is de-chlorination substance stored away from chlorine containers?
Comment:
■ Are the tablets the proper size and type?
■ Are tablet de-chlorinators operational?
Number of tubes in use?
Comment:
Yes No NA NEStandby Power
■ Is automatically activated standby power available?
■ Is the generator tested by interrupting primary power source?
■ Is the generator tested under load?
■ Was generator tested & operational during the inspection?
■ Do the generator(s) have adequate capacity to operate the entire wastewater site?
■ Is there an emergency agreement with a fuel vendor for extended run on back-up power?
■ Is the generator fuel level monitored?
Yes No NA NESolids Handling Equipment
■ Is the equipment operational?
■ Is the chemical feed equipment operational?
■ Is storage adequate?
■ Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
■ Is the site free of sludge buildup on belts and/or rollers of filter press?
■ Is the site free of excessive moisture in belt filter press sludge cake?
■ The facility has an approved sludge management plan?
Page #8
I
Owner - Facility: Roanoke Rapids VWVTP
Inspection Type: Compliance Evaluation
Comment: Generator can run entire plant. It is run every month, plus the treatment
plant has agreements with Dominion Power to supply power at critical times, as often as
13 times in the winter and 19 times in the summer. The generator is under a service
contract that checks and runs it every quarter.
Yes No NA NE
Laboratory Yes No NA NE
■ Are field parameters performed by certified personnel or laboratory?
■ Are all other parameters(excluding field parameters) performed by a certified lab?
■ # Is the facility using a contract lab?
■ Is proper temperature set for sample storage (kept at 1.0 to 4.4 degrees Celsius)?
■ Incubator (Fecal Coliform) set to 44.5 degrees Celsius+A 0.2 degrees?
■ Incubator (BOD) set to 20.0 degrees Celsius +/-1.0 degrees?
Influent Sampling Yes No NA NE
■ # Is composite sampling flow proportional?
■ oIs sample collected above side streams?
■ Is proper volume collected?
■ 0Is the tubing clean?
■ Is proper temperature set for sample storage (kept at 1.0 to 4.4 degrees Celsius)?
■ Is sampling performed according to the permit?
Comment:T = 0.7C
Effluent Sampling Yes No NA NE
■ Is composite sampling flow proportional?
■ Is sample collected below all treatment units?
■ Is proper volume collected?
Is the tubing clean?■
■ Is proper temperature set for sample storage (kept at 1.0 to 4.4 degrees Celsius)?
■ Is the facility sampling performed as required by the permit (frequency, sampling type representative)?
Comment:T=1.4C
Page #9
Permit: NC0024201
Inspection Date: 11/14/2006
Owner - Facility: Roanoke Rapids WWTP
Inspection Type: Compliance Evaluation
Comment: Sample storage = 2C, Fecal incubator = 44.5C, BOD incubator = 20C The
lab is no longer certified for Total Solids, a parameter that is not in the permit. There are
no plans to strive for certification.
Solids Handling Equipment
Comment: In addition to anaerobic vector reduction to meet 503 requirements, lime is
added to the stored sludge for odor abatement.
f - ^9 - c> fa
No.
3.
Facility
a.
b.
c.
Primary Discharge Point Location
a.
b.
c.Receiving Stream OK on Application
OK on Existing Permit or provide Receiving Stream or affected waters:
USGS Quadrangle Map name and number OK on Application
OK on Existing Permit £3, or provide USGS Quadrangle Map name and number:
c.
d.
County: Halifax
Permitee: Roanoke Rapids Sank Dist.
Application/ Permit No.: NC0024201
Staff Report Prepared By: Myrl Niselv
Date: 11/30/2006
To: NPDES Discharge Permitting Unit
Attn. NPDES Reviewer: Jim McKav
Date of site visit: 11/14/2006
Person contacted and telephone number: Greg Camp, 252-536-4884
Site visit conducted by: Myrl Wisely
Inspection Report Attached: [3 Yes or
or No.
Project Name:
SOC Priority Project? (Y/N) N If Yes, SOC No.
NPDES REGIONAL WATER QUALITY
STAFF REPORT AND RECOMMENDATIONS
(This form is best filled out on computer, rather than hard copy)
Keeping BIMS Accurate: Is the following BIMS information (a. through e. below) correct?
O Yes or No. If No, please either indicate that it is correct on the current application or the
existing permit or provide the details. If none can be supplied, please explain:
Fill this section only if BIMS or Application Info is incorrect or missins
Latitude/Longitude of Outfall (These are often inaccurate) OK on Application Q, (check at
http://topozone.com ) OK on Existing Permit Q, or provide Latitude: 36.26.13 Longitude:
77.36.36
Location Address: OK on Application Q,
OK on Existing Permit [3, or provide Location:
Latitude/Longitude (These are often inaccurate) OK on Application O, (check at
http://topozone.com ) OK on Existing Permit Q, or provide Latitude: Longitude:
Driving Directions OK on Application □,
OK on Existing Permit or provide Driving Directions (please be accurate):
A. GENERAL INFORMATION
1. This application is (check all that apply): Q New Renewal
O Modification
2. Was a site visit conducted in order to prepare this report? Yes
a.
b.
Stream Classification: Ca.
b.
c.
B. DESCRIPTION OF FACILITIES AND WASTE(S) (renewals and modifications only)
1.
2.
3.
4.
FORM: NPDES-RRO 06/03, 9/03 2
5. Are there any issues related to compliance/enforcement that should be resolved before issuing this
permit? O Yes or [XI No. If yes, please explain:
River Basin and Sub basin No.: Roanoke 23-(26)
Describe receiving stream features and downstream uses: Flow altered by releases from
hydroelectric dam
Landfilled? Yes O No^ If yes, where?
Other?
Adequate Digester Capacity? Yes [X No Q Sludge Storage Capacity? Yes XI No O
Please comment on current operational practices: See description at end of Attachment C of their
submittal
For NEW FACILITIES Proceed to Section C, Evaluation and Recommendations
(For renewals or modifications continue to section B)
NPofc REGIONAL WATER Q LIT^
STAFF REPORT AND RECOMMENDATIONS
Describe the existing treatment facility: Well maintained and well run plant with complex processes
that provide good quality effluent. Since losing several industrial inputs, they at times have influent
load concentrations so low that attaining 85% removal targets can be difficult (during wet weather). A
building boom in the area (Entertainment Center, especially) is expected to help provide more even
loadings in the near future.
Are there appropriately certified ORCs for the facilities? X Yes or XI No.
Operator in Charge: Greg Camp Certificate #6614 (Available in BIMS or Certification Website)
Back- Operator in Charge: Greta Glover Certificate # 9924
Does the facility have operational or compliance problems? Please comment: No
Summarize your BIMS review of monitoring data (Notice(s) of violation within the last permit cycle;
Current enforcement action(s)): None
Are they currently under SOC, XJ Currently under JOC, X Currently under moratorium X? Have
all compliance dates/conditions in the existing permit, SOC, JOC, etc. been complied with? X Yes
or X No. If no, please explain:
Residuals Treatment: PSRP X (Process to Significantly Reduce Pathogens, Class B) or
PFRP X (Process to Further Reduce Pathogens, Class A)?
Are they liquid or dewatered to a cake? Liquid
Land Applied? Yes X No X If so, list Non-Discharge Permit No. WQ0001989
Contractor Used: Synagro
C. EVALUATION AND RECOMMENDA TIONS
Other Disposal Options:
2.
3.
Reason
4.
5.
FORM: NPDES-RRO 06/03, 9/03 3
1. Alternative Analysis Evaluation: has the facility evaluated the non-discharge options available? Give
regional perspective for each option evaluated:
Spray Irrigation:
Connect to Regional Sewer System:
Subsurface:
List any items that you would like NPDES Unit to obtain through an additional information
request. Make sure that you provide a reason for each item:
Recommended Additional Information
NPoft REGIONAL WATER Q
STAFF REPORT AND RECOMMENDATIONS
List specific special requirements or compliance schedules that you recommend to be included in
the permit when issued. Make sure that you provide a reason for each special condition:
___________Recommended Addition_______
BIMS issue: A comprehensive listing of the all
treatment units would be helpful in BIMS.
Their suggested addition to the boilerplate (near
_______________Reason______________
Present description in BIMS notes only the
trickling filter
I suggest that this language be added to ALL
_______________Reason_____________
The change from Chockoyotte Creek to the
Roanoke River may justify the changes
List specific Permit requirements that you recommend to be removed from the permit when
issued. Make sure that you provide a reason for each condition:
___________Recommended Removal_____
Pending statistical analyses, their requests for
changes in sampling seem appropriate
I^LITY
Provide any additional narrative regarding your review of the application: Meeting the redundancy
requirements is a strength in this plant - bar screens, grit chambers, clarifiers, trickling filters and a
diesel pump on standby for "high river" discharge of effluent in case of switchbox failure. Is a
reliable plant.
end of the cover letter)boilerplate sections of NPDES permits.
Date:
D. ADDITIONAL REGIONAL STAFF REVIEW ITEMS
If next page is not used, PLEASE set printer for pages 1 through 3 to avoid wasting paper.
Use this page for facilities with more than one Discharge Pipe
Discharge Point: (Fill this section only if BIMS or Application Info is incorrect or missing)
d. Latitude/Longitude OK
e.
c.
Discharge Point: (Fill this section only if BIMS or Application Info is incorrect or missing)
4
a.
b.
6. Recommendation: O Hold, pending receipt and review of additional information by regional office;
O Hold, pending review and approval of required additional information by NPDES permitting
office; 0 Issue; O Deny. If deny, please state reasons:
NPD^S R^?IONAL WATER Q^LITY
STAFF REPORT AND RECOMMENDATIONS
on Application 0, (check at http://topozone.com These are often
inaccurate) OK on Existing Permit □, or provide Latitude: Longitude:
Stream Classification:
River Basin and Sub basin No.:
Describe receiving stream features and downstream uses:
b. Driving Directions OK on Application Q,
OK on Existing Permit Q or provide Driving Directions (please be accurate):
c. USGS Quadrangle Map name and number OK on Application □»
OK on Existing Permit QJ, or provide USGS Quadrangle Map name and number:
Receiving Stream OK on Application O,
OK on Existing Permit O, or provide Receiving Stream or affected waters:
a. Location OK on Application | |,
FORM: NPDES-RRO 06/03, 9/03
Reminder: attach inspection report if Yes was checked for 2 d.
X.l Q KI
Signature of WQS regional supervisor: ’
a. Location OK on Application [J,
OK on Existing Permit Q, or provide Location:
7. Signature of report preparer: