HomeMy WebLinkAboutWQ0043463_Final Permit_20240627
June 27, 2024
SANJAY B. SHAH – MEMBER
SANMARGI, PLLC
3682 RAEBURN COURT
FAYETTEVILLE, NORTH CAROLINA 28314
Subject: Permit No. WQ0043463
Family Dollar – Currie WWTF
Wastewater Irrigation System
Pender County
Dear Mr. Shah,
In response to your permit change of ownership request received on June 5, 2024, we are
forwarding herewith Permit No. WQ0043463 dated June 27, 2024, to SANMARGI, PLLC for the continued
operation of the subject wastewater treatment and irrigation facilities.
This permit is effective from the date of issuance through December 31, 2029, shall replace Permit
No. WQ0043463 issued on December 9, 2022, and is subject to the conditions and limitations therein. The
Permittee shall submit a renewal application no later than July 4, 2029.
Please pay attention to the monitoring requirements listed in Attachments A, B, and C for they may
differ from the previous permit issuance. Failure to establish an adequate system for collecting and
maintaining the required operational information may result in future non-compliance.
The Division has removed the following permit conditions since the last permit issuance dated
December 9, 2022:
➢ Old Condition I.1 – The Division has removed this condition because the Permittee submitted
the Final Engineering Certification on May 1, 2023.
➢ Old Condition I.2 – The Division has removed this condition because the Wilmington Regional
Office has conducted a start-up inspection.
➢ Old Condition I.3 – The Division has removed this condition because the Wilmington Regional
Office has approved monitoring well MW-1.
➢ Old Condition I.4 – The Division has removed this condition because the Permittee submitted
a site map on May 1, 2023.
➢ Old Condition I.5 – The Division has removed this condition because the Permittee submitted
a Well Construction Record (Form GW-1) on March 16, 2023.
➢ Old Condition I.6 – The Division has removed this condition because the Permittee submitted
a Final Operation and Maintenance Plan on May 1, 2023.
Mr. Sanjay B. Shah
June 27, 2024
Page 2 of 3
➢ Old Condition I.7 – The Division has removed this condition because the Permittee submitted
a follow-up soil evaluation on May 1, 2023.
➢ Old Condition II.3 – The Division has removed this condition because the Permittee has
completed construction of monitoring well MW-1.
➢ Old Condition II.11 – The Division has removed this condition because the Permittee owns all
the irrigation sites.
➢ Old Condition IV.10 – The Division has removed this condition because the Permittee has
completed initial sampling of monitoring well MW-1.
The following permit conditions are new or modified since the last permit issuance dated
December 9, 2022:
➢ Condition III.7 – The Division has modified this condition to require annual testing and
calibration of irrigation equipment.
➢ Condition IV.7 – The Division has modified the record keeping duration for this condition from
five years to eight years because this permit renewal shall be for eight years per 15A NCAC
02T .0111(e).
➢ Condition IV.8 – The Division has modified the record keeping duration for this condition from
five years to eight years because this permit renewal shall be for eight years per 15A NCAC
02T .0111(e).
➢ Condition V.2 – The Division has modified the record keeping duration for this condition from
five years to eight years because this permit renewal shall be for eight years per 15A NCAC
02T .0111(e).
➢ Condition VI.10 – This condition requires the Permittee to pay an annual fee for each year of
the term of this permit.
This permit can be contested as provided in Chapter 150B of the North Carolina General Statutes
by filing a Petition for a Contested Case Hearing (Petition) with the North Carolina Office of Administrative
Hearings (OAH) within 30 calendar days. Requirements for filing a Petition are set forth in Chapter 150B
of the North Carolina General Statutes and Title 26 of the North Carolina Administrative Code. Those
interested in filing may access additional information regarding the requirements for filing a Petition and
Petition forms at the OAH website or by calling the OAH Clerk’s Office at (919) 431-3000. A party filing
a Petition shall serve a copy of the Petition on the Department of Environmental Quality’s Office of General
Counsel at 1601 Mail Service Center, Raleigh, NC 27699-1601. If the party filing the Petition is not the
Permittee, then the party shall also serve the Permittee pursuant to G.S. 150B-23(a).
Mr. Sanjay B. Shah
June 27, 2024
Page 3 of 3
If you need additional information concerning this permit, please contact Leah Parente at (919)
707-3656 or leah.parente@deq.nc.gov.
Sincerely,
Richard E. Rogers, Jr., Director
Division of Water Resources
cc: Pender County Health Department (Electronic Copy)
Wilmington Regional Office, Water Quality Regional Operations Section (Electronic Copy)
Laserfiche File (Electronic Copy)
Digital Permit Archive (Electronic Copy)
THIS PAGE BLANK
WQ0043463 Version 1.1 Shell Version 230725 Page 1 of 9
NORTH CAROLINA
ENVIRONMENTAL MANAGEMENT COMMISSION
DEPARTMENT OF ENVIRONMENTAL QUALITY
RALEIGH
WASTEWATER IRRIGATION SYSTEM PERMIT
Pursuant to the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as amended,
and other applicable Laws, Rules, and Regulations
PERMISSION IS HEREBY GRANTED TO
SANMARGI, PLLC
Pender County
FOR THE
continued operation of a 260 gallon per day (GPD) wastewater treatment and irrigation facility consisting
of:
a 1,000 gallon septic tank with an effluent filter assembly; a 1,300 gallon recirculation tank with an Orenco
Systems Biotube pump vault containing two 30 gallon per minute (GPM) at 65 feet (ft) of total dynamic
head (TDH) high-head effluent pumps with high-water alarms and two recirculating splitter valves serving
two parallel AdvanTex AX20 textile filers; an ultraviolet (UV) disinfection system with two UV banks
each containing one bulb and a maximum disinfection capacity of 10 GPM; a 1,500 gallon effluent dosing
tank with two 20 GPM at 100 ft TDH submersible pumps and high-water alarms; an automatic dual zone
headworks with an effluent flowmeter, filter, and filter flushing assemblies; an irrigation controller with
rain sensor; a 0.0874 acre drip irrigation mound area comprised of two zones; and all associated piping,
valves, controls, and appurtenances
to serve the Family Dollar – Currie WWTF, with no discharge of wastes to surface waters, pursuant to the
application received on June 5, 2024, and in conformity with the Division-approved plans and specifications
considered a part of this permit.
This permit is effective from the date of issuance through December 31, 2029, shall replace Permit No.
WQ0043463 issued on December 9, 2022, and is subject to the following conditions and limitations:
I. SCHEDULES
1. If the permitted facilities change ownership or the Permittee changes its name, the Permittee shall
submit a permit modification request on Division-approved forms within 90 days of the change of
ownership. The Permittee shall comply with all terms and conditions of this permit until the Division
transfers the permit to the successor-owner. [G.S. 143-215.1(d3)]
2. The Permittee shall request renewal of this permit on Division-approved forms no later than July 4,
2029. [15A NCAC 02T .0105(b), 02T .0109]
WQ0043463 Version 1.1 Shell Version 230725 Page 2 of 9
II. PERFORMANCE STANDARDS
1. The Permittee shall operate and maintain the subject wastewater treatment and irrigation facilities so
there is no discharge to surface waters, nor any contravention of groundwater or surface water
standards. In the event the facilities do not perform as designed, including the creation of nuisance
conditions due to improper operation and maintenance, or failure of the irrigation areas to assimilate
the effluent, the Permittee shall take immediate corrective actions, including Division-required actions,
such as the construction of additional or replacement wastewater treatment or disposal facilities. [15A
NCAC 02T .0108(b)(1)(A)]
2. This permit shall not relieve the Permittee of its responsibility for contravention of groundwater or
surface water standards resulting from the operation of this facility. [15A NCAC 02T .0108(b)(1)(A)]
3. Effluent quality shall not exceed the limitations specified in Attachment A. [15A NCAC 02T .0505(b)]
4. The Permittee shall not irrigate effluent in exceedance of the hydraulic and agronomic rates specified
in Attachment B. [15A NCAC 02T .0505(c), 02T .0505(n)]
5. The Permittee shall connect the irrigation system to a rain or moisture sensor designed to prevent
irrigation during precipitation events or wet conditions. [15A NCAC 02T .0505(x)]
6. For wastewater irrigation fields originally permitted on or after December 30, 1983, the Division has
established the compliance boundary 250 feet from the irrigation area boundary or 50 feet within the
property boundary, whichever is closest to the irrigation area boundary. Any exceedance of
groundwater standards at or beyond the compliance boundary shall require the Permittee to take
corrective action. The Division shall note any Division-approved relocation of the compliance
boundary in Attachment B. The Division shall consider multiple contiguous properties under common
ownership and permitted for use as a disposal system as a single property regarding the determination
of a compliance boundary. [15A NCAC 02L .0106(e), 02L .0107(b), 02L .0107(c), 02L .0107(f), 02T
.0105(h)]
7. The Division has established the review boundary midway between the compliance boundary and the
irrigation area boundary. Any exceedance of groundwater standards at or beyond the review boundary
shall require the Permittee to take preventative action. [15A NCAC 02L .0106(d), 02L .0108]
8. The Permittee shall notify the Division of any sale or transfer of property affecting a compliance
boundary (i.e., parcel subdivision). [15A NCAC 02L .0107(l)]
9. The Permittee or any landowner who owns land within the compliance boundary shall not construct
any water supply wells within the compliance boundary. [15A NCAC 02L .0107(i)]
WQ0043463 Version 1.1 Shell Version 230725 Page 3 of 9
10. The Permittee shall operate and maintain the permitted facilities pursuant to the following setbacks:
a. The Division originally permitted the irrigation sites on December 9, 2022, with an application
received on May 20, 2022. The setbacks for drip irrigation sites originally permitted or modified
with an application received on or after September 1, 2018, are as follows (all distances in feet):
i. Each habitable residence or place of assembly under separate ownership: 100 1
ii. Each habitable residence or place of assembly owned by the Permittee: 15
iii. Each private or public water supply source: 100
iv. Surface waters: 100
v. Groundwater lowering ditches: 100
vi. Surface water diversions: 25
vii. Each well with exception of monitoring wells: 100
viii. Each property line: 50 2
ix. Top of slope of embankments or cuts of two feet or more in vertical height: 15
x. Each water line: 10
xi. Subsurface groundwater lowering drainage systems: 100
xii. Public right of way: 50
xiii. Nitrification field: 20
xiv. Each building foundation or basement: 15
1 Habitable residences or places of assembly under separate ownership constructed after the
Division originally permitted or subsequently modified the facilities are exempt from this
setback.
2 Setbacks to property lines are not applicable when the Permittee, or the entity from which the
Permittee is leasing, owns both parcels separated by the property line.
[15A NCAC 02T .0506(a), 02T .0506(e), 02T .0506(f)]
b. The Division originally permitted the treatment and storage units on December 9, 2022, with an
application received on May 20, 2022. The setbacks for treatment and storage units originally
permitted or modified with an application received on or after September 1, 2018, are as follows
(all distances in feet):
i. Each habitable residence or place of assembly under separate ownership: 100 1
ii. Each private or public water supply source: 100
iii. Surface waters: 50
iv. Each well with exception of monitoring wells: 100
v. Each property line: 50 2
1 Habitable residences or places of assembly under separate ownership constructed after the
Division originally permitted or subsequently modified the facilities are exempt from this
setback.
2 Setbacks to property lines are not applicable when the Permittee, or the entity from which the
Permittee is leasing, owns both parcels separated by the property line.
[15A NCAC 02T .0506(b), 02T .0506(e), 02T .0506(f)]
WQ0043463 Version 1.1 Shell Version 230725 Page 4 of 9
III. OPERATION AND MAINTENANCE
1. The Permittee shall operate and maintain the subject facilities as a non-discharge system. [15A NCAC
02T .0101]
2. The Permittee shall maintain an Operation and Maintenance Plan, which shall include:
a. A description of the operation of the system in sufficient detail to show what operations are
necessary for the system to function and who shall conduct the operations.
b. A description of the anticipated maintenance of the system.
c. Provisions for safety measures, including restriction of access to the site and equipment.
d. Spill control provisions that include response to upsets and bypasses, including control,
containment, and remediation; and contact information for personnel, emergency responders, and
regulatory agencies.
[15A NCAC 02T .0507(a)]
3. Upon the Water Pollution Control System Operators Certification Commission’s (WPCSOCC)
classification of the subject non-discharge facilities, the Permittee shall designate and employ a certified
Operator in Responsible Charge (ORC), and one or more certified operators as Back-up ORCs. The
ORC or its Back-up shall operate and visit the facilities as required pursuant to 15A NCAC 08G .0204
and 08G .0205. [15A NCAC 02T .0117]
4. The Permittee shall maintain a year-round vegetative cover on the irrigation area such that crop health
is optimal and allows even effluent distribution and inspection of the irrigation system. [15A NCAC
02T .0507(b)]
5. The Permittee shall take measures to prevent effluent ponding in or runoff from the irrigation area.
[15A NCAC 02T .0507(c)]
6. The Permittee shall not irrigate treated effluent during inclement weather or when the soil is in a
condition that will cause ponding or runoff. [15A NCAC 02T .0505(x)]
7. The Permittee shall test and calibrate the irrigation equipment annually. [15A NCAC 02T .0507(d)]
8. The Permittee shall only irrigate treated effluent from the Family Dollar – Currie WWTF onto the sites
listed in Attachment B. [15A NCAC 02T .0501]
9. The Permittee shall not allow vehicles or heavy machinery on the irrigation area, except during
equipment installation or maintenance activities. [15A NCAC 02T .0507(e)]
10. The Permittee shall prohibit public access to the wastewater treatment, storage, and irrigation facilities.
[15A NCAC 02T .0505(q)]
11. The Permittee shall dispose of or utilize generated residuals in a Division-approved manner. [15A
NCAC 02T .0508, 02T .1101].
12. The Permittee shall not divert or bypass untreated or partially treated wastewater from the subject
facilities. [15A NCAC 02T .0505(j)]
13. The Permittee shall establish and maintain a protective vegetative cover on all berms, pipe runs, erosion
control areas, surface water diversions, and earthen embankments (i.e., the outside toe of the
embankment to the maximum allowable temporary storage elevation on the inside of the embankment).
The Permittee shall remove all trees, shrubs, and other woody vegetation from earthen dikes and
embankments. The Permittee shall keep all earthen embankments mowed or otherwise controlled and
accessible. [15A NCAC 02T .0507(g)]
WQ0043463 Version 1.1 Shell Version 230725 Page 5 of 9
14. The Permittee shall test and calibrate metering equipment annually. [15A NCAC 02T .0507(d)]
15. The Permittee shall equip the plumbing serving the Family Dollar – Currie WWTF with low-flow
fixtures such as spring-loaded or automatically activated faucets, low-flow urinals, and low-flow toilets.
[15A NCAC 02T .0108(b)(1)(A)]
16. The Permittee and/or tenants shall prohibit public access to plumbing fixtures serving the Family Dollar
– Currie WWTF. The Permittee and/or tenants shall provide signage denoting “Employees-Only.”.
[15A NCAC 02T .0108(b)(1)(A)]
17. The Permittee and/or tenants shall not dispose of any food waste (solid or liquid) into the plumbing
fixtures serving the Family Dollar – Currie WWTF. [15A NCAC 02T .0108(b)(1)(A)]
18. The Permittee shall develop and implement an education program to inform tenants and its employees
about restrictions to the wastewater system (as specified in Conditions III.16 and III.17). The Permittee
shall provide educational material to all employees in a language they understand. The Permittee shall
make all educational materials available to the Division upon request. [15A NCAC 02T
.0108(b)(1)(A)]
IV. MONITORING AND REPORTING
1. The Permittee shall conduct and report any Division-required monitoring, including the monitoring of
groundwater, surface water or wetlands, waste, wastewater, residuals, soil, treatment processes, lagoon
or storage ponds, and plant tissue, if necessary to evaluate this facility’s impact on groundwater and
surface water. [15A NCAC 02T .0108(c)]
2. A Division-certified laboratory shall conduct all analyses for the required parameters specified in
Attachments A and C. Parameters measured on-site with in-line metering equipment are exempt from
a Division-certified laboratory analysis. [15A NCAC 02H .0805]
3. The Permittee shall continuously monitor flow through the treatment facility and report daily flow
values on Form NDMR. Facilities with a permitted flow of less than 10,000 GPD may estimate its
flow from water usage records provided the water source has a metering device. [15A NCAC 02T
.0105(k), 02T .0108(c)]
4. The Permittee shall monitor the treated effluent at the frequencies and locations for the parameters
specified in Attachment A. [15A NCAC 02T .0105(k), 02T .0108(c)]
5. The Permittee shall maintain records tracking the amount of effluent irrigated, which shall include the
following information for each irrigation site listed in Attachment B:
a. Date of irrigation.
b. Volume of effluent irrigated.
c. Site irrigated.
d. Length of site irrigation time.
e. Continuous weekly, monthly, and year-to-date hydraulic (inches/acre) loadings.
f. Continuous monthly and year-to-date loadings for any non-hydraulic parameter specifically
limited in Attachment B.
g. Weather conditions.
h. Maintenance of cover crops.
[15A NCAC 02T .0108(c)]
WQ0043463 Version 1.1 Shell Version 230725 Page 6 of 9
6. On or before the last day of the month following the previous month’s sampling, t he Permittee shall
submit monitoring data (as specified in Conditions IV.3 and IV.4) on Form NDMR for each PPI, and
operation and disposal records (as specified in Condition IV.5) on Form NDAR-1 for every site in
Attachment B. If no activities occurred during the monitoring month, the Permittee shall still submit
monitoring reports documenting the absence of the activity. The Permittee shall submit the reports via
the Non-Discharge monitoring report portal. [15A NCAC 02T .0105(l)]
7. The Permittee shall maintain records of all residuals removed from this facility. The Permittee shall
maintain these records for eight years and shall make them available to the Division upon request.
These records shall include:
a. Name of the residuals hauler.
b. Non-Discharge permit number authorizing the residuals disposal, or a letter from a municipality
agreeing to accept the residuals.
c. Residuals hauling date.
d. Volume of residuals removed.
[15A NCAC 02T .0508(b)]
8. The Permittee shall keep a log of all maintenance done at this facility. The Permittee shall maintain
this log for eight years and shall make it available to the Division upon request. This log shall include:
a. Date of flow measurement device calibration.
b. Date of irrigation equipment calibration.
c. Visual observations of the plant and plant site.
d. Record of preventative maintenance (e.g., changing of equipment, adjustments, testing,
inspections, cleanings, etc.).
[15A NCAC 02T .0507(h)]
9. The Permittee shall sample monitoring well MW-1 at the frequencies and for the parameters specified
in Attachment C. [15A NCAC 02T .0105(m)]
10. On or before the last day of the month following the previous month’s sampling, the Permittee shall
submit a Compliance Monitoring Form (GW-59) and its associated laboratory analyses for each
monitoring well in Attachment C. The Permittee shall submit the Compliance Monitoring Forms via
the Non-Discharge monitoring report portal. [15A NCAC 02T .0105(m)]
11. The Permittee shall conduct an annual representative soil analysis (i.e., Standard Soil Fertility Analysis)
on each irrigation site listed in Attachment B. The Permittee shall maintain these results at the facility
for eight years and shall make them available to the Division upon request. Each Standard Soil Fertility
Analysis shall include the following parameters:
Acidity Exchangeable Sodium Percentage Phosphorus
Base Saturation (by calculation) Magnesium Potassium
Calcium Manganese Sodium
Cation Exchange Capacity Percent Humic Matter Zinc
Copper pH
[15A NCAC 02T .0108(c)]
WQ0043463 Version 1.1 Shell Version 230725 Page 7 of 9
12. Noncompliance Notification:
The Permittee shall report to the Wilmington Regional Office, telephone number (910) 796-7215,
within 24 hours of first knowledge of the following:
a. Treatment of wastes abnormal in quantity or characteristic, including the known passage of a
hazardous substance.
b. Any process unit failure (e.g., mechanical, electrical, structural, etc.) that makes the facility
incapable of adequate wastewater treatment.
c. Any facility failure resulting in a discharge to surface waters.
d. Any time self-monitoring indicates the facility has gone out of compliance with its permit
limitations.
e. Ponding in or runoff from the irrigation sites.
Emergencies requiring reporting outside normal business hours shall call the Division’s Emergency
Response personnel at the telephone number (800) 858-0368. All noncompliance notifications shall
file a written report to the Wilmington Regional Office within five days of first knowledge of the
occurrence, and this report shall outline the actions proposed or taken to ensure the problem does not
recur. [15A NCAC 02T .0108(b)(1)(A)]
V. INSPECTIONS
1. The Permittee shall perform inspections and maintenance to ensure proper operation of the wastewater
treatment and irrigation facilities. [15A NCAC 02T .0507(i)]
2. The Permittee shall inspect the wastewater treatment and irrigation facilities to prevent malfunctions,
facility deterioration, and operator errors that may result in discharges of wastes to the environment,
threats to human health, or public nuisances. The Permittee shall maintain an inspection log that
includes the date and time of inspection, observations made, and maintenance, repairs, or corrective
actions taken. The Permittee shall maintain this inspection log for eight years from the date of the
inspection and shall make this log available to the Division upon request. [15A NCAC 02T .0507(h),
02T .0507(i)]
3. Division-authorized representatives may, upon presentation of credentials, enter and inspect any
property, premises, or place related to the permitted wastewater treatment and irrigation facilities at any
reasonable time for determining compliance with this permit. Division-authorized representatives may
inspect or copy records maintained under the terms and conditions of this permit and may collect
influent, treatment process water, effluent, residual, soil, plant tissue, groundwater, or surface water
samples. [G.S. 143-215.3(a)(2)]
WQ0043463 Version 1.1 Shell Version 230725 Page 8 of 9
VI. GENERAL
1. The Permittee’s failure to comply with this permit’s conditions and limitations may subject the
Permittee to a Division enforcement action. [G.S. 143-215.6A, 143-215.6B, 143-215.6C]
2. This permit is effective only for the nature and volume of wastes described in the permit application
and Division-approved plans and specifications. [G.S. 143-215.1(d)]
3. There are no variances to administrative codes or general statutes governing the construction or
operation of the permitted facilities unless the Permittee specifically requested a variance in the
application and the Division approved the variance as noted in this permit’s facility description. [15A
NCAC 02T .0105(b)]
4. This permit does not exempt the Permittee from complying with all statutes, rules, regulations, or
ordinances that other jurisdictional government agencies (e.g., local, state, and federal) may require.
[15A NCAC 02T .0108(b)(1)(A)]
5. The Permittee shall retain this permit and the Division-approved plans and specifications for the life of
the permitted facilities. [15A NCAC 02T .0105(o), 02T .0116(d)]
6. The Permittee shall comply with all permit conditions and requirements until the proper closure of the
permitted facilities, or until another appropriate authority permits the facilities. [15A NCAC 02T
.0105(j)]
7. This permit is subject to revocation or modification upon 60-day notice from the Division Director in
whole or part for:
a. Violation of any terms or conditions of this permit or 15A NCAC 02T.
b. Obtaining a permit by misrepresentation or failure to disclose all relevant facts.
c. The Permittee’s refusal to allow authorized Department employees upon presentation of
credentials:
i. To enter the Permittee’s premises where a system is located or where the Permittee keeps any
Division-required records under the terms and conditions of this permit.
ii. To have access to any permit-required documents and records.
iii. To inspect any monitoring equipment or method as required in this permit.
iv. To sample any pollutants.
d. The Permittee’s failure to pay the annual fee for administering and compliance monitoring.
e. A Division determination that the conditions of this permit conflict with the North Carolina
Administrative Code or General Statutes.
[15A NCAC 02T .0110]
WQ0043463 Version 1.1 Shell Version 230725 Page 9 of 9
8. Unless the Division determines that the Permittee needs a permit modification for the construction of
facilities to resolve non-compliance with any environmental statute or rule, or the Division Director
grants a variance, expansion of the permitted facilities shall not occur if any of the following apply:
a. The Permittee or any parent, subsidiary, or other affiliate of the Permittee has been convicted of
environmental crimes under G.S. 143-215.6B or under Federal law that would otherwise be
prosecuted under G.S. 143-215.6B, and the Permittee or any parent, subsidiary, or other affiliate of
the Permittee has abandoned or exhausted all appeals of this conviction.
b. The Permittee or any parent, subsidiary, or other affiliate of the Permittee has previously abandoned
a wastewater treatment facility without properly closing the facility in accordance with its permit
or 15A NCAC 02T.
c. The Permittee or any parent, subsidiary, or other affiliate of the Permittee has not paid a civil
penalty, and the Permittee or any parent, subsidiary, or other affiliate of the Permittee has
abandoned or exhausted all appeals of this penalty.
d. The Permittee or any parent, subsidiary, or other affiliate of the Permittee is currently not compliant
with any compliance schedule in a permit, settlement agreement, or order.
e. The Permittee or any parent, subsidiary, or other affiliate of the Permittee has not paid an annual
fee pursuant to 15A NCAC 02T .0105(e)(2).
[15A NCAC 02T .0120(b), 02T .0120(d)]
9. Unless the Division Director grants a variance, the Division shall not renew this permit if the Permittee
or any affiliation has not paid an annual fee pursuant to 15A NCAC 02T .0105(e)(2). [15A NCAC 02T
.0120(c), 02T .0120(d)]
10. The Permittee shall pay an annual fee for each year of the term of this permit pursuant to the schedule
in G.S. 143-215.3D(a). The Permittee shall continue to pay annual fees for any facility operating on
an expired permit that the Division has not rescinded or revoked. [15A NCAC 02T .0105(e)(2)]
Permit issued this the 27th day of June 2024
NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION
____________________________________________
Richard E. Rogers, Jr., Director
Division of Water Resources
By Authority of the Environmental Management Commission
Permit Number WQ0043463
THIS PAGE BLANK
ATTACHMENT A – LIMITATIONS AND MONITORING REQUIREMENTS Certification Date: June 27, 2024
SANMARGI, PLLC Permit Number: WQ0043463 Version: 1.1
WQ0043463 Version 1.1 Attachment A Page 1 of 1
PPI 001 – WWTF Effluent
EFFLUENT CHARACTERISTICS EFFLUENT LIMITS MONITORING REQUIREMENTS
PCS
Code Parameter Description Units of
Measure
Monthly
Average
Monthly
Geometric Mean Daily Minimum Daily Maximum Measurement
Frequency
Sample
Type
00310 BOD, 5-Day (20 ºC) mg/L 30 Annually 1 Grab
00940 Chloride (as Cl) mg/L 3 x Year 2 Grab
31616 Coliform, Fecal MF, M-FC Broth, 44.5 ºC #/100 mL 200 Annually 1 Grab
50050 Flow, in Conduit or thru Treatment Plant GPD 260 Monthly Estimate
00610 Nitrogen, Ammonia Total (as N) mg/L 15 Annually 1 Grab
00625 Nitrogen, Kjeldahl, Total (as N) mg/L Annually 1 Grab
00620 Nitrogen, Nitrate Total (as N) mg/L Annually 1 Grab
00600 Nitrogen, Total (as N) mg/L Annually 1 Grab
00400 pH su 2 x Year 3 Grab
00665 Phosphorus, Total (as P) mg/L Annually 1 Grab
70300 Solids, Total Dissolved – 180 ºC mg/L 3 x Year 2 Grab
00530 Solids, Total Suspended mg/L 30 Annually 1 Grab
1. The Permittee shall conduct Annual sampling in July.
2. The Permittee shall conduct 3 x Year sampling in March, July, and November.
3. The Permittee shall conduct 2 x Year sampling in January and July.
THIS PAGE BLANK
ATTACHMENT B – APPROVED LAND APPLICATION SITES AND LIMITATIONS Certification Date: June 27, 2024
SANMARGI, PLLC Permit Number: WQ0043463 Version: 1.1
WQ0043463 Version 1.1 Attachment B Page 1 of 1
IRRIGATION AREA INFORMATION APPLICATION LIMITATIONS
Field Owner Parcel No. County Latitude Longitude Net
Acreage
Dominant
Soil Series Parameter Hourly
Rate
Yearly
Max Units
Zone 1 SANMARGI, PLLC 2285-63-0939-0000 Pender 34.443996° -78.05051° 0.0437 Murville Muck 01284 – Non-Discharge Application Rate 0.008 39.99 inches
Zone 2 SANMARGI, PLLC 2285-63-0939-0000 Pender 34.443999° -78.051111° 0.0437 Murville Muck 01284 – Non-Discharge Application Rate 0.008 39.99 inches
Total: 0.0874
THIS PAGE BLANK
ATTACHMENT C – GROUNDWATER MONITORING AND LIMITATIONS Certification Date: June 27, 2024
SANMARGI, PLLC Permit Number: WQ0043463 Version: 1.1
WQ0043463 Version 1.1 Attachment C Page 1 of 1
Monitoring Wells: MW-1
GROUNDWATER CHARACTERISTICS GROUNDWATER STANDARDS MONITORING REQUIREMENTS
PCS Code Parameter Description Daily Maximum Frequency Measurement Sample Type Footnotes
00940 Chloride (as Cl) 250 mg/L 3 x Year 1 Grab 1
31616 Coliform, Fecal MF, M-FC Broth, 44.5 ºC #/100 mL 3 x Year 1 Grab 1
00610 Nitrogen, Ammonia Total (as N) 1.5 mg/L 3 x Year 1 Grab 1
00620 Nitrogen, Nitrate Total (as N) 10 mg/L 3 x Year 1 Grab 1
00400 pH 6.5-8.5 su 3 x Year 1 Grab 1, 2
00665 Phosphorus, Total (as P) mg/L 3 x Year 1 Grab 1
70300 Solids, Total Dissolved - 180 ºC 500 mg/L 3 x Year 1 Grab 1
82546 Water Level, Distance from measuring point feet 3 x Year 1 Calculated 1, 2, 3
1. The Permittee shall conduct 3 x Year monitoring in March, July, and November.
2. The Permittee shall measure the water levels prior to purging the wells. The Permittee shall measure the depth to water in each well from the surveyed point on the top of the casing. The Permittee
shall measure pH after purging and prior to sampling for the remaining parameters.
3. The Permittee shall survey the measuring points (top of well casing) of all monitoring wells to provide the relative elevation of the measuring point for each monitoring well. The Permittee shall
survey the measuring points (top of casing) of all monitoring wells relative to a common datum.
4. The Permittee shall report monitoring well data on Compliance Monitoring Forms (GW-59s) consistent with the nomenclature and location information provided in this attachment.
1. Wu/ I \— u I \C)U—u7MVVIINt— \UVIL\,w i —UO//- i UUU I—rLANUS. I b.2U22.UWU UY/08/2022 1 6:10:08 NATALIE DELL
FIGURE 1