HomeMy WebLinkAboutNC0026573_NOV-2024-LV-0379_20240508_responseCity of Morganton Water Resources Department May 8th, 2024 Daniel Boss, Assistant Regional Supervisor Water Quality Regional Operations Section Asheville Regional Office Division of Water Resources, NCDEQ Subject: Response to NOV-2024-LV-0379 Dear Mr. Boss, We have reviewed the permit violation NOV-2024-LV-0379 for Permit NC0026573. The facility had several issues during the month to cause the exceedance of 0.14 mg/1 over monthly average. The first two weeks of the month had higher TSS average due to facility still recovering from the washout/young sludge issues from prior month (January). Then the second half of the month, on three different days, we had secondary return activated sludge pumps stop pumping due to air locking and caused TSS to escape from clarifier for short periods of time. This issue only happens maybe once to twice a year. After the events of the RAS pumps, ORC implemented a twice a day pump air bleed off regiment and began RAS flow meter checks six times per day in an effort to prevent pump air locking. The facility has also began a SCADA rehabilitation project to address failed PLCs and software so these RAS pumps and other sections in the facility are fully monitored and trending again. This will be of great assistance once completed, hopefully by end of the year. If there is any questions or if more information is needed, please reach me at 828-438-5375 or at eself(c�morgantonNC.gov Sincerely, Eli Self Wastewater Plant Superintendent & ORC City of Morganton NC Telephone 828-437-8863 305 East Union St. Post Office Box 3448 www.morgantonNC.gov Morganton, NC 28655 Morganton, NC 28680-3448