HomeMy WebLinkAboutNC0061492_Inspection_20240618United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NCO061492 111 121 24/06/05 I17 18 I C I 19 Ls_] 20I j I
211111 I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
I 72 I n,J I I I 71 I 74 79 I I I I I I I80
701� I 711 L
LJ L
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
12:50PM 24/06/05
24/03/01
Maury Sanitary Land District WWTP
NCSR 1401
Exit Time/Date
Permit Expiration Date
Maury NC 28554
02:OOPM 24/06/05
28/05/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
James Jeffrey Kuipers/ORC/252-747-2450/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
James Jeffrey Kuipers,PO Box 98 Maury NC 285540098/Operator/252-747-2450/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Sludge Handling Dispo: Facility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
DocuSigned by:
Breann Spencer DWR/WARD WQ/252-946-6481/ 6/18/2024
Robert E Bullock DWR/WARD WQ/252-948-3843/
252 D5 D F605C E433...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
vmU " DWR / WaRO WQROS / 252-948-3939 6/18/2024
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NCO061492 I11 12I 24/06/05 117 18 i c i
(Cont.)
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
A compliance inspection was conducted on 6/5/2024 by Breann Spencer and Robbie Bullock with
DWQ- WaRO. James Kuiper was the ORC on site during the inspection.
There is no standby generator at the WWTP. If power is lost, flow is diverted to the storage lagoon.
Renewed permit #NC0061492 became effective March 1, 2024. Facility uses Waypoint as the
contract lab. Facility is field certified for pH, DO, temperature, and TRC. Field lab certification # 5309.
DMR for Sept. 2023 was checked against lab reports for accuracy. The BOD on the DMR was
recorded as < 20 when lab reports showed < 2. The DMRs for Aug. and Oct. 2023 were checked for
BOD and were found to be < 2. Error was noted and ORC has revised eDMR. The facility is behind
on submitting the Annual Reports. BIMS has listed backup ORC Julian Jones as invalid at time of
inspection. ORC was notified and is working on resolving these issues. The bar screen area needs to
be cleanned out. Empty and extra gas clyinders were not secured in the chlorine storage area.
The facility was found to be compliant with permit #NC0061492.
Page#
Permit: NCO061492 Owner -Facility: Maury Sanitary Land District WWTP
Inspection Date: 06/05/2024 Inspection Type: Compliance Evaluation
Permit
Yes
No
NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
0
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
❑
0
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: There is no standby generator at the WWTP. Renewed permit NCO061492 became
effective March 1, 2024.
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ■ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ■ ❑ ❑
❑ ❑ ■ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ■ ❑ ❑
■ ❑ ❑ ❑
❑ ■ ❑ ❑
Page# 3
Permit: NCO061492
Inspection Date: 06/05/2024
Owner -Facility: Maury Sanitary Land District WWTP
Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Comment: DMR for Sept. 2023 was checked against lab reports for accuracy. The BOD on the
DMR was recorded as < 20 when lab reports showed < 2. The DMRs for Aug. and Oct.
2023 were checked for BOD and were found to be < 2. Error was note and ORC has
revised eDMR. The facility is behind on submitting the Annual Reports. BIMS has listed
backup ORC Julian Jones as invalid at time of inspection. ORC was notified and is
workina on resolvina these issues.
Laboratory
Yes
No
NA
NE
Are field parameters performed by certified personnel or laboratory?
0
❑
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab?
0
❑
❑
❑
# Is the facility using a contract lab?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
■
❑
❑
❑
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
■
❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
❑
■
❑
Comment: Facility uses Waypoint as the contract lab. Facility is field certified for pH, DO,
temperature, and TRC. Field lab certification # 5309.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, 0 ❑ ❑ ❑
and sampling location)?
Comment:
Bar Screens
Yes
No
NA
NE
Type of bar screen
a.Manual
❑
b.Mechanical
Are the bars adequately screening debris?
0
❑
❑
❑
Is the screen free of excessive debris?
❑
0
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Page# 4
Permit: NCO061492 Owner -Facility: Maury Sanitary Land District WWTP
Inspection Date: 06/05/2024 Inspection Type: Compliance Evaluation
Bar Screens Yes No NA NE
Comment: Bar screen area needs to cleaned out.
Grit Removal
Yes
No
NA NE
Type of grit removal
a.Manual
■
b.Mechanical
❑
Is the grit free of excessive organic matter?
■
❑
❑ ❑
Is the grit free of excessive odor?
■
❑
❑ ❑
# Is disposal of grit in compliance?
■
❑
❑ ❑
Comment: Grit is vacuumed out when needed.
Oxidation Ditches
Yes
No
NA
NE
Are the aerators operational?
■
❑
❑
❑
Are the aerators free of excessive solids build up?
■
❑
❑
❑
# Is the foam the proper color for the treatment process?
■
❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
■
❑
❑
❑
Is the DO level acceptable?
■
❑
❑
❑
Are settleometer results acceptable (> 30 minutes)?
■
❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
■
❑
❑
❑
Are settelometer results acceptable?(400 to 800 ml/I in 30 minutes)
■
❑
❑
❑
Comment: ORC stated DO was 3 ma/L and settlability was 690 mL.
Secondary Clarifier
Yes
No
NA
NE
Is the clarifier free of black and odorous wastewater?
■
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
■
❑
❑
❑
Are weirs level?
■
❑
❑
❑
Is the site free of weir blockage?
■
❑
❑
❑
Is the site free of evidence of short-circuiting?
■
❑
❑
❑
Is scum removal adequate?
■
❑
❑
❑
Is the site free of excessive floating sludge?
■
❑
❑
❑
Is the drive unit operational?
■
❑
❑
❑
Is the return rate acceptable (low turbulence)?
■
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
■
❑
❑
❑
Page# 5
Permit: NCO061492 Owner -Facility: Maury Sanitary Land District WWTP
Inspection Date: 06/05/2024 Inspection Type: Compliance Evaluation
Secondary Clarifier Yes No NA NE
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth) ❑ ❑ ❑
Comment: ORC stated sludge level was 3-3.5 ft for both clarifiers.
Disinfection -Gas
Yes
No
NA
NE
Are cylinders secured adequately?
❑
0
❑
❑
Are cylinders protected from direct sunlight?
0
❑
❑
❑
Is there adequate reserve supply of disinfectant?
■
❑
❑
❑
Is the level of chlorine residual acceptable?
0
❑
❑
❑
Is the contact chamber free of growth, or sludge buildup?
0
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
0
❑
❑
❑
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No.
❑
❑
0
❑
7782-50-5)?
If yes, then is there a Risk Management Plan on site?
❑
❑
0
❑
If yes, then what is the EPA twelve digit ID Number? (1000-
If yes, then when was the RMP last updated?
Comment: Empty and spare cylinders were not secured.
De -chlorination
Yes
No
NA
NE
Type of system ?
Gas
Is the feed ratio proportional to chlorine amount (1 to 1)?
0
❑
❑
❑
Is storage appropriate for cylinders?
■
❑
❑
❑
# Is de -chlorination substance stored away from chlorine containers?
0
❑
❑
❑
Are the tablets the proper size and type?
❑
❑
❑
Comment: Sulfur dioxide is used to de -chlorinate effluent.
Are tablet de -chlorinators operational?
❑
❑
❑
Number of tubes in use?
Comment:
Flow Measurement - Effluent
Yes
No
NA
NE
# Is flow meter used for reporting?
0
❑
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
0
❑
❑
❑
Page# 6
Permit: NCO061492 Owner - Facility: Maury Sanitary Land District WWTP
Inspection Date: 06/05/2024 Inspection Type: Compliance Evaluation
Flow Measurement- Effluent Yes No NA NE
Comment: Chadwick Instrument Service calibrated flow meter 1/30/24.
Effluent Sampling
Yes
No
NA
NE
Is composite sampling flow proportional?
0
❑
❑
❑
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
0
❑
❑
❑
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
0
❑
❑
❑
representative)?
Comment:
Pumps-RAS-WAS
Yes
No
NA
NE
Are pumps in place?
0
❑
❑
❑
Are pumps operational?
0
❑
❑
❑
Are there adequate spare parts and supplies on site?
0
❑
❑
❑
Comment:
Standby Power
Yes
No
NA
NE
Is automatically activated standby power available?
❑
0
❑
❑
Is the generator tested by interrupting primary power source?
❑
0
❑
❑
Is the generator tested under load?
❑
0
❑
❑
Was generator tested & operational during the inspection?
❑
0
❑
❑
Do the generator(s) have adequate capacity to operate the entire wastewater site?
❑
0
❑
❑
Is there an emergency agreement with a fuel vendor for extended run on back-up
❑
■
❑
❑
power?
Is the generator fuel level monitored?
❑
0
❑
❑
Comment: There is no standby generator. If power is lost, flow is diverted to the storage lagoon.
Chemical Feed
Is containment adequate?
Is storage adequate?
Are backup pumps available?
Yes No NA NE
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Page# 7
Permit: NC0061492
Inspection Date: 06/05/2024
Chemical Feed
Is the site free of excessive leaking?
Comment:
Owner -Facility: Maury Sanitary Land District WWTP
Inspection Type: Compliance Evaluation
Yes No NA NE
■ ❑ ❑ ❑
Page#