SENT VIA ELECTRONIC MAIL ONLY: NO HARD COPY WILL BE MAILED.
June 12, 2024
Eric H Mick
Email: erichmick@gmail.com
SUBJECT: NOTICE OF VIOLATION
Tracking Number: NOV-2024-PC-0390
Permit No. NCG550275
326 Smokey Shadows Lane
Haywood County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the 326 Smokey Shadows Lane on
May 30, 2024. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in NPDES WW Permit No. NCG550275. A summary of the findings and
comments noted during the inspection are provided in the enclosed copy of the inspection report.
The Compliance Evaluation inspection was conducted by Division of Water Resources staff from the Asheville
Regional Office. The following violations were noted during the inspection:
Inspection Area Description of Violation _________________________________________________________________________________________________________________________________________________________________________
Operations & Maintenance System components could not be located, including the septic tank, sand filter trench, tablet
chlorination unit, and effluent pipe. It appears that the system is not being properly
maintained.
[NCG550000 Part I. D. 4. Permit Conditions (Operation, Maintenance & Records)
All system components, including but not necessarily limited to, septic tanks,
surface sand filters, other filter components, pump/recirculation tanks, controls
and alarms, disinfection units, dechlorination apparatus, and the outfalls shall be
maintained at all times and in good operating order.] _________________________________________________________________________________________________________________________________________________________________________
Septic Tank Septic tank pumping records were not provided.
[NCG550000 Part I. D. 3. a.- b. Permit Conditions (Operation, Maintenance &
Records) Septic tanks shall be inspected at least yearly to determine if solids must
be removed or if other maintenance is necessary. Septic tanks shall be pumped out
at least once every five years or when the solids level is found to be more than 1/3 of the liquid depth in any compartment, whichever is greater.]
_________________________________________________________________________________________________________________________________________________________________________
DocuSign Envelope ID: C9246A50-DD34-4E9C-9ED3-929F836FA19D
Remedial actions should have already been taken to correct this problem and prevent further occurrences in the
future. The Division of Water Resources may pursue enforcement action for this and any additional violations of
State law.
To prevent further action, please respond in writing to this office within 30 days upon your receipt of this Notice
of Violation regarding your plans or measures to be taken to address the indicated violations and other identified
issues, if applicable.
If you should have any questions, please do not hesitate to contact Lauren Armeni with the Water Quality
Regional Operations Section in the Asheville Regional Office at 828-296-4667.
Sincerely,
Daniel Boss, Assistant Regional Supervisor
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS: Inspection Report, NCG55 General Permit
Ec: Laserfiche
DocuSign Envelope ID: C9246A50-DD34-4E9C-9ED3-929F836FA19D
EPA
United States Environmental Protection Agency
Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 N 52 NCG550275 24/05/30 C S31112171819 20
21 66
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
N67707172 73 74 75 80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
326 Smokey Shadows Lane
326 Smokey Shadows Ln
Maggie Valley NC 28751
Entry Time/Date Permit Effective Date
Exit Time/Date Permit Expiration Date
11:00AM 24/05/30 20/12/07
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Other Facility Data
11:30PM 24/05/30 25/10/31
Name, Address of Responsible Official/Title/Phone and Fax Number
Eric H Mick,8805 Darcy Hopkins Dr Charlotte NC 28277//704-231-9812/Contacted
Yes
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Operations & Maintenance Self-Monitoring Program Facility Site Review
Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date
Lauren E Armeni DWR/ARO WQ/828-296-4500/
Mikal Willmer DWR/ARO WQ/828-296-4686/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#1
DocuSign Envelope ID: C9246A50-DD34-4E9C-9ED3-929F836FA19D
6/12/2024
6/12/2024
6/12/2024
NPDES yr/mo/day
24/05/30
Inspection Type
C3111218
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Lauren Armeni and Mikal Willmer, with the Asheville Regional Office, conducted a Compliance
Evaluation Inspection of the single-family wastewater disposal system that services 326 Smokey
Shadows Lane on May 30, 2024. This inspection was conducted to determine if the system is being
operated and maintained in compliance with General NPDES Permit No. NCG550000.
Ms. Armeni spoke with Mr. Eric Mick prior to the inspection and he indicated that all system
components would be located and the tank would be checked and pumped if needed. Ms. Armeni let
Mr. Mick know when the inspection would take place, and she did not hear back from him regarding if
the system components had been located/maintained as needed. This property continues to be a
part-time residence.
The following items were noted during the inspection:
1. Operations & Maintenance: Overall, the system components all need to be located, including the
septic tank, sand filter trench, tablet chlorination unit, and effluent pipe. See additional items below
for details of each component.
2. Septic Tank: Septic tank pumping records were not provided. The 2019 Inspection Report
indicated that Clearwater Environmental had located and checked the septic tank around 2017. They
reported that the tank water level was less than half full at that time; however, there was potentially a
mid-seam leak within the tank. It does not appear that the tank has been checked since 2017. The
tank needs to be checked to verify if the solids need pumped, and also to determine if there is a
mid-seam leak, and if so, to repair this leak. The septic tank needs to be pumped by a certified
septage firm every five years and/or when the solids level is 1/3 the liquid level in either compartment
of the tank.
3. Sand Filter: The sand filter could not be located, and according to the last report was not located
then. The sand filter should be located and checked as part of overall system maintenance.
4. Disinfection - Tablet: The tablet chlorination unit could not be located. This unit should be located,
and a few chlorination tablets should be kept in one tube at all times (do not pack full - the tablets can
cake when wet and be difficult to clean), even if the system is not discharging.
5. Effluent Pipe: The effluent pipe could not be located. This pipe needs to be located in order to
check if the system is discharging.
6. Effluent Sampling: Once the effluent pipe is located, if flow is seen discharging from the pipe at any
time throughout the year, annual sampling is required per Table C.(3.) in General Permit NCG55,
which will be attached to this report.
The following violations were noted during the inspection:
1. Operations & Maintenance: System components could not be located, including the septic tank,
sand filter trench, tablet chlorination unit, and effluent pipe. It appears that the system is not being
properly maintained.
2. Septic Tank: Septic tank pumping records were not provided.
NCG550275 17 (Cont.)
Page#2
DocuSign Envelope ID: C9246A50-DD34-4E9C-9ED3-929F836FA19D
Permit:NCG550275
Inspection Date:05/30/2024
Owner - Facility:
Inspection Type:
326 Smokey Shadows Lane
Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
The Certificate of Coverage changed ownership in October 2019.Comment:
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
All system components could not be located. See summary for details.Comment:
Septic Tank Yes No NA NE
(If pumps are used) Is an audible and visual alarm operational?
Is septic tank pumped on a schedule?
Are pumps or syphons operating properly?
Are high and low water alarms operating properly?
Septic tank pumping records were not provided. See summary for details.Comment:
Sand Filters (Low rate)Yes No NA NE
(If pumps are used) Is an audible and visible alarm Present and operational?
Is the distribution box level and watertight?
Is sand filter free of ponding?
Is the sand filter effluent re-circulated at a valid ratio?
# Is the sand filter surface free of algae or excessive vegetation?
# Is the sand filter effluent re-circulated at a valid ratio? (Approximately 3 to 1)
According to past records, this type of subsurface sand filter is supposed to be a sand
filter trench. See summary for details.
Comment:
Disinfection-Tablet Yes No NA NE
Are tablet chlorinators operational?
Are the tablets the proper size and type?
Page#3
DocuSign Envelope ID: C9246A50-DD34-4E9C-9ED3-929F836FA19D
Permit:NCG550275
Inspection Date:05/30/2024
Owner - Facility:
Inspection Type:
326 Smokey Shadows Lane
Compliance Evaluation
Disinfection-Tablet Yes No NA NE
Number of tubes in use?
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de-chlorination?
The tablet chlorination unit could not be located. See summary for details.Comment:
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
The effluent pipe could not be located. See summary for details.Comment:
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
At this time, it cannot be evaluated whether or not annual effluent sampling is required
because the effluent pipe has not been located. See summary for details.
Comment:
Page#4