HomeMy WebLinkAboutNC0036277_Compliance Evaluation Inspection_20240529ROY COOPER
Governor
ELIZABETH S. BISER
Secretary
RICHARD E. ROGERS, JR.
Director
Joseph Lockler, Operations Chief
Environmental Management Division
Charlotte Water
5100 Brookshire Blvd.
Charlotte, NC 28216
SUBJECT: Compliance Evaluation Inspection
McDowell Creek WRRF
NPDES Permit No. NCO036277
Mecklenburg County
Dear Mr. Lockler:
NORTH CAROLINA
Environmental Quality
May 29, 2024
Enclosed is a copy of the Compliance Evaluation Inspection (CEI) Report for the inspection conducted at the subject
facility on May 17, 2024, by Mr. Wes Bell of this Office. This Office would like to thank all Water Resources Recovery
Facility (WRRF) staff for their cooperation and assistance that was provided throughout this inspection. Please advise the
facility's Operator -in -Responsible Charge (ORC) of our findings by forwarding the enclosed report.
Should you have any questions concerning this report, please do not hesitate to contact Mr. Bell at (704) 235-2192 or at
wes.bell(a,deq.nc. gov.
Sincerely,
DocuSigned by:
A w N P-Lu"
F161 FB69A2D84A3...
Andrew H. Pitner, P.G.
Regional Supervisor
Water Quality Regional Operations Section
Mooresville Regional Office
Division of Water Resources, NCDEQ
Enclosure: Inspection Report
Cc: NPDES Program Files - Laserfiche
el- DEQ��
North Carolina Department of Environmental quality I Divisionof Water Resources
Mooresville Regional Office 1 610 East Center Avenue, Suite 301 1 Mooresville, North Carolina 28115
704.6631699
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NCO036277 111 121 24/05/17 I17 18 LC] I 19 I s I 20L]
21111I I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
2.0 701d I 71 I„ I 72 I r., I 71 I 74 79 I I I I I I I80
L—I ty L-1 I I
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES Dermit Number)
09:06AM 24/05/17
19/12/01
McDowell Creek WWTP
4901 Neck Rd
Exit Time/Date
Permit Expiration Date
Huntersville NC 28078
11:26AM 24/05/17
24/06/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Daniel Joseph Matias/ORC/704-547-0680/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Angela D Charles,5100 Brookshire Blvd Charlotte NC
282163371 /Di rector/704-336-5911 / No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Sludge Handling Dispo: Facility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
DocuSigned by:
Wes Bell �� �e& DWR/MRO WQ/704-235-2192/ 5/29/2024
A61696D90=437...
Signature of Man WQA&viewer Agency/Office/Phone and Fax Numbers Date
Andrew Piro(4w H P440WR/MRO WQ/704-663-1699 Ext.2180/ 5/29/2024
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NC0036277 I11 12I 24/05/17 117 18 i c i
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On -site Representatives:
The following Charlotte Water staff were in attendance during the inspection: Ms. Katie Vivas and
Messrs. Darrell DeWitt, Daniel Matias, Doug Wise, AZ Williams, and Mike Christiansen.
Page#
Permit: NCO036277 Owner -Facility: McDowell Creek WWTP
Inspection Date: 05/17/2024 Inspection Type: Compliance Evaluation
Permit
Yes
No
NA
NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
0
❑
❑
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
0
❑
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: The Division received Charlotte Water's permit renewal package on 1/2/24.
Charlotte Water implements a Division -approved Industrial Pretreatment Program.
The last compliance evaluation inspection at this facility was performed by DWR staff
on 2/23/22.
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 3
Permit: NCO036277
Inspection Date: 05/17/2024
Owner -Facility: McDowell Creek WWTP
Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Comment: The records reviewed durinq the inspection were organized and well maintained.
In-depth operation and maintenance records including process control measurements
were being documented and maintained on -site.
Discharge monitoring reports (eDMRs) were reviewed for the period April 2023 through
March 2024. No effluent limit and/or monitoring violations were noted.
Laboratory
Yes
No
NA NE
Are field parameters performed by certified personnel or laboratory?
0
❑
❑ ❑
Are all other parameters(excluding field parameters) performed by a certified lab?
0
❑
❑ ❑
# Is the facility using a contract lab?
0
❑
❑ ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
❑
❑
■ ❑
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
0 ❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
❑
0 ❑
Comment: Influent and effluent analyses (including field parameters) are performed by
Charlotte
Water's Environmental Services Laboratory (Certification #192). Waypointe Analytical,
ETT Environmental (chronic toxicity) and Environmental Testing Solutions
(chronic
toxicity) have all been contracted to provide analytical support.
Influent Sampling
# Is composite sampling flow proportional?
Is sample collected above side streams?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Is sampling performed according to the permit?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑
Comment: The subject permit requires influent BOD and TSS composite samples. The sampler
operation is checked daily by on -site staff and calibrated monthly.
Effluent Sampling
Yes
No
NA
NE
Is composite sampling flow proportional?
0
❑
❑
❑
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
■
❑
❑
❑
degrees Celsius)?
Page# 4
Permit: NCO036277
Inspection Date: 05/17/2024
Owner -Facility: McDowell Creek WWTP
Inspection Type: Compliance Evaluation
Effluent Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type 0 ❑ ❑ ❑
representative)?
Comment: The subject permit requires composite and grab effluent samples. The sampler
operation is checked daily by on -site staff and calibrated monthly.
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, 0 ❑ ❑ ❑
and sampling location)?
Comment:
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The wastewater treatment facility appeared to be properly operated and well
maintained. The operations staff incorporate a comprehensive process control
program.
The facility is equipped with a SCADA system that is accessible at thirteen (13)
locations throughout the plant site.
An Odor control system is connected to the influent pump station/screening & grit
removal facility and 1.3 million gallon day tank.
Bar Screens
Yes
No
NA NE
Type of bar screen
a.Manual
❑
b.Mechanical
Are the bars adequately screening debris?
0
❑
❑
❑
Is the screen free of excessive debris?
■
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Comment:
Grit Removal Yes No NA NE
Type of grit removal
a.Manual ❑
b.Mechanical
Is the grit free of excessive organic matter? 0 ❑ ❑ ❑
Page# 5
Permit: NC0036277
Inspection Date: 05/17/2024
Owner -Facility: McDowell Creek WWTP
Inspection Type: Compliance Evaluation
Grit Removal
Yes
No
NA
NE
Is the grit free of excessive odor?
0
❑
❑
❑
# Is disposal of grit in compliance?
0
❑
❑
❑
Comment: Screenings and grit are disposed
at the CMS Landfill located in Concord, N.C. by
Republic Services.
Pump Station - Influent
Yes
No
NA
NE
Is the pump wet well free of bypass lines or structures?
■
❑
❑
❑
Is the wet well free of excessive grease?
0
❑
❑
❑
Are all pumps present?
0
❑
❑
❑
Are all pumps operable?
0
❑
❑
❑
Are float controls operable?
■
❑
❑
❑
Is SCADA telemetry available and operational?
0
❑
❑
❑
Is audible and visual alarm available and operational?
❑
❑
0
❑
Comment:
Equalization Basins
Yes
No
NA
NE
Is the basin aerated?
0
❑
❑
❑
Is the basin free of bypass lines or structures to the natural environment?
0
❑
❑
❑
Is the basin free of excessive grease?
■
❑
❑
❑
Are all pumps present?
■
❑
❑
❑
Are all pumps operable?
0
❑
❑
❑
Are float controls operable?
0
❑
❑
❑
Are audible and visual alarms operable?
❑
❑
0
❑
# Is basin size/volume adequate?
■
❑
❑
❑
Comment: The facility is equipped with a twelve (12) million gallon (MG) equalization
basin (2
— 6
MG cells) and a 1.3 MG day tank.
Primary Clarifier
Yes
No
NA
NE
Is the clarifier free of black and odorous wastewater?
0
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
0
❑
❑
❑
Are weirs level?
0
❑
❑
❑
Is the site free of weir blockage?
■
❑
❑
❑
Is the site free of evidence of short-circuiting?
0
❑
❑
❑
Is scum removal adequate?
0
❑
❑
❑
Page# 6
Permit: NCO036277
Inspection Date: 05/17/2024
Owner -Facility: McDowell Creek WWTP
Inspection Type: Compliance Evaluation
Primary Clarifier
Yes
No
NA
NE
Is the site free of excessive floating sludge?
0
❑
❑
❑
Is the drive unit operational?
0
❑
❑
❑
Is the sludge blanket level acceptable?
0
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately'/4
of the sidewall depth) 0
❑
❑
❑
Comment: Two of the five primary clarifiers were in service
Chemical Feed
Yes
No
NA
NE
Is containment adequate?
0
❑
❑
❑
Is storage adequate?
0
❑
❑
❑
Are backup pumps available?
0
❑
❑
❑
Is the site free of excessive leaking?
0
❑
❑
❑
Comment:
Nutrient Removal
Yes
No
NA
NE
# Is total nitrogen removal required?
0
❑
❑
❑
# Is total phosphorous removal required?
0
❑
❑
❑
Type
Biological
# Is chemical feed required to sustain process?
0
❑
❑
❑
Is nutrient removal process operating properly?
0
❑
❑
❑
Comment: Both 5-stage BNR trains (anaerobic, anoxic, oxic, post anoxic and re -aeration zones
were in service. Sugar water and micro -seed (glycerin) are added as carbon
supplements. Alum can also be added prior to the secondaries if needed.
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system
Diffused
Is the basin free of dead spots?
0
❑
❑
❑
Are surface aerators and mixers operational?
0
❑
❑
❑
Are the diffusers operational?
0
❑
❑
❑
Is the foam the proper color for the treatment process?
0
❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
■
❑
❑
❑
Is the DO level acceptable?
0
❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
■
❑
❑
❑
Page# 7
Permit: NC0036277 Owner -Facility: McDowell Creek WWTP
Inspection Date: 05/17/2024 Inspection Type: Compliance Evaluation
Aeration Basins
Yes
No
NA
NE
Comment: Aqueous lime is added in the primary clarifier effluent to maintain appropriate
alkalinity/pH levels.
Secondary Clarifier
Yes
No
NA
NE
Is the clarifier free of black and odorous wastewater?
■
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
■
❑
❑
❑
Are weirs level?
■
❑
❑
❑
Is the site free of weir blockage?
■
❑
❑
❑
Is the site free of evidence of short-circuiting?
■
❑
❑
❑
Is scum removal adequate?
■
❑
❑
❑
Is the site free of excessive floating sludge?
■
❑
❑
❑
Is the drive unit operational?
■
❑
❑
❑
Is the return rate acceptable (low turbulence)?
■
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
■
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
■
❑
❑
❑
Comment: Three of the four secondary clarifiers were in service.
Pumps-RAS-WAS
Yes
No
NA
NE
Are pumps in place?
■
❑
❑
❑
Are pumps operational?
■
❑
❑
❑
Are there adequate spare parts and supplies on site?
■
❑
❑
❑
Comment:
Filtration (High Rate Tertiary)
Yes
No
NA NE
Type of operation:
Down flow
Is the filter media present?
■
❑
❑
❑
Is the filter surface free of clogging?
■
❑
❑
❑
Is the filter free of growth?
■
❑
❑
❑
Is the air scour operational?
■
❑
❑
❑
Is the scouring acceptable?
■
❑
❑
❑
Is the clear well free of excessive solids and filter media?
■
❑
❑
❑
Comment: Nine of ten tertiary filters were in service.
Page# 8
Permit: NC0036277
Inspection Date: 05/17/2024
Owner -Facility: McDowell Creek WWTP
Inspection Type: Compliance Evaluation
Disinfection - UV
Yes
No
NA
NE
Are extra UV bulbs available on site?
0
❑
❑
❑
Are UV bulbs clean?
0
❑
❑
❑
Is UV intensity adequate?
■
❑
❑
❑
Is transmittance at or above designed level?
0
❑
❑
❑
Is there a backup system on site?
0
❑
❑
❑
Is effluent clear and free of solids?
0
❑
❑
❑
Comment:
Flow Measurement - Effluent
Yes
No
NA
NE
# Is flow meter used for reporting?
0
❑
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
0
❑
Comment: The flow meter is calibrated twice per year and was last calibrated on 1/18/24 by CITI
LLC.
Effluent Pipe
Yes
No
NA
NE
Is right of way to the outfall properly maintained?
0
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
■
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
■
❑
Comment: The effluent appeared clear with no floatable solids or foam. The receiving stream did
not appear to be negatively impacted.
Anaerobic Digester
Yes
No
NA
NE
Type of operation:
Fixed cover
Is the capacity adequate?
0
❑
❑
❑
# Is gas stored on site?
■
❑
❑
❑
Is the digester(s) free of tilting covers?
■
❑
❑
❑
Is the gas burner operational?
0
❑
❑
❑
Is the digester heated?
0
❑
❑
❑
Is the temperature maintained constantly?
0
❑
❑
❑
Is tankage available for properly waste sludge?
E
❑
❑
❑
Comment: The facility was using four anaerobic digesters (fixed cover) and one for storage
(floating cover).
Page# 9
Permit: NC0036277
Inspection Date: 05/17/2024
Solids Handling Equipment
Is the equipment operational?
Is the chemical feed equipment operational?
Owner -Facility: McDowell Creek WWTP
Inspection Type: Compliance Evaluation
Is storage adequate?
Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
Is the site free of sludge buildup on belts and/or rollers of filter press?
Is the site free of excessive moisture in belt filter press sludge cake?
The facility has an approved sludge management plan?
Yes
No
NA
NE
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
Comment: The facility is equipped with two gravity belt thickeners and two belt filter presses. All
units were operational: however, only one of each was in service. Dewatered
bio-solids are land applied by Synagro under the authority of Permit No. WQO000057.
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up
power?
Is the generator fuel level monitored?
Yes
No
NA
NE
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
❑
❑
❑
■
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
Comment: The facility is equipped with two generators that are serviced quarterly by Cummings.
Page# 10