HomeMy WebLinkAboutNC0024937_Compliance Evaluation Inspection_20240529ROY COOPER
Governor
ELIZABETH S. BISER
Secretary
RICHARD E. ROGERS, JR.
Director
Joseph Lockler, Operations Chief
Environmental Management Division
Charlotte Water
5100 Brookshire Blvd.
Charlotte, NC 28216
SUBJECT: Compliance Evaluation Inspection
Sugar Creek WRRF
NPDES Permit No. NCO024937
Mecklenburg County
Dear Mr. Lockler:
NORTH CAROLINA
Environmental Quality
May 29, 2024
Enclosed is a copy of the Compliance Evaluation Inspection (CEI) Report for the inspection conducted at the subject
facility on May 16, 2024, by Mr. Wes Bell of this Office. This Office would like to thank all Water Resources Recovery
Facility (WRRF) staff for their cooperation and assistance that was provided throughout this inspection. Please advise the
facility's Operator -in -Responsible Charge (ORC) of our findings by forwarding the enclosed report.
Should you have any questions concerning this report, please do not hesitate to contact Mr. Bell at (704) 235-2192 or at
wes.bell(a,deq.nc. gov.
Sincerely,
DocuSigned by:
A w N P-Lu"
F161 FB69A2D84A3...
Andrew H. Pitner, P.G.
Regional Supervisor
Water Quality Regional Operations Section
Mooresville Regional Office
Division of Water Resources, NCDEQ
Enclosure: Inspection Report
Cc: NPDES Program Files - Laserfiche
el- DEQ��
North Carolina Department of Environmental quality I Divisionof Water Resources
Mooresville Regional Office 1 610 East Center Avenue, Suite 301 1 Mooresville, North Carolina 28115
704.6631699
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NCO024937 111 121 24/05/17 I17 18 LC] I 19 I s I 20L]
21111I I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
2.0 701d I 71 I„ I 72 I r., I 71 I 74 79 I I I I I I I80
L—I ty L-1 I I
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
09:20AM 24/05/17
24/03/01
Sugar Creek WRRF
5301 Closeburn Rd
Exit Time/Date
Permit Expiration Date
Charlotte NC 28217
01:26PM 24/05/17
28/08/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Donna Marie Slachciak/ORC/704-553-2124/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Angela D Charles,5100 Brookshire Blvd Charlotte NC
282163371/Director/704-336-5911/ No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Sludge Handling Dispo: Facility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Wes Bell signed by: DWR/MRO WQ/704-235-2192/ 5/29/2024
2 re&
E�Docu`,','�96D90=437
...
9"RiOeAReviewer Agency/Office/Phone and Fax Numbers Date
Signature of MP7F161FB69A2D84A3..
Andrew Pit'0-4 `' H P WR/MRO WQ/704-663-1699 Ext.2180/ 5/29/2024
.
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NC0024937 I11 12I 24/05/17 117 18 i c i
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On -site Representatives:
The following Charlotte Water staff were in attendance during the inspection: Ms. Donnna Slachciak
and Messrs. Darrell DeWitt, Dan Messenger, and Mike Christiansen.
Page#
Permit: NCO024937 Owner -Facility: Sugar Creek WRRF
Inspection Date: 05/17/2024 Inspection Type: Compliance Evaluation
Permit
Yes
No
NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
■
❑
application?
Is the facility as described in the permit?
■
❑
❑
❑
# Are there any special conditions for the permit?
■
❑
❑
❑
Is access to the plant site restricted to the general public?
■
❑
❑
❑
Is the inspector granted access to all areas for inspection?
■
❑
❑
❑
Comment: Charlotte Water implements a Division -approved Industrial Pretreatment Program.
The last compliance evaluation inspection at this facility was performed by DWR staff
on 2/22/22.
Record Keeping
Yes
No
NA
NE
Are records kept and maintained as required by the permit?
■
❑
❑
❑
Is all required information readily available, complete and current?
■
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
■
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
■
❑
❑
❑
Is the chain -of -custody complete?
■
❑
❑
❑
Dates, times and location of sampling
■
Name of individual performing the sampling
■
Results of analysis and calibration
■
Dates of analysis
■
Name of person performing analyses
■
Transported COCs
■
Are DMRs complete: do they include all permit parameters?
■
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
■
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
■
❑
❑
❑
operator on each shift?
Is the ORC visitation log available and current?
■
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
■
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility
■
❑
❑
❑
classification?
Is a copy of the current NPDES permit available on site?
■
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
■
❑
❑
❑
Page# 3
Permit: NCO024937
Inspection Date: 05/17/2024
Owner -Facility: Sugar Creek WRRF
Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Comment: The records reviewed durinq the inspection were organized and well maintained.
In-depth operation and maintenance records including process control measurements
were being documented and maintained on -site.
Discharge monitoring reports (eDMRs) were reviewed for the period April 2023 through
March 2024. No effluent limit and/or monitoring violations were noted.
Laboratory
Yes
No
NA NE
Are field parameters performed by certified personnel or laboratory?
0
❑
❑ ❑
Are all other parameters(excluding field parameters) performed by a certified lab?
0
❑
❑ ❑
# Is the facility using a contract lab?
0
❑
❑ ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
❑
❑
■ ❑
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
0 ❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
❑
0 ❑
Comment: Influent and effluent analyses (including field parameters) are performed by
Charlotte
Water's Environmental Services Laboratory (Certification #192). Waypointe Analytical,
ETT Environmental (chronic toxicity) and Environmental Testing Solutions
(chronic
toxicity) have all been contracted to provide analytical support.
Influent Sampling
# Is composite sampling flow proportional?
Is sample collected above side streams?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Is sampling performed according to the permit?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑
Comment: The subject permit requires influent BOD and TSS composite samples. The sampler
operation is checked daily by on -site staff and calibrated twice per month.
Effluent Sampling
Yes
No
NA
NE
Is composite sampling flow proportional?
0
❑
❑
❑
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
■
❑
❑
❑
degrees Celsius)?
Page# 4
Permit: NCO024937
Inspection Date: 05/17/2024
Owner -Facility: Sugar Creek WRRF
Inspection Type: Compliance Evaluation
Effluent Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type 0 ❑ ❑ ❑
representative)?
Comment: The subject permit requires composite and grab effluent samples. The sampler
operation is checked daily by on -site staff and calibrated twice per month.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable 0 ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The wastewater treatment facility appeared to be properly operated and well
maintained. The operations staff incorporate a comprehensive process control
program.
The facility is equipped with a SCADA system that is accessible at eleven (11) locations
throughout the plant site.
Odor control systems are connected to the influent pump station/screening & grit
removal facilities and primary clarifiers.
Bar Screens
Yes
No
NA NE
Type of bar screen
a.Manual
❑
b.Mechanical
Are the bars adequately screening debris?
0
❑
❑
❑
Is the screen free of excessive debris?
■
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Comment:
Grit Removal Yes No NA NE
Type of grit removal
a.Manual
❑
b.Mechanical
Is the grit free of excessive organic matter?
0
❑
❑
❑
Is the grit free of excessive odor?
0
❑
❑
❑
# Is disposal of grit in compliance?
0
❑
❑
❑
Comment: Screenings and grit are disposed at the CMS Landfill located in Concord,
N.C. by
Republic Services.
Page# 5
Permit: NCO024937
Inspection Date: 05/17/2024
Owner -Facility: Sugar Creek WRRF
Inspection Type: Compliance Evaluation
Pump Station - Influent
Yes
No
NA
NE
Is the pump wet well free of bypass lines or structures?
0
❑
❑
❑
Is the wet well free of excessive grease?
0
❑
❑
❑
Are all pumps present?
0
❑
❑
❑
Are all pumps operable?
0
❑
❑
❑
Are float controls operable?
0
❑
❑
❑
Is SCADA telemetry available and operational?
0
❑
❑
❑
Is audible and visual alarm available and operational?
❑
❑
■
❑
Comment:
Equalization Basins
Yes
No
NA
NE
Is the basin aerated?
❑
❑
■
❑
Is the basin free of bypass lines or structures to the natural environment?
0
❑
❑
❑
Is the basin free of excessive grease?
0
❑
❑
❑
Are all pumps present?
0
❑
❑
❑
Are all pumps operable?
■
❑
❑
❑
Are float controls operable?
0
❑
❑
❑
Are audible and visual alarms operable?
❑
❑
0
❑
# Is basin size/volume adequate?
0
❑
❑
❑
Comment: The facility is equipped with two twenty (20) million gallon equalization basins (East and
West). The West EQ basin flow is returned back to the head of the plant while the East
EQ basin flow is diverted into the outfall line to Charlotte Water's McAlpline
Creek
wastewater treatment facility.
Primary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the sludge blanket level acceptable?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 6
Permit: NCO024937
Inspection Date: 05/17/2024
Owner -Facility: Sugar Creek WRRF
Inspection Type: Compliance Evaluation
Primary Clarifier
Yes
No
NA
NE
Comment: All four primary clarifiers were operational;
however, only two were in service.
Chemical Feed
Yes
No
NA
NE
Is containment adequate?
0
❑
❑
❑
Is storage adequate?
0
❑
❑
❑
Are backup pumps available?
0
❑
❑
❑
Is the site free of excessive leaking?
■
❑
❑
❑
Comment:
Nutrient Removal
Yes
No
NA
NE
# Is total nitrogen removal required?
0
❑
❑
❑
# Is total phosphorous removal required?
0
❑
❑
❑
Type
Biological
# Is chemical feed required to sustain process?
0
❑
❑
❑
Is nutrient removal process operating properly?
0
❑
❑
❑
Comment: Each aeration basin is equipped with an anoxic zone (with mixinq) and oxic recvcle
system to reduce nutrient levels. Alum can also be added to the secondary clarifier
influent for the reduction of the phosphorus levels.
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system
Diffused
Is the basin free of dead spots?
0
❑
❑
❑
Are surface aerators and mixers operational?
0
❑
❑
❑
Are the diffusers operational?
0
❑
❑
❑
Is the foam the proper color for the treatment process?
0
❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
❑
■
❑
❑
Is the DO level acceptable?
0
❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
■
❑
❑
❑
Comment: All six (6) aeration basins were in service. Magnesium hydroxide is added to maintain
appropriate alkalinity/pH levels. Foam covered more than 25% of the basins: however,
minimal foam carryover was observed in the secondaries.
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Yes No NA NE
■ ❑ ❑ ❑
Page# 7
Permit: NCO024937
Inspection Date: 05/17/2024
Owner -Facility: Sugar Creek WRRF
Inspection Type: Compliance Evaluation
Secondary Clarifier
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
Comment: All six (6) secondary clarifiers were in service.
Pumps-RAS-WAS
Are pumps in place?
Are pumps operational?
Are there adequate spare parts and supplies on site?
Comment:
Filtration (High Rate Tertiary)
Type of operation:
Is the filter media present?
Is the filter surface free of clogging?
Is the filter free of growth?
Is the air scour operational?
Is the scouring acceptable?
Is the clear well free of excessive solids and filter media?
Comment: All ten (10) tertiary filters were in service.
Disinfection - UV
Are extra UV bulbs available on site?
Are UV bulbs clean?
Is UV intensity adequate?
Is transmittance at or above designed level?
Yes
No
NA
NE
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
Yes No NA NE
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Yes No NA NE
Down flow
❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ❑ ■
Yes No NA NE
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Page# 8
Permit: NCO024937
Inspection Date: 05/17/2024
Owner -Facility: Sugar Creek WRRF
Inspection Type: Compliance Evaluation
Disinfection - UV
Yes
No
NA
NE
Is there a backup system on site?
0
❑
❑
❑
Is effluent clear and free of solids?
0
❑
❑
❑
Comment:
Flow Measurement - Effluent
Yes
No
NA
NE
# Is flow meter used for reporting?
0
❑
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
0
❑
Comment: The flow meter is calibrated twice per year and was last calibrated on 1/17/24 by CITI
LLC.
Effluent Pipe
Yes
No
NA
NE
Is right of way to the outfall properly maintained?
❑
❑
0
❑
Are the receiving water free of foam other than trace amounts and other debris?
■
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
■
❑
Comment: The effluent appeared clear with no floatable solids and foam (entrained air). The
foam typically dissipates less than fifty (50) yards downstream of the discharge outfall.
The receiving stream did not appear to be negatively impacted.
Solids Handling Equipment
Is the equipment operational?
Is the chemical feed equipment operational?
Is storage adequate?
Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
Is the site free of sludge buildup on belts and/or rollers of filter press?
Is the site free of excessive moisture in belt filter press sludge cake?
The facility has an approved sludge management plan?
Yes No NA NE
■ ❑ ❑ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ❑
Comment: Primary sludge and waste activated sludge are pumped separately to Charlotte
Water's McAlpine Creek wastewater treatment facility for continued treatment and
disposal. Dewatered bio-solids are land applied by Synagro under the authority of
Permit No. WQ0000057.
Standby Power Yes No NA NE
Is automatically activated standby power available? 0 ❑ ❑ ❑
Is the generator tested by interrupting primary power source? 0 ❑ ❑ ❑
Page# 9
Permit: NC0024937 Owner -Facility: Sugar Creek WRRF
Inspection Date: 05/17/2024 Inspection Type: Compliance Evaluation
Standby Power Yes No NA NE
Is the generator tested under load?
0
❑
❑
❑
Was generator tested & operational during the inspection?
❑
❑
❑
■
Do the generator(s) have adequate capacity to operate the entire wastewater site?
0
❑
❑
❑
Is there an emergency agreement with a fuel vendor for extended run on back-up
0
❑
❑
❑
power?
Is the generator fuel level monitored?
0
❑
❑
❑
Comment: The facility is equipped with three generators that are serviced quarterly by Carolina
CAT.
Page# 10