HomeMy WebLinkAboutWQ0011360_Routine Compliance Inspection_20240425 Compliance Inspection Report
Permit:WQ0011360 Effective: 07/02/19 Expiration: 10/31/24 Owner: Murphy-Brown LLC
SOC: Effective: Expiration: Facility: Tarheel Sanitation Trailer Wash
County: Bladen 1023 Purdie Hall Rd
Region: Fayetteville
Tar Heel NC 28392
Contact Person:Gregg P Schmidt Title: Phone: 910-293-3434
Directions to Facility:
From Fayetteville, take highway 87 toward Elizabethtown. at the intersection of highway 87 and highway 20, turn right onto highway
20 and then turn left onto purdie hall road. Drive approx. 1.50 miles and turn left onto the enterance road for the Tar T
System Classifications: SI,
Primary ORC: Michael L Cudd Certification: 994597 Phone: 910-217-1836
Secondary ORC(s):
Ronald Lee Matthews 995905 910-281-3146
On-Site Representative(s):
Related Permits:
Inspection Date: 04/25/2024 Entry Time 09:OOAM Exit Time: 11:OOAM
Primary Inspector:Erica L Fenza DocuSigned by:
� � 5/9/2024 Phone: 910-433-3322
EF—
Secondary �icU Inspector(s): Docusigned by:
03EOOFAC710A40F... bm 6/13/2024
E 691DB248E_
Reason for Inspection: Routine Inspection Type: Compliance Evaluation
Permit Inspection Type: Wastewater Irrigation
Facility Status: Compliant ❑ Not Compliant
Question Areas:
Treatment Flow Measurement-Effluent Treatment Flow Measurement-Influent Miscellaneous Questions
Treatment Flow Measurement-Water Treatment Treatment Barscreen
Use Records
Record Keeping Treatment Lagoons End Use-Irrigation
Treatment Influent Pump Station Treatment Flow Measurement Storage
Wells
(See attachment summary)
Page 1 of 5
Permit: WQ0011360 Owner-Facility:Murphy-Brown LLC
Inspection Date: 04/25/2024 Inspection Type:Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
Went out on 4/25/2024 and met with ORC Mike Cudd.
Lagoon banks were well-mowed with no trees, lagoon level was at 34in.
Residual solids are being dehydrated and separated into a dumpster that McGill MC/GFL takes and disposes of
accordingly--this info should be recorded and kept(Ex. - records of how many loads, weight of loads, when they are taken,
etc.)
During Compliance Inspection, all NDMR and Grab Sample records were reviewed for any errors or discrepencies.
EnviroChem does all sampling for this truck wash site.
Spray fields had overall good cover crop health/maintenance, but needed to be harvested soon.
The following Monitoring Wells have exceede past these limits:
MW-1
03-2023 (Nitrogen, Nitrate Total N) Limit 10 and Calculated value 11.5
03-2024 (Nitrogen, Nitrate,Total N) Limits 10 and Calculated value 12.1
07-2023 (Nitrogen, Nitrate,Total N) Limit 10 and Calculated value 16.7
11-2023 (Nitrogen, Ammonia) Limit 1,500 and Calculated value 4,600.
M W-2
07-2023 (Nitrogen, Nitrate Total N) Limit 10 and calculated value 12.2
Page 2 of 5
Permit: WQ0011360 Owner-Facility:Murphy-Brown LLC
Inspection Date: 04/25/2024 Inspection Type:Compliance Evaluation Reason for Visit: Routine
Type Yes No NA NE
Reuse(Quality) ❑
Infiltration System ❑
Single Family Spray, LR ❑
Activated Sludge Spray, LR ❑
Activated Sludge Spray, HR ❑
Activated Sludge Drip, LR ❑
Recycle/Reuse ❑
Single Family Drip ❑
Lagoon Spray, LR
Treatment Yes No NA NE
Are Treatment facilities consistent with those outlined in the current permit? 0 ❑ ❑ ❑
Do all treatment units appear to be operational? (if no, note below.) 0 ❑ ❑ ❑
Comment:
Treatment Influent Pump Station Yes No NA NE
Is the pump station free of bypass lines or structures? 0 ❑ ❑ ❑
Is the general housekeeping acceptable? ❑ ❑ ❑
Are all pumps present? ❑ ❑ ❑
Are all pumps operable? ❑ ❑ ❑
Are floats/controls operable? ❑ ❑ ❑
Are audio and visual alarms available? ❑ ❑ 0 ❑
Are audio and visual alarms operational? ❑ ❑ ❑
#Are SCADA/Telemetry alarms required? ❑ ❑ ❑
Are SCADA/Telemetry available? ❑ ❑ ❑
Are SCADA/Telemetry operational? ❑ ❑ 0 ❑
Comment:
Treatment Flow Measurement-Influent Yes No NA NE
Is flowmeter calibrated annually? ❑ ❑ ❑
Is flowmeter operating properly? ❑ ❑ ❑
Does flowmeter monitor continuously? ❑ ❑ ❑
Does flowmeter record flow? ❑ ❑ ❑
Does flowmeter appear to monitor accurately? 0 ❑ ❑ ❑
Comment: Reviewed records for March 2024 NMDR and Grab Samples for any errors.
Treatment Flow Measurement-Water Use Records Yes No NA NE
Page 3 of 5
Permit: WQ0011360 Owner-Facility:Murphy-Brown LLC
Inspection Date: 04/25/2024 Inspection Type:Compliance Evaluation Reason for Visit: Routine
Is water use metered? 0 ❑ ❑ ❑
Are the daily average values properly calculated? 0 ❑ ❑ ❑
Comment:
Treatment Flow Measurement-Effluent Yes No NA NE
Is flowmeter calibrated annually? 0 ❑ ❑ ❑
Is flowmeter operating properly? 0 ❑ ❑ ❑
Does flowmeter monitor continuously? 0 ❑ ❑ ❑
Does flowmeter record flow? 0 ❑ ❑ ❑
Does flowmeter appear to monitor accurately? 0 ❑ ❑ ❑
Comment:
Treatment Barscreen Yes No NA NE
Is it free of excessive debris? ❑ ❑ ❑
Is disposal of screenings in compliance? ❑ ❑ ❑
Are the bars spaced properly? ❑ ❑ ❑
Is the unit in good condition? ❑ ❑ ❑
Comment:
Record Keeping
Yes No NA NE
Is a copy of current permit available? 0 ❑ ❑ ❑
Are monitoring reports present: NDMR? ❑ ❑ ❑
NDAR? ❑ ❑ ❑
Are flow rates less than of permitted flow? ❑ ❑ ❑
Are flow rates less than of permitted flow? ❑ ❑ ❑
Are application rates adhered to? ❑ ❑ ❑
Is GW monitoring being conducted, if required (GW-59s submitted)? ❑ ❑ ❑
Are all samples analyzed for all required parameters? ❑ ❑ ❑
Are there any 2L GW quality violations? ❑ ❑ ❑
Is GW-59A certification form completed for facility? ❑ ❑ ❑
Is effluent sampled for same parameters as GW? ❑ ❑ ❑
Do effluent concentrations exceed GW standards? ❑ ❑ ❑
Are annual soil reports available? ❑ ❑ ❑
#Are PAN records required? ❑ ❑ ❑
#Did last soil report indicate a need for lime? ❑ ❑ ❑
If so, has it been applied? ❑ ❑ ❑
Are operational logs present? ❑ ❑ ❑
Are lab sheets available for review? 0 ❑ ❑ ❑
Page 4 of 5
Permit: WQ0011360 Owner-Facility:Murphy-Brown LLC
Inspection Date: 04/25/2024 Inspection Type:Compliance Evaluation Reason for Visit: Routine
Do lab sheets support data reported on NDMR? 0 ❑ ❑ ❑
Do lab sheets support data reported on GW-59s? 0 ❑ ❑ ❑
Are Operational and Maintenance records present? 0 ❑ ❑ ❑
Were Operational and Maintenance records complete? 0 ❑ ❑ ❑
Has permittee been free of public complaints in last 12 months? 0 ❑ ❑ ❑
Is a copy of the SOC readily available? ❑ ❑ 0 ❑
No treatment units bypassed since last inspection? 0 ❑ ❑ ❑
Comment: One of the monitoring wells exceeded limitations--MW-1, exceeded its limits for months March,
July and November 2023.
Reviewed NDMR records and Grab Samples records for March 2024.
Paperwork was looked over to confirm ORC and backup ORC.
End Use-Irrigation Yes No NA NE
Are buffers adequate? ❑ ❑ ❑
Is the cover crop type specified in permit? ❑ ❑ ❑
Is the crop cover acceptable? ❑ ❑ ❑
Is the site condition adequate? ❑ ❑ ❑
Is the site free of runoff/ponding? ❑ ❑ ❑
Is the acreage specified in the permit being utilized? ❑ ❑ ❑
Is the application equipment present? ❑ ❑ ❑
Is the application equipment operational? ❑ ❑ ❑
Is the disposal field free of limiting slopes? ❑ ❑ ❑
Is access restricted and/or signs posted during active site use? ❑ ❑ ❑
Are any supply wells within the CB? ❑ ❑ ❑
Are any supply wells within 250' of the CB? ❑ ❑ ❑
How close is the closest water supply well? ❑ ❑ ❑
Is municipal water available in the area? ❑ ❑ ❑
# Info only: Does the permit call for monitoring wells? ❑ ❑ ❑
Are GW monitoring wells located properly w/respect to RB and CB? ❑ ❑ ❑
Are GW monitoring wells properly constructed, including screened interval? ❑ ❑ ❑
Are monitoring wells damaged? ❑ 0 ❑ ❑
Comment: Monitoring wells are in tact, well maintained and fully operational.
Page 5 of 5