HomeMy WebLinkAboutNCG551527_Compliance Evaluation Inspection_20231220ROY COOPER
covemor
ELIZABETH S. BISER
Secreft y
RICHARD E. ROGERS, JR.
Dlmyw
Joshua and Jamie Mills
8013 Salix Drive
Durham N.C. 27713
NORTH CAROLINA
Enldhm mental Quality
January 26, 2023
Subject: Compliance Evaluation Inspection
Single Family Wastewater Treatment System
General NPDES Permit NCG550000
Certificate of coverage NCG551527
Facility: 8013 Salix Drive
Durham County
Dear Mr. Mills,
On December 20, 2023, Curtis Tyree from the Raleigh Regional Office visited your single-
family residence (SFR) wastewater treatment system to evaluate compliance with the subject
General NPDES Permit.
Our records indicate the treatment system consists of a septic tank; a distribution box; a primary
sand filter; a tablet chlorinator; a chlorine contact chamber; and a discharge pipe.
General NPDES Permit NCG550000 and Certificate of Coverage (COC) NCG551527 authorize
the discharge of domestic wastewater from your treatment system to an unnamed tributary to
Northeast Creek, in the Cape Fear River Basin..
Findings during the inspection were as follows:
I. The septic tank shall be checked annually and pumped out every 3 to 5 years. The septic
tank was pumped out in February 2023.
2. Treatment system operation. The treatment system shall be maintained at all times to
prevent seepage of sewage to the surface of the ground. At the time of the inspection, the
system appeared to be well maintained.
3. Chlorination. The tablet chlorinator shall be inspected weekly to ensure there is an
adequate supply of tablets for continuous and proper operation. Wastewater grade tablets
(calcium hypochlorite) shall be added as needed to provide proper chlorination
(swimming pool chlorine tablets shall not be used). At the time of the inspection, the
chlorinator had a sufficient amount of tablets and correct type of tablets are being used..
F North Carolina Department of Environmental Quality r Division of Water Resourtes
Raleigh Regional Office I 3800 Barren Drive I Raleigh, North Carolina 27609
919,'M 4200
4. Outfall location. A visual review of the outfall location shall be executed twice each year
(one at the time of sampling) to ensure that no visible solids or other obvious evidence of
system malfunctioning is observed Any visible signs of a malfunctioning system shall be
documented, and steps taken to correct the problem. At the time of the inspection, the
outfall location was clear and appeared to be well maintained and free of any obstructions.
There was no water discharging at the time of the inspection.
5. Effluent sampling requirements. Effluent sampling must be conducted annually as part
of your permit requirements. The effluent samples must be analyzed by a North Caroline
Certified Lab and the results must be kept on site for three years. There were no effluent
sampling results available at the time of inspection.
G. Fees and renewals. COC's with unpaid administering and compliance monitoring fees
will not be automatically renewed The fees must be paid annually and within 30 days of
notification. All fees have been paid.
If you have questions or comments about this inspection or the requirements of your permit,
please contact Curtis Tyree via email at curtis jyree a)dea.gc,.Aov or 919-791-4251.
Sincerely,
Vanessa E. Manuel, Assistant Regional Supervisor
Water Quality Regional Operations Section
Raleigh Regional Office
Division of Water Resources, NCDEQ
Attachment: EPA Water Compliance Inspection Report
Cc: Laserfiche
North Carolina Department of Environmental Quality l Division of Water Resources
512 North Salisbury Street 1 1611 Mail Service Center l Raleigh, North Carolina 27699-1611
�� 419.707.9000
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yrlmo/day Inspection Type Inspector Fac Type
1
j�j 2 L3I NCG551527 11 12 23/12/20 17 18 IC 19 G 20U
21
_LLg
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 CIA Reserved
67
701 I 71 I f 72 i ti I 731 I 174 7 _LLU80
LJ li LJ LLJ
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
09:55AM 23/12/20
17/02/24
8013 Salix Drive
Exit Time/Date
Permit Expiration Dale
p
8013 Salix Dr
Durham NC 27713
10:15AM 23/12/20
18/07/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
1/1
Name, Address of Responsible OfficialMtle/Phone and Fax Number
Joshua Mills,8013 Salix Dr Durham NC 27713//919-621-2734/ Contacted
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Operations & Maintenar Sludge Handling Dispo: 0 Facility Site Review Effluent/Receiving Wate
Laboratory Other
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
CurtisYree DWR/RRO W01919-791-42391
r
J/011*"
/-I L
Signature of Mana ent O A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yrlmolday inspection Type
NCG551527 I1 1 23/12/20 117 118 1 c,
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
The permitte was not home at the time of inspection. through a phone conversation with the
permittee, he told me that the septic tank hadbeen pumped out in February of 2023. The system
appeared to be well maintained. The effluent pipe was a little difficult to find but the permittee knew
where it was located and he will try to keep it maintained a little better.
Page# 2
Permit: NCG551527 Owner - Facility: 8013 Salix Drive
Inspection Date: 12/20/2023 Inspection Type: Compliance Evaluation
Other Yes No NA NE
Comment:
Operations $ Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ 0 ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained? 0 ❑ ❑ ❑
Are the receiving water free of foam other than trace amounts and other debris? 0 ❑ ❑ ❑
If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ M ❑
Comment:
Septic Tank
Yes
No
NA NE
(If pumps are used) Is an audible and visual alarm operational?
❑
❑
❑
❑
Is septic tank pumped on a schedule?
❑
❑
❑
Are pumps or syphons operating properly?
❑
❑
No
Are high and low water alarms operating properly?
❑
❑
M
❑
Comment:
Sand Filters (Low rate)
Yes
No
NA NE
(If pumps are used) Is an audible and visible alarm Present and operational?
❑
❑
M
❑
Is the distribution box level and watertight?
❑
❑
❑
Is sand filter free of ponding?
❑
❑
❑
Is the sand filter effluent re -circulated at a valid ratio?
❑
❑
M
❑
# Is the sand filter surface free of algae or excessive vegetation?
M
❑
❑
❑
# Is the sand filter effluent re -circulated at a valid ratio? (Approximately 3 to 1)
❑
❑
■
❑
Comment: The sand filters appear to be operating as designed
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory? ❑ ❑ 0 ❑
Are all other parameters(excluding field parameters) performed by a certified lab? ❑ ❑ 0 ❑
Page# 3
A r
Permit: NCG551527 Owner - Facility: 8013 Salix Drive
Inspection Bate: 12/20/2023 Inspection Type: Compliance Evaluation
Laboratory
Yes
No NA NE
# Is the facility using a contract lab?
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
❑
❑
❑
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
M
❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
[]
M
❑
Comment:
Disinfection -Tablet
Are tablet chlorinators operational?
Are the tablets the proper size and type?
Number of tubes in use?
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de -chlorination?
Comment: The correct lype tablets are in use
Yes
No NA NE
M
❑
❑
❑
00011
2
■
❑
❑
❑
■
❑
❑
❑
❑
❑
■
❑
Page# 4