Loading...
HomeMy WebLinkAboutWQ0045474_More Information (Requested)_20240604WQ0045474 M&H Storage - Request for Additional Information 0 Cocanower, Jordan M To ron@tcgpa.com Cc Tharrington, Tom Mr. CuLlipher 0 <-D Reply <t Reply All —> Forward ® E I am writingto you regarding the fast -track sewer extension application for M&H Storage (W00045474) Please receive this message as a formal request for additional information. Tue 6/4/2024 2:19 PM I have conducted a preliminary review of the application and supporting documents for the subject application. In accordance with 15A NCAC 02T.0107, please provide the information requested below: The pump station is provided as a simplex station fora commercial building over 600 GPD flow. Simplex pump stations are considered alternative designs, and anew application must be submitted to the Central Office (Raleigh) if this is the route you would like to go. If you wish this to remain in fast track, please revise the FTA so that two pumps are provided for the pump station. 2. Please provide a revised page 3 of the FTA where Section 6. Is filled out to denote what power reliability option the applicant wishes to opt for. 3. Please confirm that there are no pump stations between the proposed project and the downstream treatment facility Per 15A NCAC 2T .0107(e) please submit this information within 30 days. Please reach out with any questions you may have. I appreciate your time. Jordan C Jordan Cocanower Biological Engineer Department of Water -Resources North Carolina Department of Environmental Quality Office: (910) 796-7345 Address: 127 Cardinal Drive Ext., Wilmington NC 28405 D_E Email correspondence to and from this address is subject to the North Carolina Public Records Law and may be disclosed to third parties