Loading...
HomeMy WebLinkAboutNCG060428_Tier 1 Response_20221205 RECEIVED Mooresville Regional Office DEC 0 5 2022 Tier 1 response. NCDEQ To Whom it may concern, Public Water Supply The UTZ Quality Foods facility performed the first storm water sampling and had a benchmark exceedance for COD and pH.The report is included with this letter. After investigating possible causes, it was determined the area around our trash compactor was not properly cleaned causing excessive run off of food waste.This was the most probable cause for the COD Exceedance.The plan is to clean the area immediately and the long-term plan is to add a concrete containment curb around the compactor. pH testing was performed off site and therefore caused the results to be in-valid.A pH meter was purchased, and all future testing will be performed on site. We will log all information into the SWPPP as directed by the Permit. Regards, David W. Moore Facility/Maintenance Manager 237 Industrial Drive Kings Mountain, NC 28086 DavidmooreCcDutzsnacks.com Cell: 704-476-0823 Desk: 828-565-7452 ftft. CELEBRATE iu,Ice �u Waypoint 449 Springbrook Rd,Charlotte, NC 28217 Main 704.5.529.63646364 ANALYTICAL www.waypointanalytical.com 11/3/2022 RECEIVED Utz Quality Foods, LLC- Kings Mountain Plant Mooresville Regional Office David Moore 237 Industrial Drive King's Mountain, INC, 28086 DEC U 5 2022 Ref: Analytical Testing NCDEQ Lab Report Number: 22-299-0021 PUbIIC Client Project Description: Quarterly Stormwater Samples water Supply Dear David Moore: Waypoint Analytical, LLC (Charlotte) received sample(s)on 10/26/2022 for the analyses presented in the following report. The above referenced project has been analyzed per your instructions. The analyses were performed in accordance with the applicable analytical method. The analytical data has been validated using standard quality control measures performed as required by the analytical method. Quality Assurance, method validations, instrumentation maintenance and calibration for all parameters were performed in accordance with guidelines established by the USEPA(including 40 CFR 136 Method Update Rule May 2021) unless otherwise indicated. Certain parameters (chlorine, pH, dissolved oxygen, sulfite...)are required to be analyzed within 15 minutes of sampling. Usually, but not always, any field parameter analyzed at the laboratory is outside of this holding time. Refer to sample analysis time for confirmation of holding time compliance. The results are shown on the attached Report of Analysis(s). Results for solid matrices are reported on an as- received basis unless otherwise indicated.This report shall not be reproduced except in full and relates only to the samples included in this report. Please do not hesitate to contact me or client services if you have any questions or need additional information. Sincerely, 411X Jamie Corporaal Laboratory Project Manager Laboratory's liability in any claim relating to analyses performed shall be limited to, at laboratory's option, repeating the analysis in question at laboratory's expense, or the refund of the charges paid for performance of said analysis. Page 1 of 6 Wrt� /r1OI�} 449 Springbrook Rd,Charlotte, .5 26364 QYN ` Main 704.529.6364 ANALYTICAL www.waypointanalytical.com Certification Summary Laboratory ID: WP CNC: Waypoint Analytical Carolina, Inc. (C), Charlotte, NC State Program Lab ID Expiration Date North Carolina State Program 37735 07/31/2023 North Carolina State Program 402 12/31/2022 South Carolina State Program 99012 07/31/2023 South Carolina State Program 99012 12/31/2022 Page 1 of 1 00016122-299-0021 Page 2 of 6 Waypoint. 449 Springbrook Rd, Charlotte, .5 28264 Maln 704.529.6364 ANALYTICAL www.waypointanalytical.com Sample Summary Table Report Number: 22-299-0021 Client Project Description: Quarterly Stormwater Samples Lab No Client Sample ID Matrix Date Collected Date Received 91571 Stormwater Aqueous 10/26/2022 11:15 10/26/2022 12:35 Page 3 of 6 Waypoint. 949 5pringbrook Rd,Charlotte, NC 28217 Main 709.5.529.636464 ANALYTICAL www.waypointanalytical.com 00299 Utz Quality Foods,LLC-Kings Mountain Plant Project Quarterly Stormwater Samples David Moore Report Date : 11/03/2022 237 Industrial Drive Information: Received : 10/26/2022 King's Mountain , NC 28086 Report Number:22-299-0021 REPORT OFANAL YSIS Lab No: 91571 Matrix: Aqueous Sample ID :Stormwater Sampled: 10/26/2022 11:15 Test Results Units MQL DF Date/Time By Analytical Analyzed Method COD(Chemical Oxygen Demand) 160 mg/L 50 1 11/O1122 10:18 SMW 5220D-2011 SGT HEM: Non-Polar Material <6A mg/L 6.4 1 10/27/22 09:30 SLO 1664B-SGf PH 9.7 H S.U. 1 10/27/22 14:50 CUB 4500H+B-2011 Total Suspended Solids 6.5 mg/L 4.1 1 10/28/22 11:35 CM] 2540D-2015 Qualifiers/ OF Dilution Factor H Beyond holding time Definitions MQL Method Quantitation Limit Page 4 of 6 Waypoi nt 449 Springbrook Rd,Charlotte, NC 28217 Main 704.529.6364 ANALYTICAL www.waypointanalOcal.com Shipment Receipt Form Customer Number:00299 Customer Name: Utz Quality Foods, LLC - Kings Mountain Plant Report Number: 22-299-0021 Shipping Method U Fed Ex ( t US Postal • Lab Other : F � (_! UPS _ Client Courier Thermometer ID: IRT-15 2.8C Shipping container/cooler uncompromised? Yes _) No Number of coolers/boxes received Custody seals intact on shipping container/cooler? Yes No (4) Not Present Custody seals intact on sample bottles? Yes '1 No (.0) Not Present Chain of Custody (COC) present? ! Yes L) No COC agrees with sample label(s)? • Yes j No COC properly completed • Yes No Samples in proper containers? • Yes ) No Sample containers intact? • Yes No No Sufficient sample volume for indicated test(s)? • Yes ) No All samples received within holding time? • Yes hl No Cooler temperature in compliance? • Yes No Cooler/Samples arrived at the laboratory on ice. •_ Yes ;` No Samples were considered acceptable as cooling process had begun. Water-Sample containers properly preserved • Yes ^) No N/A Water-VOA vials free of headspace Yes (D No (6) N/A Trip Blanks received with VOAs Yes No N/A Soil VOA method 5035—compliance criteria met Yes i^_) No #) N/A High concentration container(48 hr) F Low concentration EnCore samplers (48 hr) High concentration pre-weighed (methanol-14 d) Low conc pre-weighed vials (Sod Bis-14 d) Special precautions or instructions included? Yes No Comments: Signature: ngelo Norvell Date &Time: 10/26/2022 14:18:58 Page 5 of 6 • CHAIN OF CUSTODY RECORD LAB USE ONLY Waypoint. PAGE _ OF _ QUOTE/TOENSURE PROPER BILLING YES NO WA -I Samples INTACT upon arnV81? _ ANALYTICAL Project Name: Received IN ICE? 449 Springbrook Road•Charlotte,NC 28217 Short Hold Analysis es [No) UST Pro ecl: Yes IN PROPER PRESERVATIVES indicated? T _ Phone 7G41529.6364 • Fax:7041625.0409 Y (Y ) ( 1 (Yes) ( ) — 'Please ATTACH any project specific reporting(OC LEVEL 1 II III IY) Received WITHIN HOLDING TIMES? _ Client Company Name: La? S/3rK 1CS provisions and/or OC Requirements CUSTODY SEALS INTACT? Report To/Contact Name: LDK.J 1 2 I4! V WIwIv_ Invoice To: VOLATILES reed WIOUT HEADSPACE? Reporting Address: Z f t Address: PROPER CONTAIN S useddf _ Z TEMP: Therm lD: T�7 Observed c.•n -ClCornZ& C Phone: L > (Yes (No - Purchase Order NoJBIIIing Reference TO BE FILLED IN BY CLIENT/SAMPLING PERSONNEL Email Address:-A.7�a/YJU(. f`�E1 rye L'(+Si/-d M Rested Due Date J 1 Day J 2 Days J 3 Days J 4 Days J 5 Days Certification: NC SC EDD Type: POF_v"Excel_Other ^Working Days" J 6.9 Days J Standard 10 days J Ruh Work BePre Other NI Site Location Name: Y'^ Samples received after 15:00 mill be processed neat business day. Site Location Physical Piddress: cttr Turnaround time is based on business days.excluding vieekends and holidays- Water Chlorinated: YES_NO_ /^� (SEE REVERSE FOR TERMS a CONDITIONS REGARDING SERVICES r+ Q ` RENDERED BY WAYPOWT ANALYTICAL,LLC TO CLIENT) Samples iced Upon Collection: YES—NO TIME MATRIX SAMPLE CONTAINER ANALYSIS REQUESTED CLIENT DATE COLLECTED (SOIL PRESERVA. / REMARKS ID NO. SAMPLE DESCRIPTION COLLECTED MILITARY WATER,OR T•PE TIMES HOURS SLUDGE) SEEBELOW NO. SIZE ` r w 0 00299 ' a l JV Quality Finds.LLC-Kinus Mountain Plant 10-2 -2 022 OuanerN Sloan yeler Sampes 52 Sampler's Signalure Sampled By(Print Name) Q U r VV IN L- Affiliation ' v, (� kill Upon relinquishing,this Chain of Custody is your authorization for Waypoint Analytical to proceed with the analyses as requested above.Any c6anges must be Site Arrival Time: submitted In writing to the Waypoint Analytical Project Manager.There will be charges for any changes after analyses have been Initialized. R By fine Dab si-"'Rees Additional Comments: Site Deparluna Ttrrw: /�T� ��yJ) U" 12 Rah j5 ( LL 23 By(bl lure, Dale - Field Tech Fee: c•.., (7/ 7 r/y� M RekNul By Sgaalur Rorened�prjNnypam An WeN Z�4 I`J� Sewage: shixl d Shu ai NOTE:ALL SAMPLE COOLERS SHOULD BE TAPED a CUSTODY SFALS FOR RTAl10N TO THE LABORATORY. COC Group ft. SAMPLES ARE NOT ACCEPTED AND VERIFIED AGAINST COC UNDL RECEIVED AT THE LABORATORY. • JFWEa JUPS JONer _ _ NPDES: UST: I GROUNDWATER DRINKING WATER: SOLID WASTE: RCRA: BRWNFLD LANDFILL OTHER: J NC J SC J NC J SC J NC J SC J NC J SC J NC J SC J NC J SC J NC J SC J NC J SC J NC J SC ORIGINAL J zi J *CONTAINER TYPE CODES: A=Amber C=Clear G=Glass P=Plastic; TL=Teflon-Lined Cap VOA=Volatile Organics Analysis(Zero Head Space)