HomeMy WebLinkAboutNC0082694_BIMS Report_20240520United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NCO082694 111 121 24/05/03 I17 18 I C I 19 Ls_] 201 I
211111 I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I 1166
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
1.0 701, I 71 p I 72 I Lr i I 71 I 74 79 I I I I I I I80
LJ J I I
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES Dermit Number)
10:OOAM 24/05/03
15/10/01
Dallas WTP
1342 Dallas -Stanley Hwy
Exit Time/Date
Permit Expiration Date
Dallas NC 28034
12:OOPM 24/05/03
20/07/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
James M Palenick,210 N Holland St Dallas NC 280342749/Interim Town
Manager/704-922-3176/7049224701 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Operations & Maintenar 0 Self -Monitoring Progran 0 Facility Site Review
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Edward Watson DWR/MRO WQ/ /
5/17/2024
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
by:
FDocuSigned
t��•�,t,�W f f Nu t, 5/20/2024
� F-I b-I FtfbyHLU254H3...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NCO082694 I11 12I 24/05/03 117 18 i c i
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page#
Permit: NCO082694 Owner -Facility: Dallas WTP
Inspection Date: 05/03/2024 Inspection Type: Compliance Evaluation
Permit
Yes
No
NA
NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
0
❑
❑
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
0
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: The permit expired July 31, 2020. A request for rescission was submitted by
the Town
of Dallas on 4/13/2022. The Town is requesting the permit be rescinded and replaced
with a Certificate of Coverage under general permit NCG59000000.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? ❑ 0 ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The Treament lagoon is overtopped capacity. There is water overtopping the berm
adjacent tot he walkway across from the drying beds.
At the time of the site visit, the drying beds had standing water and sludge in place. By
visual observation, it appears the drying beds are not draining fluid and may require
maintenance/reconditioning in order to drain properly.
There is a storm drain adjacent to the lagoon. With the lagoon currently at holding
capacity, there is a significant chance for fluid from the lagoon to travel to the storm
drain creating an unpermitted discharge.
The conditions were also indentified at this facility during the 2022 inspection.
Page# 3