December 16, 2015
Lissara Partners LLC
Attn: CJ Ramey, Owner RECEIVED/DENR/DWR
P.O. Box 10
Bethania, NC 27010
..)EC222015
Subject: Compliance Evaluation Inspection
Permittee: Lissara Partners LLC r. Water Quality
Facility: Lissara Wastewater Treatment Plant ittlnq Sectio.s,
NPDES Permit#: NC0088749
Forsyth County
Dear Mr. Ramey:
Ron Boone of the Winston-Salem Regional Office of the NC Division of Water Resources (DWR or the
Division)conducted a compliance evaluation inspection (CEI)of the Lissara Wastewater Treatment Plant(WWTP)on
December 15, 2015. The assistance and cooperation of Lee Kimbrell, Operator in Responsible Charge(ORC), during
the inspection,was greatly appreciated.The inspection findings are summarized below and an inspection report is also
attached for your records.
The plant is located at 9689 Wildflower Woods Way, in Lewisville, NC, at approximate coordinates
36.116233°N, 80.458243°W. The permit authorizes Lissara Partners LLC to operate this 0.108 MGD WWTP and
discharge the treated effluent from the plant into Yadkin River, this section of which is currently classified as WS-IV
waters and is located in the Yadkin Pee-Dee River basin.
The plant was brought on line in April, 2015 and still only receives about 1,500 gallons of flow per day. The
plant has experienced five limit violations since being brought on line, three Fecal Coliform violations and two Total
Suspended Solids violations. The plant, which such low flow, is still struggling to completely treat the waste.
SITE REVIEW
The plant is clean and well maintained. There are several spots of corrosion all over the plant that should be
repaired before they become larger problems.The owners should also establish a maintenance program to inspect the
plant annually for the presence of corrosion and then to fix it. This is the only discrepancy noted by Mr. Boone during
the inspection.
DOCUMENTATION REVIEW
Documentation that was available was reviewed and no issues, discrepancies, or violations were noted.
However, not all required documentation was available for inspection. The owner and/or operator must ensure that a
copy of the complete discharge permit and all discharge monitoring reports (DMR), laboratory records (field and non-
field), and chains of custody are available during an inspection and kept on site at all times. No other issues were
noted.
State of North Carolina Environmental Quality Water Resources
450 West Hanes Mill Road,Suite 300 Winston-Salem.North Carolina 27105
336'76 9800
Please bear in mind that in accordance with NC General Statute 143-215.6A, the Director of the Division of
Water Resources may assess civil penalties not to exceed $25,000 per day, per violation, for violations of the
NC0088749 NPDES permit.
If you have any questions regarding the permit or this letter, please call Mr. Boone or me at(336)776-9800.
Thank you for your attention to this matter.
Sincerely,
Sherri V. Knight
Regional Supervisor
Water Resources Regional Operations
Division of Water Resources
Attachments:
1. BIMS Inspection Report
CC: WSRO-SWP
Central Files
NPDES Unit
L&N Wastewater Management
Attn: Lee Kimbrell
5646 Hampton Rd,
Clemmons, NC 27012
United States Environmental Protection Agency
Form Approved.
EPA Washington.D C 20460 OMB No.2040-0057
Water Compliance Inspection Report Approval expires 8-31-98
Section A:National Data System Coding(i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN I 2 I5 3 I NC0088749 111 12 1 15/12/15 117 18 ,. 19 w 2011
21111111 1IIIII11jII IIIIIII I IIIIII 11111111III X66
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA Reserved---------------
67 I I 70 U 71 u 72 1 N 1 731
I I74 75J 1 1 1 1 1 1 180
Section B:Facility Data
Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date
POTW name and NPDES permit Number)
10 OOAM 15/12/15 14/02/01
Lissara WTP
Exit Time/Date Permit Expiration Date
9689 Wildflower Woods Way
Lewisville NC 27023 11:00AM 15/12/15 19/01/31
Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data
///
Randall Keith Bell/CRC/336-373-7514/
Virgil Lee Kimbrell/ORC/336-399-9319/
Name,Address of Responsible Official/Title/Phone and Fax Number
Contacted
C J Ramey,P0 Box 10 Bethania NC 27010//336-922-4000/3369221762
No
Section C.Areas Evaluated During Inspection(Check only those areas evaluated)
El Permit • Flow Measurement I Operations&Maintenance • Records/Reports
I. Self-Monitoring Program • Sludge Handling Disposal II Facility Site Review • Effluent/Receiving Waters
• Laboratory
Section D: Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s)and Signature(s)of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Ron Boon WSRO WQ//336-776-9690/ 2-//c7//5
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3(Rev 9-94)Previous editions are obsolete.
Page# 1
NPDES yr/mo/day Inspection Type 1
31 NC0088749 Ill 121 15/12/15 11 7 18 Li
I
Section D:Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
Please refer to the attached inspection summary letter.
Page# 2
Permit: NC0088749 Owner-Facility: Lissara WTP
Inspection Date: 12/15/2015 Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new 00 • 0
application?
Is the facility as described in the permit? ❑ ❑ E ❑
#Are there any special conditions for the permit? 0 • 00
Is access to the plant site restricted to the general public? • 000
Is the inspector granted access to all areas for inspection? • ❑ ❑ 0
Comment: None
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit? MOOD
Is all required information readily available, complete and current? 0 • 00
Are all records maintained for 3 years(lab. reg. required 5 years)? 00011
Are analytical results consistent with data reported on DMRs? ❑ ❑ ❑ •
Is the chain-of-custody complete? • 000
Dates, times and location of sampling •
Name of individual performing the sampling •
Results of analysis and calibration •
Dates of analysis
Name of person performing analyses
Transported COCs U
Are DMRs complete: do they include all permit parameters? • 000
Has the facility submitted its annual compliance report to users and DWQ? DOMO
(If the facility is=or>5 MGD permitted flow) Do they operate 24/7 with a certified operator 0 • 00
on each shift?
Is the ORC visitation log available and current? • ❑ ❑ ❑
Is the ORC certified at grade equal to or higher than the facility classification? • 000
Is the backup operator certified at one grade less or greater than the facility classification? • ❑ ❑ ❑
Is a copy of the current NPDES permit available on site? 0 • 00
Facility has copy of previous year's Annual Report on file for review? 00 • O
Comment: Plant in operation for less than 1 year. Not all DMRs, lab records, chains of custody, etc,
available during the inspection. Has copy of permit limitations page but not the entire permit.
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory? • 000
Page# 3
Permit: NC0088749 Owner-Facility: Lissara VVTP
Inspection Date: 1 211 5/2 01 5 Inspection Type: Compliance Evaluation
Laboratory Yes No NA NE
Are all other parameters(excluding field parameters)performed by a certified lab? • ❑ ❑ ❑
#Is the facility using a contract lab? • 000
#Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees 000 •
Celsius)?
Incubator(Fecal Coliform)set to 44.5 degrees Celsius+/-0.2 degrees? ODOM
Incubator(BOD) set to 20.0 degrees Celsius+/- 1.0 degrees? ❑ ❑ ❑ U
Comment: None
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? 00110
Is sample collected below all treatment units? • DOD
Is proper volume collected? U ❑ ❑ ❑
Is the tubing clean? 00 • 0
#Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees 00110
Celsius)?
Is the facility sampling performed as required by the permit(frequency, sampling type • ❑ ❑ ❑
representative)?
Comment: Samples are taken from the effluent v-notch weir on the flow box, not from the end of the
pipe,which is approximately 1,000 feet northwest of the flow box.
Equalization Basins Yes No NA NE
Is the basin aerated? • 000
Is the basin free of bypass lines or structures to the natural environment? U 000
Is the basin free of excessive grease? • 000
Are all pumps present? • 000
Are all pumps operable? • 000
Are float controls operable? • 000
Are audible and visual alarms operable? ❑ ❑ E ❑
#Is basin size/volume adequate? ❑ ❑ ❑ U
Comment: Basin does not have audible and visual alarms but is tied into a telemetry system that
notifiies operator by phone of specific alarm conditions. Owners should also install local
audible and visual alarms in case of telemetry failure, which would also include failure of the
phone lines.
Aeration Basins Yes No NA NE
Mode of operation Ext.Air
Page# 4
Permit: NC0088749 Owner-Facility: Lissara WTP
Inspection Date: 12/15/2015 Inspection Type: Compliance Evaluation
Aeration Basins Yes No NA NE
Type of aeration system Fixed
Is the basin free of dead spots?
Are surface aerators and mixers operational? ❑ ONO
Are the diffusers operational? • 000
Is the foam the proper color for the treatment process? • 000
Does the foam cover less than 25%of the basin's surface? U ❑ ❑ ❑
Is the DO level acceptable? U ❑ ❑ ❑
Is the DO level acceptable?(1.0 to 3.0 mg/I) • ❑ ❑ ❑
Comment: None
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater? U ❑ ❑ ❑
Is the site free of excessive buildup of solids in center well of circular clarifier? 00110
Are weirs level? 1. 0 ❑ ❑
Is the site free of weir blockage? • ❑ ❑ ❑
Is the site free of evidence of short-circuiting? U ❑ ❑ ❑
Is scum removal adequate? U ❑ ❑ ❑
Is the site free of excessive floating sludge? U ❑ ❑ ❑
Is the drive unit operational? ❑ ❑ • ❑
Is the return rate acceptable(low turbulence)? • E100
Is the overflow clear of excessive solids/pin floc? • 000
Is the sludge blanket level acceptable?(Approximately Y4 of the sidewall depth) ❑ ❑ ❑ U
Comment: None
Pumps-RAS-WAS Yes No NA NE
Are pumps in place? U ❑ ❑ ❑
Are pumps operational? 110 ❑ ❑
Are there adequate spare parts and supplies on site? • ❑ ❑ 0
Comment: None
Disinfection-Tablet Yes No NA NE
Are tablet chlorinators operational? • ❑ ❑ ❑
Are the tablets the proper size and type? • ❑ ❑ ❑
Page# 5
Permit: NC0088749 Owner-Facility: Lissara WTP
Inspection Date: 12/15/2015 Inspection Type: Compliance Evaluation
Disinfection-Tablet Yes No NA NE
Number of tubes in use? 8
Is the level of chlorine residual acceptable? 0 0 0 •
Is the contact chamber free of growth, or sludge buildup? • 0 0 0
Is there chlorine residual prior to de-chlorination? 0 0 0 •
Comment: None
De-chlorination Yes No NA NE
Type of system ? Tablet
Is the feed ratio proportional to chlorine amount(1 to 1)? • 0 0 0
Is storage appropriate for cylinders? U ❑ 0 0
#Is de-chlorination substance stored away from chlorine containers? U 0 0 0
Are the tablets the proper size and type? • ❑ 0 0
Comment: None
Are tablet de-chlorinators operational? • ❑ 0 ❑
Number of tubes in use? 8
Comment: None
Flow Measurement- Effluent Yes No NA NE
#Is flow meter used for reporting? In ❑ ❑ 0
Is flow meter calibrated annually? II ❑ ❑ ❑
Is the flow meter operational? N ❑ ❑ p
(If units are separated)Does the chart recorder match the flow meter? • 0 0 ❑
Comment: None
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained? • ❑ 0 0
Are the receiving water free of foam other than trace amounts and other debris? U ❑ 0 ❑
If effluent (diffuser pipes are required) are they operating properly? 0 ❑ • ❑
Comment: Way to outfall is treacherous.Accommodations should be made so operators can access
the end of the pipe to collect samples.
Aerobic Digester Yes No NA NE
Is the capacity adequate? U 0 0 0
Page# 6
Permit: NC0088749 Owner-Facility: Lissara WTP
Inspection Date: 12/15/2015 Inspection Type: Compliance Evaluation
Aerobic Digester Yes No NA NE
Is the mixing adequate? • ❑ ❑ ❑
Is the site free of excessive foaming in the tank? • 0 0 0
#Is the odor acceptable? • 0 ❑ 0
#Is tankage available for properly waste sludge? • ❑ ❑ ❑
Comment: None
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • ❑ ❑ 0
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable • ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: There are several spots of corrosion all over the plant that should be addressed now.
Owners should develop maintenance program to fix spot corrosion every six months at a
minimum to prevent small spot corrosion from becoming large problems.
Standby Power Yes No NA NE
Is automatically activated standby power available? • ❑ ❑ 0
Is the generator tested by interrupting primary power source? ❑ ❑ ❑ II
Is the generator tested under load? 0 ❑ ❑ •
Was generator tested&operational during the inspection? ❑ U ❑ ❑
Do the generator(s)have adequate capacity to operate the entire wastewater site'? • ❑ p ❑
Is there an emergency agreement with a fuel vendor for extended run on back-up power? ❑ 0 p •
Is the generator fuel level monitored? 0 ❑ ❑ •
Comment: None
Page# 7