HomeMy WebLinkAboutNC0048658_NOVNOI2024PC0255_20240417
Certified Mail # 9589 0710 5270 0731 8014 09
Return Receipt Requested
April 17, 2024
Aubrey L Deaver
A&D Water Service Inc
PO Box 1407
Pisgah Forest, NC 28768-1407
SUBJECT: NOTICE OF VIOLATION & INTENT TO ASSESS CIVIL PENALTY
Tracking Number: NOV-2024-PC-0255
Permit No. NC0048658
Sherwood Forest WWTP
Transylvania County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Sherwood Forest WWTP on April
16, 2024. This inspection was conducted to verify that the facility is operating in compliance with the conditions
and limitations specified in NPDES WW Permit No. NC0048658. A summary of the findings and comments noted
during the inspection are provided in the enclosed copy of the inspection report.
The Compliance Evaluation inspection was conducted by Division of Water Resources staff from the Asheville
Regional Office. The following violation(s) were noted during the inspection:
Inspection Area Description of Violation _________________________________________________________________________________________________________________________________________________________________________
Disinfection-Tablet The chlorine contact chamber was full of sand/solids. Wastewater may be short-circuiting
the contact chamber through a break in the contact chamber wall. _________________________________________________________________________________________________________________________________________________________________________ Effluent Pipe The outfall could not be located.
_________________________________________________________________________________________________________________________________________________________________________
Sand Filters (Low rate) One filter bed had clear ponding, uneven distribution, and organic matter on the surface. _________________________________________________________________________________________________________________________________________________________________________
DocuSign Envelope ID: D5F377A5-FDCD-43E9-A76F-0EC9B9BD9DD3
A Notice of Violation/Intent to Issue Civil Penalty is being issued for the noted violation of North Carolina General
Statute (G.S.) 143-215.1 and the facility’s NPDES WW Permit. Pursuant to G.S. 143-215.6A, a civil penalty of
not more than twenty-five thousand dollars ($25,000.00) may be assessed against any person who violates or
fails to act in accordance with the terms, conditions, or requirements of any permit issued pursuant to G.S.
143-215.1.
If you wish to provide additional information regarding the noted violation, request technical assistance, or discuss
overall compliance please respond in writing within ten (10) business days after receipt of this Notice. A review of
your response will be considered along with any additional information provided. You will then be notified of any
civil penalties that may be assessed regarding the violations. If no response is received in this Office
within the 10-day period, a civil penalty assessment may be prepared.
Remedial actions should have already been taken to correct this problem and prevent further occurrences in the
future. The Division of Water Resources may pursue enforcement action for this and any additional violations of
State law. If the violations are of a continuing nature, not related to operation and/or maintenance problems, and
you anticipate remedial construction activities, then you may wish to consider applying for a Special Order by
Consent.
Reminder: Pursuant to Permit Condition 6 in Section E, the Permittee is required to verbally notify the Regional
Office as soon as possible, not to exceed 24 hours, from first knowledge of any non-compliance at
the facility including limit violations, bypasses of, or failure of a treatment unit. A written report may
be required within 5 days if directed by Division staff. Prior notice should be given for anticipated or
potential problems due to planned maintenance activities, taking units off-line, etc.
If you should have any questions, please do not hesitate to contact me with the Water Quality Regional Operations
Section in the Asheville Regional Office at 828-296-4500.
Sincerely,
Daniel Boss, Assistant Regional Supervisor
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS: Inspection Report
Ec: Laserfiche
DocuSign Envelope ID: D5F377A5-FDCD-43E9-A76F-0EC9B9BD9DD3
EPA
United States Environmental Protection Agency
Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 N 52 NC0048658 24/04/16 C R31112171819 20
21 66
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
N67707172 73 74 75 80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Sherwood Forest WWTP
8365 Greenville Hwy
Brevard NC 28712
Entry Time/Date Permit Effective Date
Exit Time/Date Permit Expiration Date
12:45PM 24/04/16 21/01/01
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Other Facility Data
01:45PM 24/04/16 25/09/30
Name, Address of Responsible Official/Title/Phone and Fax Number
Patty Carland,117 Kira Ln Hendersonville NC 287391407//828-890-4810/Contacted
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Facility Site Review
Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date
Daniel J Boss DWR/ARO WQ/828-296-4658/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#1
DocuSign Envelope ID: D5F377A5-FDCD-43E9-A76F-0EC9B9BD9DD3
4/25/2024
NPDES yr/mo/day
24/04/16
Inspection Type
C3111218
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On 4/16/2024 I met with Wesley Royal (ORC), Tristan Odekirk (EPA), and John Goodwin (EPA) for a
Compliance Evaluation Inspection of the Sherwood Forest WWTP.
This facility is in serious need of repair. The sand filter is ponding and distribution appears to be
uneven. One of the lateral pipes was broken. Mr. Royal says that the wrong type of sand is in the
filter beds.
The chlorine contact chamber is leaking and the base of one of the walls is broken and leaking. The
effluent from the filter beds may be short-circuiting through the filter bed and broken contact chamber
walls. There was a flow of water into the contact chamber through the broken wall and the filter bed
is only a few feet behind that contact chamber wall. This flow from the ground was significantly
greater than the flow coming into the chlorine contact chamber through the contact chamber's
influent pipe.
NC0048658 17 (Cont.)
Page#2
DocuSign Envelope ID: D5F377A5-FDCD-43E9-A76F-0EC9B9BD9DD3
Permit:NC0048658
Inspection Date:04/16/2024
Owner - Facility:
Inspection Type:
Sherwood Forest WWTP
Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Comment:
Flow Measurement - Effluent Yes No NA NE
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Flow is estimated.Comment:
Septic Tank Yes No NA NE
(If pumps are used) Is an audible and visual alarm operational?
Is septic tank pumped on a schedule?
Are pumps or syphons operating properly?
Are high and low water alarms operating properly?
There is only one dosing siphon for the septic tank.Comment:
Sand Filters (Low rate)Yes No NA NE
(If pumps are used) Is an audible and visible alarm Present and operational?
Is the distribution box level and watertight?
Is sand filter free of ponding?
Is the sand filter effluent re-circulated at a valid ratio?
# Is the sand filter surface free of algae or excessive vegetation?
Page#3
DocuSign Envelope ID: D5F377A5-FDCD-43E9-A76F-0EC9B9BD9DD3
Permit:NC0048658
Inspection Date:04/16/2024
Owner - Facility:
Inspection Type:
Sherwood Forest WWTP
Compliance Evaluation
Sand Filters (Low rate)Yes No NA NE
# Is the sand filter effluent re-circulated at a valid ratio? (Approximately 3 to 1)
The WWTP has two large sand filter beds. One filter bed had clear ponding, uneven
distribution, and organic matter on the surface. The flow of wastewater had been shut
off to this filter bed for two days and it still had small puddles on the surface. The other
filter bed did not have visible ponding but it had only been receiving flow for two days.
Comment:
Disinfection-Tablet Yes No NA NE
Are tablet chlorinators operational?
Are the tablets the proper size and type?
Number of tubes in use?2
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de-chlorination?
The chlorine contact chamber was full of sand/solids. The contact chamber has a
depth of approximate 4 feet according to the ORC. The sand/solids nearly filled the
contact chamber entirely. Wastewater may be short-circuiting the contact chamber
through a break in the contact chamber wall.
Comment:
De-chlorination Yes No NA NE
Type of system ?Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de-chlorination substance stored away from chlorine containers?
Comment:
Are the tablets the proper size and type?
Are tablet de-chlorinators operational?
Number of tubes in use?2
Comment:
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
The ORC stated that no one knows where the outfall is located.Comment:
Page#4
DocuSign Envelope ID: D5F377A5-FDCD-43E9-A76F-0EC9B9BD9DD3