HomeMy WebLinkAboutNCG030535_2024 DMR_20240422 NCDEQ Division of Energy, Mineral and Land Resources
Stormwater Discharge Monitoring Report (DMR) Form for NCG030000
Metal Fabrication
Click here for instructions
Complete,sign,scan and submit the DMR via the Stormwater NPDES Permit Data Monitoring Report(DMR)Upload form within
30 days of receiving sampling results. Mail the original,signed hard copy of the DMR to the appropriate DEMLR Regional Office.
Certificate of Coverage No.NCGO3 0 5 3 5 Person Collecting Samples: William Edens
Facility Name: ZF Chassis Components, LLC. Laboratory Name: Pace Analytical
Facility County:Catawba Laboratory Cert.No.: 92721952
Discharge during this period:❑■ Yes ❑ No (if no,skip to signature and date)
Has your facility implemented mandatory Tier response actions for any benchmark exceedances?❑Yes ❑® No
If so,which Tier(I,II,or III)?
Analytical Monitoring Requirements for Outfalls with Industrial Activities—Benchmarks in(Red)
Parameter Parameter Outfall 1 Outfall 2 Outfall Outfall Outfall
Code
N/A Receiving Stream Class NA NA
N/A Date Sample Collected MM/DD/YYYY 03/27/2024 03/27/2024
46529 24-Hour Rainfall in inches .15 .15
00552 Non-Polar Oil&Grease in mg/L(15) 6.5 ND
C0530 TSS in mg/L(100 or 50*) 5.8 2.9
00400 pH in standard units(6.0—9.0) 7.3 6.6
NCOIL New Motor/Hydraulic Oil Usage in NA NA
gal/month
01119 Copper,total recoverable in mg/L ND ND
(0.010 FW,0.005 SW)
01051 Lead,total recoverable in mg/L ND ND
(0.075 FW,0.220 SW)
01094 Zinc,total recoverable in mg/L(0.126 .031 .020
FW,0.095 SW)
78141 Total Toxic Organics(TTO)in mg/L(1) NA NA
* Outfalls to Outstanding Resource Waters(ORW),High Quality Waters(HQW),Trout Waters(Tr)and Primary Nursery Areas(PNA)
have a benchmark TSS limit of 50 mg/L.All other water classifications have a benchmark of 100 mg/L.
Notes(optional):Very low rainfall from the prior night and high amounts of pollen debris.
"I certify by my signature below,under penalty of law,that this document and all attachments were prepared under my direction or
supervision in accordance with a system designed to assure that qualified personnel properly gather and evaluate the information
submitted. Based on my inquiry of the person or persons who manage the system,or those persons directly responsible for
gathering the information,the information submitted is,to the best of my knowledge and belief,true,accurate,and complete.I am
aware that there are significant penalties for submitting false information,including the possibility of fines and imprisonment for
knowing violations."
tee; -..:.--. (c _ 4/22/2024
Signature of Permittee or Delegated Authorized Individual Date