Loading...
HomeMy WebLinkAboutWQ0042923_Application (FTSE)_20240419 NC Dept of r;J.irOicii:t'nlni Qt1l14y State of North Carolina Department of Environmental Quality DW R MAR I ] 2024 Division of Water Resources FAST TRACK SEWER SYSTEM EXTENSION APPLICATION Division of Water Resources Raleigh Reg;opall FTA 10-23& SUPPORTING DOCUMENTATION Application plumber: ito be completed by DWR) All items must be completed or the application will be returned I. APPLICANT INFORMATION: I. Applicant's name: City of Oxford(company,municipality, HOA, utility,etc.) 2. Applicant type: ❑ Individual ❑ Corporation ❑General Partnership ❑ Privately-Owned Public Utility ❑ Federal ❑ State/County ® Municipal ❑ Other 3. Signature authority's name: Amy Ratliff per 15A NCAC 02T.01061b) Title: City Engineer 4. Applicant's mailing address: P.O. Box 506 City: Oxford State: NC Zip: 27565- 5. Applicant's contact information: Phone number: (919)603-1 1 13 Email Address: aratliffa,oxfordnc.org IL PROJECT INFORMATION: 1. Project name: Hatcher Creek 2. Applicationi Project status: ❑ Proposed(New Permit) ® Existing Permit/Project ❑ ARPA funded If a modification,provide the existing permit number: WQ0042923 and issued date: 12-7-21, For modifications,also attach a detailed narrative description as described in Item G of the checklist. If new construction,but part of a master plan,provide the existing permit number: WQ00 3. County where project is located:Qranville 4. Approximate Coordinates(Decimal Degrees): Latitude: 36.2858 Longitude: -78.6097 5. Parcel ID(if applicable): 191204524624(or Parcel ID to closest downstream sewer) III. CONSULTANT INFORMATION: 1. Professional Engineer: Christopher N Huff License Number: 024420 Firm: WithersRavenel Mailing address: 115 MacKenan Drive City:Cary State: NC Zip: 2751 1- Phone number:(9I9)469-3340 Email Address:chuN@withersravenel.com IV. WASTEWATER TREATMENT FACILITY(WWTF) INFORMATION: 1. Facility Name: City of Oxford Permit Number:NC-0025054 Owner Name: City of Oxford V. RECEIVING DOWNSTREAM SEWER INFORMATION: 1. Permit Number(s): WQ 2. Downstream (Receiving)Sewer information: 8 inch Gravity X Force Main 3. System Wide Collection System Permit Number(s)(if applicable): WQCS00086 Owner Name(s): City of Oxford FORM: FTA 10-23 Pagel of 5 V1. GENERAL REQUIREMENTS I. If the Applicant is a Privately-Owned Public Utility, has a Certificate of Public Convenience and Necessity been attached? [:] Yes ❑ No ® NiA 2. If the Applicant is a Developer of lots to be sold,has a Developer's O ep rational_Agreement(FORM: DEV)been attached? ❑ Yes ❑ No ® N'A 3. If the Applicant is a HomeProperty Owners'Association,has an HOA'POA Qperational Agreement(FORM: HOA)and supplementary documentation as required by 15A NCAC 02T.01 15(c)been attached? ❑ Yes ❑ No ® N;A 4. Origin of wastewater:(check all that apply): ® Residential(Individually Owned) ❑ Retail(stores,centers,malls) ❑ Car Wash ❑ Residential(Leased) ❑ Retail with food preparation/service ❑ Hotel and/or Motels ❑ School preschool 'day care ❑ Medical!dental veterinary facilities ❑ Swimming Pool'Clubhouse ❑ Food and drink facilities ❑ Church ❑ Swimming Pool Filter Backwash ❑ Businesses offices r factories ❑ Nursing Home ❑ Other(Explain in Attachment) 5. Nature of wastewater: 100%Domestic %Commercial °o Industrial(See 15A NCAC 02T.0103(20)) If Industrial, is there a Pretreatment Program in effect?❑ Yes❑ No 6. Has a flow reduction been approved under 15A NCAC 02T.01 14(fl? ❑ Yes ® No );, If yes,provide a copy of flow reduction approval letter with this application 7. Summarize wastewater generated by project: Establishment Type(see 02T.0114(f)) Daily Design Flow'b No.of Units Flow 2 Bedroom Units-Townhome 240 galibedroom 54 12,960 GPD 3 Bedroom Units-Townhome 360 gal/bedroom 54 19,440 GPD 3 Bedroom Units-Single Family 360 gal/bedroom 27 9,720 GPD gal/ GPD gal/ GPD gal/ GPD Total 42,120 GPD a See 15A NCAC 02T.01 14(b),(d),(exl) and(e)(2) for caveats to wastewater design flow rates (i.e. proposed unknown non-residential development uses; public access facilities located near high public use areas; and residential property located south or east of the Atlantic Intracoastal Waterway to be used as vacation rentals as defined in G.S.42A_4). b Per 15A NCAC 02T.01 14(c), design flow rates for establishments not identified [in table 15A NCAC 02T.01 141 shall be determined using available flow data, water using fixtures,occupancy or operation patterns,and other measured data. 8. Wastewater generated by project:42,120 GPD(per 15A NCAC 02T.01 14 and G.S. 143-215.1) ➢ Do not include future flows or previously permitted allocations If permitted flow is zero,please indicate why: ❑ Pump Stationr'Force Main or Gravity Sewer where flow will be permitted in subsequent permits that connect to this line. Please provide supplementary information indicating the approximate timeframe for permitting upstream sewers with flow. ❑ Flow has already been allocated in Permit Number: Issuance Date: ❑ Rehabilitation or replacement of existing sewers with no new flow expected ❑ Other(Explain): FORM: FTA 10-23 Page 2 of 5 VII. GRAVITY SEWER DESIGN CRITERIA (If Applicable)-02T.0305& MDC(Gravity Sewers): 1. Summarize gravity sewer to be permitted: Size(inches) Length(feet) Material Section 11& III of the MDC for Permitting of Gravity Sewers contains information related to design criteria Section III contains information related to minimum slopes for gravity sewer(s) Oversizing lines to meet minimum slope requirements is not allowed and a violation of the MDC VI ll. PUMP STATION DESIGN CRITERIA(If Applicable)—02T.0305& MDC(Pump Stations/Force Mains): PROVIDE A SEPARATE COPY OF THIS PAGE FOR EACH PUMP STATION INCLUDED IN THIS PROJECT 1. Pump station number or name: Hatcher Creek Pump Station 2. Approximate Coordinates(Decimal Degrees): Latitude: 36.2840 Longitude: -78.6131 3. Total number of pumps at the pump station:2 3. Design flow of the pump station: .042 millions gallons per day(firm capacity) ➢ This should reflect the total GPM for the pump station with the largest pump out of service. 4. Operational point(s)per pump(s): 340 gallons per minute(GPM)at 108 feet total dynamic head(TDH) 5. Summarize the force main to be permitted(for this Pump Station): Size(inches) Length(feet) Material 8 2495 PVC 8 65 DI If any portion of the force main is less than 4-inches in diameter, please identify the method of solids reduction per MDCPSFM Section 2.01 C.Lb. ❑ Grinder Pump ❑ Mechanical Bar Screen ❑Other(please specify) 6. Power reliability in accordance with 15A NCAC 02T.0305(h)LIJ: ® Standby power source or ❑ Standby pump Must have automatic activation and telemetry- 15A NCAC 02T.0305(h)(1)(B): ➢ Required for all pump stations with an average daily flow greater than or equal to 15,000 gallons per day ➢ Must be permanent to facility and may not be portable Or if the pump station has an average daily flow less than 15,000 gallons per day 15A NCACO2T.0305(h)(1)(C). ❑ Portable power source with manual activation,quick-connection receptacle and telemetry- or ❑ Portable pumping unit with plugged emergency pump connection and telemetry: Include documentation that the portable source is owned or contracted by the applicant and is compatible with the station. ➢ If the portable power source or pump is dedicated to multiple pump stations,an evaluation of all the pump stations'storage capacities and the rotation schedule of the portable power source or pump, including travel timeframes, shall be provided as part of this permit application in the case of a multiple station power outage. FORM: FTA 10-23 Page 3 of 5 1X. SETBACKS& SEPARATIONS—(02B.0200 & 15A NCAC 02T.0305(f)): I. Does the project comply with all separations/alternatives found in 15A NCAC 02T.0305(f)&(g)? ® Yes ❑ No 15A NCAC 02T.0305 contains minimum separations that shall be provided for sewers stems: Setback Parameter* Separation Required Storm sewers and other utilities not listed below(vertical) 18 inches 'Water mains(vertical -water over sewer preferred, including in benched trenches) 18 inches '--Water mains(horizontal) 10 feet Reclaimed water lines(vertical -reclaimed over sewer) 18 inches Reclaimed water lines(horizontal-reclaimed over sewer) 2 feet "Any private or public water supply source, including any wells, WS-1 waters of Class 1 or Class II impounded reservoirs used as a source of drinking water, and associated wetlands. 100 feet "Waters classified WS(except WS-I or WS-V), B, SA, ORW, HQW,or SB from normal high water(or tide elevation)and wetlands associated with these waters(see item IX.2) 50 feet **Any other stream, lake, impoundment, or ground water lowering and surface drainage ditches,as well as wetlands associated with these waters or classified as WL. 10 feet Any building foundation (horizontal) 5 feet Any basement(horizontal) 10 feet Top slope of embankment or cuts of 2 feet or more vertical height 10 feet Drainage systems and interceptor drains 5 feet Any swimming pools 10 feet Final earth grade(vertical) 36 inches ➢ If noncompliance with 02T.0305(Qpr(11, see Section X.I of this application *15A NCAC 02T.0305(g contains alternatives where separations in 02T. 305 t cannot be achieved. Please check"yes" above if these alternatives are used and provide narrative information to explain. **Stream classifications can be identified using the Division's NC Surface Water Classifications webpaze 2. Does this project comply with the minimum separation requirements for water mains? ® Yes ❑ No ❑N A ➢ If no,please refer to 15A NCAC 18C.0906(f)for documentation requirements and submit a separate document, signed/sealed by an NC licensed PE,verifying the criteria outlined in that Rule. 3. Does the project comply with separation requirements for wetlands? ® Yes ❑ No ❑N A ➢ Please provide supplementary information identifying the areas of non-conformance. ➢ See the Division's draft separation requirements for situations where separation cannot be met. ➢ No variance is required if the alternative design criteria specified is utilized in design and construction. 4. Is the project located in a river basin subject to any State buffer rules? ® Yes Basin name: ❑ No If yes,does the project comply with setbacks found in the river basin rules per 15A NCAC 02B .0200? ® Yes ❑No ➢ This includes Trout Buffered Streams per 15A NCAC 213.0202 5. Does the project require coverage?auth orizat ion under a 404 Nationwide individual permits ® Yes ❑ No or 401 Water Quality Certifications? ➢ Please provide the permit number,permitting status in the cover letter if coverage'authorization is required. 6. Does project comply with 15A NCAC 02T.0105(c)(6)(additional permit&`certifications)? ® Yes ❑ No Per 15A NCAC 02T.0105(cX6), directly related environmental permits or certification applications must be being prepared, have been applied for,or have been obtained. Issuance of this permit is contingent on issuance of dependent permits(erosion and sedimentation control plans,stormwater management plans, etc.). 7. Does this project include any sewer collection lines that are deemed"high-priority?" ❑ Yes ® No Per 15A NCAC 02T.0402, "high-priority sewer"means any aerial sewer,sewer contacting surface waters, siphon,or sewers positioned parallel to streambanks that are subject to erosion that undermines or deteriorates the sewer. Siphons and sewers suspended through interference/conflict boxes require a variance approval. ➢ If yes, include an attachment with details for each line, including type(aerial line,size, material,and location). High priority lines shall be inspected by the permittee or its representative at least once every six-months and inspections documented per 15A NCAC 02T.0403(a)(5)or the permittee's individual System-Wide Collection permit. FORM: FTA 10-23 Page 4 of 5 1`IC I)epf c►ErvirQr�;tey�at Cu,.t„ X. CERTIFICATIONS: MAR 112024 1. Does the submitted system comply with I SAGA_Q2L the Mini&06 fl&i Liter.-a-f� - —Pen—nittin _ pS iione and force Mains jlatest version,and the Qravky Sewtr Minimum Deskm C. eFig(Weg v as applicable? ® Yes ❑No If no, for projects requiring a single variance, complete and submit the Variance/Alternative Design Request application (VADC 10-14) and supporting documents for review to the Central Office. Approvpl of thg reguelf will by issued concurrently with the approval of the permit, and projects requiring a variance approval may be subject to longer review times. For proiects.requiring two or mor v riances or where the variance is determined by the Division to be a si ntficant portion of the prolect,the full technical review Is required. 2. Professional Fngineces Certification- 1, ne s naC �1{r } ��� attest that this application for I'rofc%stonal _ ►Q ��C_ ����� ( Engime from Application Rem III.I ) (Project Name from Application Item 11 1) has been reviewed by me and Is accurate, complete and consistent with the information supplied in the plans, specifications,engineering calculations,and all other supporting documentation to the best of my knowledge. I further attest that to the best of my knowledge the proposed design has been prepared in accordance with the applicable regulations, Minimum Drv�n Qitcria_Jgr.Gravity Sewers(latest version),and the M%njm Vn1Pesi&n('riteria tier th.e_U_tgJ'rack Y rnti in of Pump 51at_ions and Force Mains(latest versionj. Although other professionals may have developed certain portions of this submittal package, inclusion of these materials under my signature and seal signifies that I have reviewed this material and have judged it to be consistent with the proposed design. NOTE - In accordance with General Statutes 143-215.6A and 143-215.6B, any person who knowingly makes any false statement, representation, or certification in any application package shall be guilty of a Class 2 misdemeanor, which may include a fine not to exceed$10,000,as well as civil penalties up to$25,000 per violation.Misrepresentation of the application information,including failure to disclose any design non-compliance with the applicable Rules and design criteria,may subject the North Carolina-licensed Professional Engineer to referral to the licensing board.(21 NC Jb#%7A1) North Carolina Professional Engineer's seal,signature,and date: a ES wi t i ' 0 0244,�!l Z't 1�5:�;•h;G 1 N C i ..... ..... p M E�R .............. 3. Applicant's Certification per 15A NCAC 02T.0106(b): 1, rK y L 2 ;L. Lr--tom attest that this application for ATe-��C tit 1,4,f- (Signature Authority Nanic from Application Itcn►t 3) (Projccl Munc from Application hctn 11.1) attest that this application has been reviewed by me and is accurate and complete to the best of my knowledge. I understand that if all required parts of this application are not completed and that if all required supporting documentation and attachments are not included, this application package is subject to being returned as incomplete. I understand that any discharge of wastewater from this non-discharge system to surface waters or the land will result in an immediate enforcement action that may include civil penalties,injunctive relief,and/or criminal prosecution. I will make no claim against the Division of Water Resources should a condition of this permit be violated. i also understand that if all required parts of this application package are not completed and that if all required supporting information and attachments are not included, this application package will be returned to me as incomplete. NOTE In accordance with General Statutes 143-2 15.6A and 143-215 bw, any person who knowingly makes any false statement, representation, or certification in any application package shall be guilty of a Class 2 misdemeanor, which may include a fine not to exceed S 10,000 as well as civil penalties up to$25,000 per violation. Signature: V�Z_ Date 0310_14,aq - Customer Pump Performance Datasheet P E N TA I R r> Project name : Default Encompass 2.0 21 4 0 Item number 001 Size :Myers-4VC/4VCX Service Stages :1 Quanlity :1 Based on curve number :SUB_S_E_AH 00027 E 4 Rev Quote number :918843 2012-03-23 Dale last saved :28 Oct 2021 11:13 AM Operating Conditions Liquid Flow,rated :475.0 USgpm Liquid typo :Water Differential head/pressure,rated(requested) :101.01t Additional liquid description Differential head/pressure,rated(actual) :101.6 It Solids diameter,max 0.00 mm Suclion pressure,rated/max :0.00/0.00 bar.g Solids diameter limit :81.03 mm NPSH available.rated :Ample Solids concentration,by volume 0.00% Site Supply Frequency :60 Hz 'Temperature,max 20.00 deg C Performance Fluid density,rated/max :0.99810.998 kg/dm3 Speed criteria :Synchronous Viscosity,rated :1.00 cSl Speed,rated 1750 rpm Vapor pressure,rated :0.02 bar.a Impeller diameter,rated •264 mm Material Impeller diameter,maximum :305 mm Material selected :Standard Impeller diameter,minimum :203 mm Pressure Data Efficiency :61.75% Maximum working pressure :3.71 bar g NPSH required/margin required -/0.00 m Maximum allowable working pressure :N/A nq(imp.eye flow)/S(imp,eye flow) :371-Metric units Maximum allowable suction pressure :N/A Minimum Continuous Stable Flow :258.8 USgpm Hydrostatic test pressure :N/A Head,maximum,rated diameter : 124.4 it Driver&Power Data(@Max density) Head rise to shutoff :23.19 Driver sizing specification ;Rated power Flow,best eft. point : 1,082.9 USgpm Margin over specilicalion .00 Flow ratio, rated/BEP :43.86% : Service factor :1.00 1.00 Diameter ratio(rated/max) :86.46% Power,hydraulic :9.03 kW Head ratio(rated dia/max dia) 67.61 % y Power,rated 14. kW Cq/Ch/Ce/Cn [ANSI/HI 9.6.7-20101 : 1.00 1 1.00!1.00/1.00 : Selection status :Acceptable Power,maximum,rated diameter :24.81 81 kW Minimum recommended motor rating 14.91 kW/20.00 hp 32 24 Power Y y 16 3 0 a e 6 200 - -- - ------- -- - - ------- - - - ---.__..---- -- Minimum ConUnuuus Slable Flow 180 305 mm Preferred operaling region 160 Ba 65 140 G9 72 1 120 j 264 mm 75 100 72 69 2 80 60 203 mm 40 20 0 0 200 1-1 400 600 800 1,000 1.200 1.400 1AM 1.00n C-0u Flow- USgpm PREEERFIED SOURCES INC PHONt=: FAX WithersRavenel / Our People.Your Success NC Dept of nvirormer3r al Quality March 11,2024 MAR 2024 Raleigh Regional Office - Water Quality Section 3800 Barrett Drive Rate-fth Reg;onal 0iffice Raleigh, North Carolina 27609 Attn: Richard Simpson - Environmental Engineer II RE: Hatcher Creek development- Fast-Track Application Modification State Permit No.:WQ0042923 WR Project No. 0200058.00 Dear,Mr.Simpson: On behalf of Hatcher Creek, LLC please find attached documentation in support of a modified Fast-Track Application(FTA 10-231)for the pump station for the above referenced project. As noted in the application, this modification consists of decreasing the pumping capacity of the pump station from 475 gpm to 340 gpm. The reason for the modification is that at the time of pump testing it was brought to our attention,the pumps were pumping much less than designed. Upon investigation, we were informed that the provided tie in pressure to an existing 8" Town of Oxford force main was greater than reported. The pump station was initially designed with a head of 101 feet and after testing the head appears to be 108 feet. Likewise, the pump station was designed with a peaking factor of 3.68 for the pumping rate of 475-gpm and after testing the peaking factor has dropped to 3.35 for the 340-gpm pumping rate. The proposed modification meets all NCDEQ-DWR minimum design criteria for pump station design. Included with this submittal is one original and one copy of the items listed below: • Original Application Form(FTA 10-231) • Copy of Application Form(FTA 10-231) • Application Fee- Check in the Amount of$600.00 Please advise if you require additional information or have any questions concerning this submittal. Sincerely WithersRavenel (-41 ,41 Christ her N. Huff, P Cc: Hatcher Creek, LLC 115 MacKenan Drive I Cary, NC 27511 t:919.469.33401 f: 919.467.60081 www.withersravenel.corn I License No. F-1479 Asheville I Cary I Charlotte I Greensboro I Lumberton I Pittsboro I Raleigh I Southern Pines I Wilmington