HomeMy WebLinkAboutNCG550598_Authorization to Construct_20240404 DocuSign Envelope ID: B2lC8069-EE76-4389-ACD4-7E5AF9463AC1
Eta`STATE
ROY COOPER _
Governor
ELIZABETH S.BISER
Secretary
RICHARD E.ROGERS,JR. NORTH CAROLINA
Director Environmental Quality
4/4/2024
Sunlight Realty of North Carolina
6919 Innesbrook Way
Bahama,NC 27503
Subject: Authorization to Construct(ATC)
Certificate of Coverage (COC)NCG550598
under General Permit NCG550000
Single Family Residence (SFR)
6919 Innesbrook Way, Bahama
Durham County
Dear Mr. Luis A. Flores:
You currently have coverage under NPDES General Permit NCG550000 for Single Family
Residence wastewater discharge. The Division of Water Resources (DWR) understands that the
subject property is having issues with its existing wastewater treatment sandfilter system. Your
authorized consultant, Agri-Waste Technology, Inc., intends to upgrade/install a wastewater
treatment system designed to discharge to Surface Waters of the State in accordance with plans
and specifications signed by the engineer on August 16, 2023. Compliance under General Permit
NCG550000 restricts discharge flow, not to exceed 1,000 gallons per day. This ATC covers
treatment facilities for up to your existing discharge limit of 360 gallons per day(120 gallons per
bedroom).
Please note that you must provide regular treatment-system operation, maintenance and
inspections in accord with manufacturer's recommendations and this ATC; all records, water
analyses, and logs to be kept onsite available for DWR inspection [NCG550000, Section A. (2.)].
Operation and Maintenance. The Permittee is responsible to maintain all components of the
approved treatment system, designed to meet Surface Water-Quality Standards. Compliance
includes following the manufacturer's guidelines, conducting and documenting inspections,
establishing sources for OEM spare parts and supplies, taking samples for analyses, making
necessary repairs, and documenting said maintenance for the duration of the permit. Please
note that the receiving stream is currently classified and governed as WS-II; HQW,NSW, CA
(Water Supply II, High Quality Waters,Nutrient Sensitive Waters, and Critical Area).
If DWR determines that your discharge contributes to future degradation or impairment of this
waterbody, an individual NPDES permit may be mandatory. Upon DWR's request, the
Permittee must provide records and demonstrate regular efforts to maintain the approved
treatment system. The Division recommends that the Permittee solicit manufacture-certified
training, or a qualified contractor or service to regularly inspect and maintain this treatment
system.
D E Q�� North Carolina Department of Environmental Quality I Division of Water Resources
5 512 North Salisbury Street 1 1617 Mail Service Center I Raleigh,North Carolina 27699-1617
NORTH CAHOLMA ��
DeparkneW a ���nu oua\ �/ 919.707.9000
DocuSign Envelope ID:B21C8069-EE76-4389-ACD4-7E5AF9463AC1
_»I _ ___
NPDES General Permit NC550598
Authorization to Construct(ATC) Permit. This ATC details the conditions of installation and
operation. Before startup, activation requires notice to the Raleigh Regional Office (919-791-
4200), attention Michael Hall, a minimum of three (3) days in advance of discharge. Such
notification shall be made during normal office hours from 8:00 a.m. until 5:00 p.m. Monday
through Friday, excluding State holidays. The attached Engineer's Certification form must be
returned to DWR by the Engineer, documenting compliance "as built" in accord with this ATC
and approved plans and specifications submitted to DWR on August 16, 2023. No changes may
be made without prior approval.
Therefore, in accord with the application and the attached approved plans and specifications,
DWR hereby authorizes the installation of upgrades to the existing surface-water discharge
treatment system described as:
• Existing Septic Tank with New Orenco Effluent Filter
• Existing Sand Filter
• Pump Chamber
• UV Disinfection
• Discharge Point with Rip-Rap
• Control Panel
Compliance with the above shall include a leakage test performed on reused tanks and proposed
new tanks, or leak-certified new by the manufacture not to exceed an exfiltration rate of twenty
(20) gallons per twenty-four(24) hours per 1,000 gallons of tank capacity. The Engineer's
Certification shall serve as proof of compliance with this condition. Mail the completed
Engineer's Certification to:
DEQ/DWR/NPDES Program
1617 Mail Service Center
Raleigh,NC 27699-1617
❖ The Permittee shall, for the life of the treatment facility, maintain on site
a copy of the approved plans and specifications available for DWR
inspection.
All elbow piping must conform to the long-sweeping type. All cleanouts must be housed in
meter boxes below grade. This treatment system shall be located at least 15 feet away from a
dwelling, at least 100 feet from any water-supply well either on- or off-site. The system shall
also be located and constructed above any applicable 100-year flood line; 50-ft setback from
property lines.
Upon completing construction and prior to operating this permitted facility, a North
Carolina-registered engineer shall sign and submit to DWR the attached Engineer's Certification
form, thereby certifying that the permitted facility has been installed in accordance with the
NPDES Permit, this Certificate of Coverage, this Authorization to Construct, and the approved
plans and specifications.
DocuSign Envelope ID:B21C8069-EE76-4389-ACD4-7E5AF9463AC1
»I-- __-
NPDES General Permit NC550598
This ATC permit is issued in accordance with Part III, Paragraph 2 of NPDES General Permit
NCG550000, and is subject to revocation unless wastewater treatment facilities are constructed
in accordance with the conditions and limitations specified in this General Permit. In the event
that the facilities fail to perform satisfactorily, including creating nuisance conditions, the
Permittee shall take immediate corrective action as may be required by this Division, such as the
construction of additional or replacement wastewater treatment(s) or disposal facilities. Failure to
abide by the requirements of this ATC permit may subject the Permittee to an enforcement
action by the Division of Water Resources in accordance with North Carolina General Statute
143-215.6A to 143-215.6C.
NPDES Contact. If you have any questions concerning the requirements of this Authorization
to Construct(ATC)permit,please email Caroline Robinson at caroline.robinson@deq.nc.gov or
call her direct line 919-707-9130.
Sincerely,
DocuSigned by:
8328B44CE9EB4A1...
John E. Hennessy
Section Chief Regional Operations
Division of Water Resources
Attachments: Engineer's Certification form(to be signed and returned to DWR)
cc: Raleigh Regional Office—Laserfiche
NPDES General Permit Files—Laserfiche
Kevin Davidson, Agri-Waste Technology, Inc.
DocuSign Envelope ID: B2lC8069-EE76-4389-ACD4-7E5AF9463AC1
Eta`STATE aF�
ROY COOPER
Governor
ELIZABETH S.BISER
Secretary *�Af QUAM W
RICHAM E.ROGERS,JR. NORTH CAROLINA
Director Environmental Quality
Permittee: 6919 Innesbrook Way
NPDES COClATC Number: NCG550598
Co un Durham County
Engineer's Certification:
I, ,a duly registered Professional Engineer
in the State of North Carolina, as authorized by the Pennittee to observe [daily, part time, full time]
the construction of the project, ,
Project Name
Location
do hereby state that to the best of my abilities,I practiced due care and diligence to observe the construction of
said project such that it was advanced and completed in accordance and in compliance with the NPDES Permit,
approved plans and specifications,Authorization to Construct Permit, and General Permit Certificate of Coverage
issued by the Division of Water Resources.
Signature
Registration No.
Date
[Stamp]
[Any person who knowingly makes any false statement,representation,or certification in any application,record,report,plan
or other document filed or required to be maintained under Article 21 or regulations of the Environmental Management
Commission implementing that Article,or who falsifies,tampers with or knowingly renders inaccurate any recording or
monitoring device or method required to be operated or maintained under Article 21 or regulations of the Environmental
Management Commission implementing that Article,shall be guilty of a misdemeanor punishable by a fine not to exceed
$10,000,or by imprisonment not to exceed six months,or by both. [18 U.S.C. Section 1001 provides a punishment by a fine
of not more than$10,000 or imprisonment not more than 5 years,or both,for a similar offense.]
M E Q Q North Carolina Department of Environmental Quality I Division of Water Resources
512 North Salisbury Street 1 1617 Mail Service Center I Raleigh,North Carolina 27699-1617
D"rwNORTH CAROLINA
� ni \ O / 919.707.9000