HomeMy WebLinkAboutNC0074233_Compliance Evaluation Inspection_20151204 PAT MCCRORY
4
Govemor
i'
DONALD R. VAN DER VAART
Secretary
WaterResources S. JAY ZIMMERMAN
ENVIRONMENTAL QUALITY
Director
December 4, 2015
RECEIVED/DENR/DWR
Mr. Rick Sain DEC 15 2015
Catawba County School Maintenance
Post Office Box 1010 Water Quality
Newton, NC 28658 Permitting Section
SUBJECT: Compliance Evaluation Inspection
Blackburn Elementary School WWTP
NPDES Permit NCO074233
Catawba County, NC
Dear Sain:
On December 1, 2015, Roberto Scheller of this Office conducted an inspection at the
subject facility. This inspection was conducted as a Compliance Evaluation Inspection
(CEI) to insure compliance with permit requirements and conditions. At the time of
inspection the facility appeared to be well maintained and operated; however, please
note this Office's comments under the Operations & Maintenance section of the
enclosed report. We wish to thank you and your operating staff for your assistance
regarding the inspection. A copy of this inspection will be forwarded to the facility's
Operator-in-Responsible-Charge (ORC).
The enclosed reportshould be self-explanatory; however, should you have any
questions, please do not hesitate to contact Roberto Scheller at (704) 235-2204 or
roberto.scheller@ncdenr.gov.
Sin rely,
Roberto L. Scheller
Senior Environmental Specialist
Water Quality Regional Operations
Division of Water Resources
Enclosure: Inspection Report
cc: David P. McCorkle, PO Box 1010, Newton, NC 28658
Wastewater Branch
MSC 1617 — Central files basement
State of North Carolina I Environmental Quality I Water Resources I Water Quality Regional Operations
Mooresville Regional Office)610 East Center Avenue,Suite 3011 Mooresville,North Carolina 28115
704 663 1699
United States Environmental Protection Agency Form Approved
EPA Washington,D C 20460 OMB No 2040-0057
Water Compliance Inspection Report Approval expires 8-31-98
Section A:National Data System Coding(i.e.,PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 15 1 3 I NCO074233 I11 12 5/12/01 17 18 1 -1 19 I G j 20I I
211 1 1 1 1 1 11111111111 1111111 1111111 11111111111 166
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----- -- Reserved---------
67 70 71 tyI I 72 1 ti j 731 I 174 75 80
L� Section B:Facility Data LJ I I I
Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date
POTW name and NPDES permit Number) 11.15AM 15/12/01 15/08/01
Blackburn Elementary School
Exit Time/Date Permit Expiration Date -
4377 NC Hwy 10 W
11 46A 15/12/01 20/07/31
Newton NC 28658
Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data
David P McCorkle/ORC/828-217-0362/
Name,Address of Responsible Official/Title/Phone and Fax Number
Contacted
Rick Sain,PO Box 1010 Newton INC 28658//828-464-3562/8284654442
No
Section C.Areas Evaluated During Inspection(Check only those areas evaluated)
® Permit ® Operations&Maintenance ® Records/Reports ® Self-Monitoring Program
® Facility Site Review ® Effluent/Receiving Waters ® Laboratory
Section D:Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s)and Signature(s)of Inspector(s) Agency/Office/Phone and Fax Numbers Dlate�,. , c�
Roberto Scheller MRO WQ//252-946-6481/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3(Rev 9-94)Previous editions are obsolete
Page# 1
NPDES yr/mo/day Inspection Type 1
31 NCO074233 I11 12 15/12/01 17 18 I
Section D•Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
Page# 2
Permit: NC0074233 Owner-Facility: Blackburn Elementary School
Inspection Date: 12/01/2015 Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ ® ❑
application?
Is the facility as described in the permit? ■ ❑ ❑ ❑
#Are there any special conditions for the permit? ❑ M ❑ ❑
Is access to the plant site restricted to the,general public? ■ ❑ ❑ ❑
Is the inspector granted access to all areas for Inspection? O ❑ ❑ ❑
Comment:
Operations& Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? ® ❑ ❑ ❑
Does the facility analyze process control parameters,for ex- MLSS, MCRT, Settleable ❑ ❑ ® ❑
Solids, pH,DO, Sludge Judge, and other that are applicable?
Comment: Pit in which chlorinator and de-chlorinator are located may be consdered a"confined space"
and should be addresses in accordance with OSHA 29 CFR 1910.146.
Danger Keep Out signs should be posted around facility fence.
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit? ® ❑ ❑ ❑
Is all required information readily available, complete and current? ® ❑ ❑ ❑
Are all records maintained for 3 years(lab. reg. required 5 years)? ❑ ❑ ❑ ❑
Are analytical results consistent with data reported on DMRs? 0 ❑ ❑ ❑
Is the chain-of-custody complete? ® ❑ ❑ ❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete:do they include all permit parameters? ® ❑ ❑ ❑
Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ ❑ M
(If the facility is=or>5 MGD permitted flow)Do they operate 24/7 with a certified operator ❑ ❑ M ❑
on each shift?
Is the ORC visitation log available and current? M ❑ ❑ ❑
Is the ORC certified at grade equal to or higher than the facility classification? 0 ❑ ❑ ❑
Is the backup operator certified at one grade less or greater than the facility classification? 0 ❑ ❑ ❑
Page# 3
Permit: NCO074233 Owner-Facility: Blackburn Elementary School
Inspection Date: 12/01/2015 Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Is a copy of the current NPDES permit available on site?, M ❑ ❑ ❑
Facility has copy of previous year's Annual Report on file for review? M ❑ ❑ ❑
Comment: Records kept at Catawba County School Maintenace building.
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory? e ❑ ❑ ❑
Are all other parameters(excluding field parameters)performed by a certified lab? M ❑ ❑ ❑
#Is the facility using a contract lab? M ❑ ❑ ❑
#Is proper temperature set for sample storage(kept at less than or'equal to 6.0 degrees 0 ❑ ❑ ❑
Celsius)?
Incubator(Fecal Coliform)set to 44.5 degrees Celsius+/-0.2 degrees? ❑ ❑ ❑
Incubator(BOD)set to 20.0 degrees Celsius+/-1 0 degrees? ❑ ❑ ❑
Comment:
Sand Filters (Low rate) Yes No NA NE
(If pumps are used)Is an audible and visible alarm Present and operational? ® ❑ ❑ ❑
Is the distribution box level and watertight? ❑ ❑ ® ❑
Is sand filter free of ponding? ® ❑ ❑ ❑
Is the sand filter effluent re-circulated at a valid ratio? ® ❑ ❑ ❑
#Is the sand filter surface free of algae or excessive vegetation? ® ❑ ❑ ❑
#Is the sand filter effluent re-circulated at a valid ratio?(Approximately 3 to 1) ® ❑ ❑ ❑
Comment:
Disinfection-Tablet Yes No NA NE
Are tablet chlorinators operational? M ❑ ❑ ❑
Are the tablets the proper size and type? ■ ❑ ❑ ❑
Number of tubes in use? 6
Is the level of chlorine residual acceptable? ® ❑ ❑ ❑
Is the contact chamber free of growth, or sludge buildup? ■ ❑l ❑ ❑
Is there chlorine residual prior to de-chlorination? 0 ❑ ❑ ❑
Comment:
Septic Tank Yes No NA NE
Page# 4
Permit: NC0074233 Owner-Facility: Blackburn Elementary School
Inspection Date: 12/01/2015 Inspection Type: Compliance Evaluation
Septic Tank Yes No NA NE
(If pumps are used) Is an audible and visual alarm operational? ❑ ❑ ® ❑
Is septic tank pumped on a schedule? M ❑ ❑ ❑
Are pumps or syphons operating properly? ® ❑ ❑ ❑
Are high and low water alarms operating properly? ❑ ❑ i ❑
Comment:
De-chlorination Yes No NA NE
Type of system? Tablet
Is the feed ratio proportional to chlorine amount(1 to 1)? ® ❑ ❑ ❑
Is storage appropriate for cylinders? ❑ ❑ ® ❑
#Is de-chlorination substance stored away from chlorine containers? ® ❑ ❑ ❑
Comment:
Are the tablets the proper size and type? ® ❑ ❑ ❑
Are tablet de-chlorinators operational? ® ❑ ❑ ❑
Number of tubes in use? 6
Comment:
Page# 5