HomeMy WebLinkAboutWQ0016376_Compliance Evaluation Inspection_20240312DocuSign Envelope ID: A478E754-6079-44F9-AF59-7C9DDEF726CE
Compliance Inspection Report
Permit: WQ0016376 Effective: 10/20/20 Expiration: 11/30/25 Owner : S & J Villari Livestock LLC
SOC: Effective: Expiration: Facility: S & J Villari Livestock WWTF
County: Duplin 892 Penny Branch Rd
Region: Wilmington
Warsaw NC 283987760
Contact Person: Jeff P Cappadona Title: Engineer Phone: 910-233-0075
Directions to Facility:
1-40 to Exit 364, Warsaw. West on Hwy 24 for 0.9 mi. North on Old Courthouse Road for 0.9 mi, Turn right on Penny Branch Rd.,
travel 1.8 mi to entrance on left.
System Classifications: S1,
Primary ORC: Gerald Lamar Matthews Certification: 993131 Phone: 910-293-2157
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
Inspection Date: 03/12/2024 Entry Time 10:OOAM Exit Time: 11:30AM
Primary Inspector: Helen I Perez DDo uSig ed by. Phone: 910-796-7387
Secondary Inspector(s):E lI^J
1 D645B4A39694BE...
Reason for Inspection: Routine Inspection Type: Compliance Evaluation
Permit Inspection Type: Wastewater Irrigation
Facility Status: ❑ Compliant Not Compliant
Question Areas:
Treatment Flow Measurement -Effluent Treatment Flow Measurement -Influent Miscellaneous Questions
Treatment Flow Measurement -Water Treatment Treatment Barscreen
Use Records
Record Keeping Treatment Lagoons End Use -Irrigation
Treatment Disinfection Treatment Flow Measurement
(See attachment summary)
Page 1 of 7
DocuSign Envelope ID: A478E754-6079-44F9-AF59-7C9DDEF726CE
Permit: WQ0016376 Owner - Facility: S & J Villari Livestock LLC
Inspection Date: 03/12/2024 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
A routine compliance inspection of the S & J Villari Livestock WWTF was conducted on March 12, 2024. The purpose of the
evaluation was to verify that the facility is operating in compliance with the conditions and limitations specified in Permit
WQ0016376. Gerald Matthews, ORC, was present during the inspection.
This facility is a facultative lagoon, spray irrigation system for industrial waste. In January of this year, the average flow was
66,575 GPD of the 100,260 GPD permitted flow. Measuring of the solids in the synthetically -lined lagoon will be done in the
near future. The Permittee is considering sending the solids to Carbon Cycle, located across the street from the facility,
when they complete construction. There have been some odor complaints from neighboring residents. The facility has a
spray odor system along the edge of the spray fields to help with the odor. There appears to be a need for more signs/gates
to restrict public access to the irrigation fields, especially Fields 14E and 14W, along Blackmore Road.
A review of records showed that all of the 2022 and 2023 GW-59s were not submitted as required. The ORC electronically
sent these copies to the Wilmington Regional Office (WIRO) after the inspection. A review of the missing GW-59s show
some intermittent exceedances of Nitrate in MW-2, MW-8 and MW-9 and Ammonia exceedances in MW-7. The pH level
tends to be low in all of the monitoring wells. The WIRO will continue to watch the trends of these wells. MW-5 has not been
sampled since July 2022. This issue needs to be corrected as soon as possible. Please submit the quarterly GW-59s on
time going forward.
The Annual Soil Analysis Report was not available for review. The ORC stated that lime will be applied when field conditions
are adaquate. Results of these reports are required to be maintained at the facility for five years and be made available upon
request.
The facility is non -compliant with Non -Discharge Permit W00016376. A Notice of Deficiency will be issued for the issues
discussed above. Please review the comment sections of the inspection report for more details.
Page 2 of 7
DocuSign Envelope ID: A478E754-6079-44F9-AF59-7C9DDEF726CE
Permit: WQ0016376 Owner - Facility: S & J Villari Livestock LLC
Inspection Date: 03/12/2024 Inspection Type: Compliance Evaluation
Reason for Visit: Routine
Type
Yes No NA NE
Reuse (Quality)
❑
Infiltration System
❑
Single Family Spray, LR
❑
Activated Sludge Spray, LR
❑
Activated Sludge Spray, HR
❑
Activated Sludge Drip, LR
❑
Recycle/Reuse
❑
Single Family Drip
❑
Lagoon Spray, LR
Treatment Yes No NA NE
Are Treatment facilities consistent with those outlined in the current permit? ❑ 0 ❑ ❑
Do all treatment units appear to be operational? (if no, note below.) 0 ❑ ❑ ❑
Comment: The facultative lagoon does not have a curtain baffle or 2 floating aerators as written in the
permit description.
Treatment Flow Measurement -Influent
Yes No NA NE
Is flowmeter calibrated annually?
❑ ❑ ❑
Is flowmeter operating properly?
❑
❑ ❑
Does flowmeter monitor continuously?
❑ ❑ ❑
Does flowmeter record flow?
❑ ❑ ❑
Does flowmeter appear to monitor accurately?
❑ ❑ ❑
Comment: The influent flowmeter was recently replaced. It was calibrated on 3/11/2024 by Agriment
Services.
Treatment Flow Measurement -Water Use Records Yes No NA NE
Is water use metered? ❑ ❑ ❑
Are the daily average values properly calculated? ❑ ❑ 0❑
Comment:
Treatment Flow Measurement -Effluent Yes No NA NE
Is flowmeter calibrated annually? 0 ❑ ❑ ❑
Is flowmeter operating properly? ❑ ❑ ❑
Does flowmeter monitor continuously? ❑ ❑ ❑
Does flowmeter record flow? ❑ ❑ ❑
Does flowmeter appear to monitor accurately? 0 ❑ ❑ ❑
Comment: The effluent flowmeters for the solid set and the center pivot irrigation systems was calibrated
on 03/11/2024 byAgriment Services.
Page 3 of 7
DocuSign Envelope ID: A478E754-6079-44F9-AF59-7C9DDEF726CE
Permit: WQ0016376 Owner - Facility: S & J Villari Livestock LLC
Inspection Date: 03/12/2024 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Treatment Barscreen Yes No NA NE
Is it free of excessive debris? ❑ ❑ ❑ ❑
Is disposal of screenings in compliance? ❑ ❑ ❑ ❑
Are the bars spaced properly? ❑ ❑ ❑ ❑
Is the unit in good condition? ❑ ❑ ❑ ❑
Comment: The T-R solids separator, located in a pit at the back of the industry building, appeared to be
in good operating condition. The solids are separated before entering the lagoon and are
hauled off site by Darlinq Ingredients.
Treatment Disinfection
Is the system working?
Do the fecal coliform results indicate proper disinfection?
Is there adequate detention time (-30 minutes)?
Is the system properly maintained?
If gas, does the cylinder storage appear safe?
Is the fan in the chlorine feed room and storage area operable?
Is the chlorinator accessible?
If tablets, are tablets present?
Are the tablets the proper size and type?
Is contact chamber free of sludge, solids, and growth?
If UV, are extra UV bulbs available?
If UV, is the UV intensity adequate?
# Is it a dual feed system?
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)?
If yes, then is there a Risk Management Plan on site?
If yes, then what is the EPA twelve digit ID Number? (1000- - )
Yes No NA NE
■❑❑❑
❑ ❑ ❑ ❑
❑❑❑■
■❑❑❑
❑❑■❑
❑❑■❑
❑❑■❑
❑❑■❑
❑❑■❑
❑❑■❑
If yes, then when was the RMP last updated?
Comment: Effluent is pumped from the 1.88 MG stainless steel storage tank throuqh the 21,000 gallon
chlorine contact tank before irrigation. Liquid chlorine is used. The visual and audible alarms
for the contact chamber tank were operational when tested. The grab samples for TRC is
collected at a spigot off of the contact chamber. The TRC is analyzed by Envirochem Lab staff
weekly on site.
Record Keeping
Yes No NA NE
Is a copy of current permit available?
0
❑ ❑ ❑
Are monitoring reports present: NDMR?
❑
❑ ❑
NDAR?
❑
❑ ❑
Are flow rates less than of permitted flow?
❑ ❑ ❑
Are flow rates less than of permitted flow?
❑ ❑ ❑
Are application rates adhered to?
❑ ❑ ❑
Page 4 of 7
DocuSign Envelope ID: A478E754-6079-44F9-AF59-7C9DDEF726CE
Permit: WQ0016376 Owner - Facility: S & J Villari Livestock LLC
Inspection Date: 03/12/2024 Inspection Type: Compliance Evaluation
Reason for Visit: Routine
Is GW monitoring being conducted, if required (GW-59s submitted)?
0
❑ ❑ ❑
Are all samples analyzed for all required parameters?
0
❑ ❑ ❑
Are there any 2L GW quality violations?
0
❑ ❑ ❑
Is GW-59A certification form completed for facility?
❑
❑ ❑
Is effluent sampled for same parameters as GW?
0
❑ ❑ ❑
Do effluent concentrations exceed GW standards?
❑
❑ ❑
Are annual soil reports available?
❑
0 ❑ ❑
# Are PAN records required?
0
❑ ❑ ❑
# Did last soil report indicate a need for lime?
❑
❑ 0 ❑
If so, has it been applied?
❑
❑ 0 ❑
Are operational logs present?
0
❑ ❑ ❑
Are lab sheets available for review?
0
❑ ❑ ❑
Do lab sheets support data reported on NDMR?
0
❑ ❑ ❑
Do lab sheets support data reported on GW-59s?
❑
❑ ❑
Are Operational and Maintenance records present?
0
❑ ❑ ❑
Were Operational and Maintenance records complete?
0
❑ ❑ ❑
Has permittee been free of public complaints in last 12 months?
❑
0 ❑ ❑
Is a copy of the SOC readily available?
❑
❑ 0 ❑
No treatment units bypassed since last inspection?
0
❑ ❑ ❑
Comment: Operational and maintenance records consists of dailv check sheets and Preventative
Maintenance Work Orders that are dated and signed when completed. The field parameters,
TRC and pH, are analyzed by Envirochem Lab staff weekly. Envirochem calibrations, bench
sheets and Chain of Custodies were reviewed and appear to be complete. GW-59 reports for
2022 and 2023 were not submitted, but the monitoring wells were sampled and tested by
Envirochem. The ORC forwarded the reports electronically to WIRO after the inspection for
review and is in the process of uploading them to Laserfiche. After review, it was found that
MW-5 had not been sampled since July 2022. An annual soil analysis was not availble for
review.
End Use -Irrigation
Are buffers adequate?
Is the cover crop type specified in permit?
Is the crop cover acceptable?
Is the site condition adequate?
Is the site free of runoff / ponding?
Is the acreage specified in the permit being utilized?
Is the application equipment present?
Is the application equipment operational?
Is the disposal field free of limiting slopes?
Is access restricted and/or signs posted during active site use?
Yes No NA NE
■❑❑❑
■❑❑❑
❑ ❑ ❑
❑ ❑ ❑
■❑❑❑
Page 5 of 7
DocuSign Envelope ID: A478E754-6079-44F9-AF59-7C9DDEF726CE
Permit: WQ0016376 Owner - Facility: S & J Villari Livestock LLC
Inspection Date: 03/12/2024 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Are any supply wells within the CB? ❑ ❑ ❑
Are any supply wells within 250' of the CB? ❑ ❑ ❑
How close is the closest water supply well? ❑ ❑ ❑
Is municipal water available in the area? 0 ❑ ❑ ❑
# Info only: Does the permit call for monitoring wells? 0 ❑ ❑ ❑
Are GW monitoring wells located properly w/ respect to RB and CB? 0 ❑ ❑ ❑
Are GW monitoring wells properly constructed, including screened interval? ❑ ❑ ❑
Are monitoring wells damaged? ❑ 0 ❑ ❑
Comment: The Center Pivot, for Fields 14E and 14W, was observed to have some clopped or missing
spray heads while in operation during the inspection. The ORC had the pivot serviced and
cleaned as part of a PM Work Order, and sent verification that it was completed the following
week. The crop on Fields 1-13 and 15-17 need to be cut and baled. ORC indicated that they
are waiting on acceptable field conditions to allow maintenance of the irrigation areas. Please
remember that, according to Condition 11.4 of the permit, the Permittee shall maintain the
vegetative cover on the irrigation sites such that crop health is optimal, allows even effluent
distribution and allows inspection of the irrigation system. The permit allows for double
cropping to have a healthy crop for irrigation year round, which increases the PAN limit from
300 to 350 Ibs/acre.
FACULTATIVE LAGOON
Treatment Lagoons
Yes No NA NE
Lagoon Type
None
Primary/Secondary
Primary
Influent structure
❑ ❑ ❑
Banks/berms (seepage and erosion) ❑ 0 ❑ ❑
Vegetation (excessive vegetation on banks/berms) ❑ 0 ❑ ❑
Liner 0 ❑ ❑ ❑
Liner Type Full, synthetic
Baffles/curtains ❑ 0 ❑ ❑
Freeboard Marker 0 ❑ ❑ ❑
Required freeboard 2
Feet
Actual freeboard 3
Feet
Are increments clearly marked on gauge at adequate intervals? 0 ❑ ❑ ❑
Has the water level gauge been surveyed w/ respect to lowest point on dike? wall? ❑ ❑ ❑
No Evidence of overflow 0 ❑ ❑ ❑
Acceptable color 0 ❑ ❑ ❑
Page 6 of 7
DocuSign Envelope ID: A478E754-6079-44F9-AF59-7C9DDEF726CE
Permit: WQ0016376 Owner - Facility: S & J Villari Livestock LLC
Inspection Date: 03/12/2024 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Floating mats
Excessive solids buildup
Aerators/mixers
Effluent structure
Lagoon cover
Page 7 of 7