HomeMy WebLinkAboutNC0079821_Compliance Evaluation Inspection_20151116North Carolina Department of Environmental Quality
Pat McCrory Donald R. van der Vaart
Governor Secretary
November 16, 2015
Winston Salem/Forsyth County Utilities Division
Attn: Ron Hargrove, Utilities Director
P.O. Box 2511
Winston Salem, NC 27102-2511
Subject: Compliance Evaluation Inspections
NPDES Permits: NC0086011,-Neilson-Water-Treatment-Plant
N00079821,RAThomas Water Treatment Planta �
- Forsyth County
Dear Mr. Hargrove:
1. Ron Boone of the Winston-Salem Regional Office of the NC Division of Water Resources (DWR or the Division) conducted
compliance evaluation inspections (CEI) at the Neilson and RA Thomas water treatment plants on November 13, 2015. The
assistance and cooperation of Bill Brewer, Rodney Darr, and Kenneth Atkins was greatly appreciated. Inspection reports are
attached for your records and the inspection findings are summarized below.
NCO086011, NEILSON WATER TREATMENT PLANT
General
2. The facility is located at 5725 Frye Bridge Road, in Winston Salem, Forsyth County, North Carolina. The facility is authorized
to discharge wastewater from the treatment works through outfall 001 to an unnamed tributary (UT) of Muddy Creek, this
section of which is currently classified as Class C waters in the Yadkin Pee -Dee River basin. However, the wastewater
treatment system does NOT discharge. All wastewater is recycled through two wastewater treatment, lagoons and one. of the
raw water reservoirs. The wastewater is then treated through the potable water treatment system. The waste stream consists
of backwash water from the water treatment system's filters and sludge from the water treatment system's sedimentation
basins.
Documentation & Monitoring Review
3. All required records were readily available, complete, and current. There are no DMRs for review. The plant currently has a
waiver from submitting monthly DMRs because the plant recycles all wastewater and there is no discharge. The waiver is in
effect until the plant begins discharging again.
Site Review
4. Filter backwash wastewater is pumped to the easternmost raw water reservoir. Sedimentation basin blowdowns (sludge) go
to one of three waste lagoons and decant from that sludge is then also pumped to the easternmost raw water reservoir. All
wastewater is recycled through this process and then back through the potable water treatment system. As stated above,
there is currently no discharge from the waste treatment system. Decanted and dried sludge from the waste lagoons is land
disposed on the "Cooper Road Disposal Site", which is located a few miles from the water treatment plant.
The site was very clean and no discrepancies or violations were noted.
North Carolina Division of Water Resources, Winston-Salem Regional Office
Location: 450 West Hanes Mill Road, Winston-Salem, North Carolina 27105
Phone: 336-776-98001 FAQ(: 336-776-97971 Customer Service; 1-877-623-6748
Internet: www.ncwaterquality.org
An Equal Opportunity 1 Affirmative Action Employer
NC0079821, RA THOMAS WATER TREATMENT PLANT
General
5. All required records were readily available, complete, and current. Discharge monitoring reports for 2015 were reviewed and
no discrepancies were noted.
Site Review
6. Filter backwash wastewater goes directly to the equalization basin, then to the clarifier. The treated effluent from the clarifier
goes to a flume where it is measured and discharged. The sludge from the clarifier goes to the waste lagoons. Sedimentation
basin blowdowns (sludge) go directly to the waste lagoons. Decant from the waste lagoons goes to the equalization basin,
then to the clarifier. The effluent flow meter was last calibrated on September 16, 2015.
Please encourage your operators to continue their outstanding efforts in complying with all permit conditions. Should you have
any questions, please feel free to contact Mr. Boone or me at (336) 776-9800.
Sincerely,
'4"" -- +<','
Sherri V. Knight
Asst. Regional Supervisor
Water Quality Regional Operations
Division of Water Resources
Attachments:
1. BIMS Inspection Reports
cc: SWP — WSRO
Central Files
6NPDES 6nit_7
City of Winston Salem
Neilson Water Treatment Plant
Attn: Rodney Darr
5725 Frye Bridge Road
Clemmons, NC 27012
City of Winston Salem
RA Thomas Water Treatment Plant
Attn: Kenny Atkins
1201 South MLK Junior Drive
Winston Salem, NC 27107
United States Environmental Protection Agency
EPA
Form Approved
EPA Washington, D C 20460
OMB No 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 15 I 3 I NCO079821 111 12 15/11/13 17 18 Li19 L G i 20 LJ
21111111 111111111111111111111111111111111111 f6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA ----------------Reserved---------
I 71 I lI 72 L LN j 73LI 174 751 I I I I I I 180
67 70 L_it J I I I
Section B. FacilityData
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
10 30AM 15/11/13
09/09/01
RA Thomas WTP
1201 Martin Luther King J
Exit Time/Date
Permit Expiration Date
Winston Salem NC 27107
11 30AM 15/11/13
14/06/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Kenneth Craig Atkins/ORC/336-784-7597/
Name, Address of Responsible Official[Title/Phone and Fax Number
Contacted
Edward Nathaniel Davis,PO Box 2511 Winston Salem NC 271079998//336-784-7597/
No
Section C. Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program ■ Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory
Section D. Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Ron Boone WSRO WQ//336-776-9690/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
15-
S
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete
Page#
NPDES yr/mo/day Inspection Type
31 NCO079821 111 121 15/11/13 117 18 „
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Please refer to the attached inspection summary letter.
Page#
Permit: NCO079821 Owner -Facility: RA Thomas WTP
Inspection Date: 11/13/2015 Inspection Type: Compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires In 6 months or less). Has the permittee submitted a new
❑
❑
0
❑
application
0
❑
❑
❑
Is the facility as described In the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
0
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the Inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: None
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab, reg required 5 years)?
0
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
Name of Individual performing the sampling
0
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they Include all permit parameters?
0
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
_ ❑
❑
0
❑
(If the facility Is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
0
❑
❑
on each shift?
Is the ORC visitation log available and current?
0
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
0
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
0
❑
❑
❑
Is a copy of the current NPDES permit available on site?
0
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
0
❑
Comment: None
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory? 0 ❑ ❑ ❑
Are all other parameters(excluding field parameters) performed by a certified lab? 0 ❑ ❑ ❑
Page# 3
Permit: NCO079821
Inspection Date: 11/13/2015
Laboratory
Owner -Facility: RA Thomas WTP
Inspection Type: Compliance Evaluation
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6 0 degrees
Celsius)?
Incubator (Fecal Coliform) set to 44 5 degrees Celsius+/- 0 2 degrees?
Incubator (BOD) set to 20 0 degrees Celsius +/- 1 0 degrees?
Comment: None
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment. None
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment: None
Operations & Maintenance
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex. MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: None
Yes No NA NE
❑ ❑ ■ ❑
❑ ❑ ■ ❑
Yes No NA NE
•
❑
❑
❑
®
❑
❑
❑
❑
❑
M
❑ 1
Yes No NA NE
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ i ❑
Yes No NA NE
i ❑ ❑ ❑
■❑❑❑
Page# 4