HomeMy WebLinkAboutNC0081256_Permit Modification_20041026ftf rCce4f dR4)1
A71A.
NCDENR
North Carolina Department of Environment and Natural Resources
Division of Water Quality
Michael F. Easley, Governor
Mr. Wendell Pickett
Ward WTP Supervisor
Post Office Box 230
High Point, North Carolina 27261
Dear Mr. Pickett:
William G. Ross, Jr., Secretary
Alan W. Klimek, P.E., Director
October? 2 4
Subject: Modification of NPDES Permit NCO081256
FrankL. Ward WTP
Guilford County
The Division has reviewed and approved your request to modify the subject permit. This modification
allows for the temporary use of outfall 002, an alternate outfall from the North Lagoon at your facility. This
modification is for temporary use of 002 only. Outfall 002 is only to be used when outfall 001 is unavailable due
to maintenance or similar operations. At no time may your facility discharge from both outfalls. Limits and
monitoring requirements apply to any discharge from either outfall. No other changes to the permit have been
made.
Please find enclosed the revised pages, which should be inserted into your permit. The old pages may then
be discarded. All other terms and conditions contained in the original permit remain unchanged and in full
effect. This permit modification is issued under the requirements of North Carolina General Statutes 143-215.1
and the Memorandum of Agreement between North Carolina and the U.S. Environmental Protection Agency.
If any parts, measurement frequencies or sampling requirements contained in this permit modification are
unacceptable to you, you have the right to an adjudicatory hearing upon written request within thirty (30) days
following receipt of this letter. This request must be a written petition conforming to Chapter 150B of the North
Carolina General Statutes, filed with the Office of Administrative Hearings (6714 Mail Service Center, Raleigh,
North Carolina 27699-6714). Unless such demand is made, this decision shall be final and binding. If you have
any questions concerning this permit modification, please contact Charles Weaver of the NPDES Unit at (919)
733-5083, extension 511.
Sincerely,
(*I,Xlan W. Klimek, P.E.
cc: Central Files
Winston-Salem Regional Office / Corey Basinger
NPDES Unit
1617 Mail Service Center, Raleigh, North Carolina 27699.1617
512 N. Salisbury St., Raleigh, North Carolina 27604 Nonl hCarohna
Phone: 919-733-70151 FAX 919-733-24961 Internet: h2o.enr.state.nc.us An Equal Opportunity/AffirmativeAdonEmployer- 50% Recyclerll�atu
l0%PostConsumerPaper LNallaff
Permit NCO081256
SUPPLEMENT TO PERMIT COVER SHEET
All previous NPDES Permits issued to this facility, whether for operation or discharge are hereby
revoked. As of this permit issuance, any previously issued permit bearing this number is no longer
effective. Therefore, the exclusive authority to operate and discharge from this facility arises under
the permit conditions, requirements, terms, and provisions included herein.
The City of High Point is hereby authorized to:
1. Continue to operate a water treatment plant with a discharge of filter -backwash
wastewater. This facility is located in High Point at the Frank L. Ward WTP on
East Kivett Drive in Guilford County.
2. Discharge from the South Lagoon via outfall 001 at the location specified on the
attached map into an unnamed tributary to Richland Creek, classified C waters
in the Cape Fear River Basin.
3. Discharge from the North Lagoon on an as -needed basis via outfall 002 [ca. 400
feet upstream of outfall 0011 into an unnamed tributary to Richland Creek,
classified C waters in the Cape Fear River Basin.
Permit NC0081256
A. (1.) EFFLUENT LBUTATIONS AND MONITORING REQUIREMENTS
During the period beginning on November 1, 2004 and lasting until expiration, the Permittee is
authorized to discharge from outfall 001 or 002. Discharge may occur from only one outfall.
Simultaneous discharge from both outfalls is prohibited. Discharges from either outfall shall be
limited and monitored by the Permittee as specified below:
EFFLUENT
CHARACTERISTICS
LIMITS
MONITORING REQUIREMENTS
Monthly
Average
Daily
Maximum
Measurement
Frequency
Sample Type
Sample Location
Flow
Weekly
Instantaneous
Effluent
Total Suspended Residue
30.0 mglL
45.0 mglL
21Month
Grab
Effluent
Settleable Solids
0.1 mVL
0.2 mVL
Weekly
Grab
Effluent
Turbidity'
Weekly
Grab
Upstream & Downstream
Total Residual Chlorine
Weekly
Grab
Effluent
Aluminum
Weekly
Grab
Effluent
Footnotes:
1. The discharge from this facility shall not cause turbidity in the receiving stream to exceed 50 NTU. If the
instream turbidity exceeds 50 NTU due to natural background conditions, the discharge cannot cause
turbidity to increase in the receiving stream.
All samples must be collected from a typical discharge event.
There shall be no discharge of floating solids or visible foam in other than trace amounts.
CITY OF HIGH POINT
NORTH CAROLINA
August 26, 2004
Dave Goodrich
Division of Water Quality / NPDES Unit
1617 Mail Service Center
Raleigh, NC 27699-1617
Subject: Minor Permit Modification
J
SEP
City of High Point — Frank L. Ward WTP
NPDES Permit No. NCO081256
Guilford County
Dear Mr. Goodrich,
Please find enclosed a NPDES Short Permit Application for the Frank L. Ward WTP.
After talking to Cory Basinger in the Winston Salem regional office and Susan Wilson in
the Raleigh office, it was suggested that I fill out this application and give you a detailed
explanation of what we wanted to do.
We have 2 alum sludge lagoons in which we put our treatment solids. At the present time
our south lagoon is fulL what we would like to do is to permit another discharge point on
the north lagoon until we can get the south lagoon cleaned. This point would only be used
temporarily or if we needed to do maintenance on the other lagoon. At no time would we
use both discharge points simultaneously. The temporary discharge point would be
approximately 400 ft. up stream of the original point and would be sampled as permit
requirements dictate. A diagram has been enclosed to illiterate its relation to the original
discharge point. We would call it 002. If you have any other questions, please contact me
at 336-883-3410. Thank you.
Sincerely
Wendell Pickett
City of High Point
Ward Water Treatment Superintendent
PUBLIC SERVICES DEPARTMENT, P.O. BOX 230, High Point, North Carolina, 27261
Telephone (336) 883-3410 Fax (336) 883-3109 TDD (336) 883-8517
NPDES PERMIT APPLICATION - SHORT FORM C-WTP
For discharges associated with conventional water treatment plants
N. C. Department of Environment and Natural Resources
Division of Water Quality / NPDES Unit
1617 Mail Service Center, Raleigh, NC 27699-1617
NPDES Permit Number C00 81256
1. Contact Information:
Facility Name
Owner Name
Street Address
City
State / Zip Code
Telephone Number
Fax Number
e-mail Address
Operator Name
Street Address
City
State / Zip Code
Telephone Number
Please print or type
Frank L. Ward WTP
of High Point
2011 E. Kiveit Drive
High Point
North Carolina 27260
( 336 ) 883-3410
( 336 ) 883-3109
wspickeft@ci.high-point.nc.us
Robert Wendell Pickett
302 Carriage Lane
Linwood
North Carolina 27299
( 336 ) 853-2091
2. Location of facility producing discharge:
Facility Name (If different from above)
Street Address or State Road
City / Zip Code
County Guilford
3. Standard Industrial Classification (SIC) Codes:4941
4.
Principal process(es): Water Treatment
5. Ownership Status:
Federal 0 State 0 Private 0
6. Check here if discharge is continuous 19
If not continuous,
Frequency of discharge during the day:
Frequency of discharge during the month (week):
7. Number of separate discharge points: 2 (1 permitted )
S. Description of source water(s) (i.e. ground water or surface water)
Surface Water
Public
Page 1 of 2 Version -OW3
NPDES PERMIT APPLICATION - SHORT FORM C-WTP
For discharges associated with conventional water treatment plants
9. Name of receiving stream(s) (Provide map of exact location of each outfall, including latitude and
longitude:
unnamed Tributary to Richland Creek, 001- N35t8.053', W7cY58.326, 002-N35p58.120, W79a58.317
10. List all permits, construction approvals and/or applications (check all that apply and provide
permit numbers or check none if not applicable):
Tyae Permit Number
Tyke Permit Number
[]
None
p
Non -Attainment
0
UIC
Ocean Dumping
®
NPDES NCO081256
0 Dredge/Fill Permits
PSD
RCRA
NESHAPS
0
Other
11. Is this facility located on Native American lands? (check one)
YES
12. Please list all water treatment additives, including cleaning chemicals, that have the
potential to be discharged.
Aluminum Sulfate
yaustic soaa
Bleach
13. For .NEW water treatment plants, please submit all analyses of source water collected.
I certify that I am familiar with the information contained in the application and that to the best
of my knowledge and belief such information is true, complete, and accurate.
Robert Wendell Pickett
Printed name of Person Signing
tore of Applicant
Water Treatment Plant Superintendent
Title
Date
North Carolina General Statute 143-215.6 (b)(2) provides that: Any person who knowingly makes any false statement representation, or
certification in any application, record, report, plan, or other document files or required to be maintained under Article 21 or regulations of the
Environmental Management Commission implementing that Article, or who falsifies, tampers with, or knowingly renders inaccurate any
recording or monitoring device or method required to be operated or maintained under Article 21 or regulations of the Environmental
Management Commission implementing that Article, shall be guilty of a misdemeanor punishable by a fine not to exceed $10 000 or by
imprisonment not to exceed sox months, or by both. (18 U.S.C. Section 1001 provides a punishment by a fine of not more than $10,000 or
imprisonment not more than 5 years, or both, for a similar offense.)
Page 2 of 2 Version -003
Fhmary I ooM air
Sowce (-Damns
R Rv Wab
Fmm Ndbw Lab fPo/Ymerf
1
Sfatlm
coJafN1
a -pampa
Secondary sowce
CTemkal Btdk Tank,
1-6,000 WI. Fluolkb Tank
3-10,000 gal. Cau Tank
1- 6,000 gal. C.011oabn Inhk Tank
1- 20,000 gal. Num Tank ( undmgmmal)
Yrr—pmydbrnWga' �S'
Da N.pa L_ 111
D f
YiT laanm
CRY of High Point
Wrd WaterFptrvtlon P/rd
PWS ID O1d1-020
a NTH
Tank
003 LofnW
Mramlwnt
(Nmm�nh Aor
mnvxnaf alnlNy n uv)
(aernMaty
tiw Lhbrml Xnnf ,mmy in uaa)
k (Alum eddltlanl
Compll. ample
Fb—Amaon
jC..Dc sod)
IlnlahaC
upnow Cla flcalicn
Non,MarcoEa001
oanpl vmplaa
law Ylan! Oda 01T
C
Coop. Cade im
aatlW wmrr 103
IIbM watx m0a 002
fella. m
O O O
3-10,000 pals. Bulk Bleach Tanta
SaM tapom
�FaNa
Wafr
a-P�1ra1
FYna