HomeMy WebLinkAboutNC0089893_Compliance Evaluation Inspection_20231212 (3)United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NCO089893 111 121 23/12/05 I17 18 LC] I 19 I s I 20L]
21111I I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
I 72 I n, I 71 I 74 79 I I I I I I I80
701� I 711 L
LJ L -1 I I
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES Dermit Number)
11:03AM 23/12/05
23/05/01
Yadkin River Water Treatment Plant
3522 New Salem Rd
Exit Time/Date
Permit Expiration Date
Unionville NC 28110
12:07PM 23/12/05
25/06/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Jonathan T Smith/ORC/704-320-6758/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Brian Matthews,500 N Main St Ste 920 Monroe NC 28112//704-292-2597/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Records/Reports Facility Site Review
Effluent/Receiving Wate
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Sig natur )Dqt g%R"r(s) Agency/Office/Phone and Fax Numbers Date
Lrtj�6 ��Roberto Scheller DWR/MRO WQ/707-235-2204/ 12/11/2023
2A007838943E...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
Brandy Costner DWR/MRO WQ/704-235-2185/ DocuSigned by: 12/12/2023
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. �-27DF9ACFbs8043F...
Page#
NPDES yr/mo/day Inspection Type
NCO089893 I11 12I 23/12/05 117 18 i c i
(Cont.)
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
The Yadkin River Water Treatment Plant has Grade I Physical -Chemical treatment under NPDES
Permit # NC0089893. The subject permit became effective July 1, 2020, and expires on June 30,
2025. Facility has a design potable flowrate of 13 MGD and a maximum monthly average wastewater
discharge of 0.49 MGD. Discharge is into an unnamed tributary of Richardson Creek, Class C waters,
in the Yadkin -Pee Dee River Basin.
During the on -site inspection and records review it was noted that flow rates are above permitted
limits. Facility is reported as having issues with start-up and as of the date of inspection, has not
started producing potable water for distribution. Flow is to be reported in Million Gallons per Day
(MGD).
Effluent discharge was clear with no visible suspended soilds at point of discharge from Outfall #001.
Discharge pipe stops short of creek and flows down gradient, overland, to creek creating erosion and
turbidity issues. Effluent should be in a pipe or lined constructed channel to discharge into Ut of
Richardson Creek. Please note that construction of discharge point on creek may require a 404
and/or 401 Permit.
Page#
Permit: NC0089893
Inspection Date: 12/05/2023
Owner -Facility: Yadkin River Water Treatment Plant
Inspection Type: Compliance Evaluation
Permit
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Comment:
Yes No NA NE
❑ ❑ ■ ❑
■ ❑ ❑ ❑
❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Page# 3