HomeMy WebLinkAboutNC0038300_CEI 2024_20240226 United States Environmental Protection Agency Form Approved.
EPA Washington,D.C.20460 OMB No.2040-0057
Water Compliance Inspection Report Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 [ j 2 H 3 I NCO038300 111 121 24/02/26 I17 18 I r I 19 I G j 201
211 11 I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I 1 1 I I �66
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
67 70 I I 71 I L
I 72 I r i I 73 I� I 74 71 I I I I I I I80
LJ L Section B: Facility Data J I
Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date
POTW name and NPDES permit Number) 10:30AM 24/02/26 22/08/01
S.S. Mobile Home Park
241 Graham Moore Rd Exit Time/Date Permit Expiration Date
Staley NC 27355 11:45AM 24/02/26 26/09/30
Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data
Name,Address of Responsible Official/Title/Phone and Fax Number
Contacted
James Reginald Edwards,1808 Pinecrest St Burlington NC
272155639H336-260-3396/3362271202 No
Section C:Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Operations&Maintenar Records/Reports 0 Self-Monitoring Progran
Sludge Handling Dispo: 0 Facility Site Review Effluent/Receiving Wate
Section D: Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s)and Signature(s)of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Stephen D Smith DWR/RRO WQ/919-791-4200/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
DocuS igned by:
3/11/2024
EPA Form 90T I� ev 9-94)Previous editions are obsolete.
Page# 1
NPDES yr/mo/day Inspection Type 1
31 NC0038300 I11 12I 24/02/26 1
17 18I
Section D: Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
Page# 2
Permit: NCO038300 Owner-Facility: S.S. Mobile Home Park
Inspection Date: 02/26/2024 Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ 0 ❑
application?
Is the facility as described in the permit? 0 ❑ ❑ ❑
#Are there any special conditions for the permit? ❑ ❑ 0 ❑
Is access to the plant site restricted to the general public? 0 ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? 0 ❑ ❑ ❑
Comment:
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained? 0 ❑ ❑ ❑
Are the receiving water free of foam other than trace amounts and other debris? 0 ❑ ❑ ❑
If effluent (diffuser pipes are required) are they operating properly? 0 ❑ ❑ ❑
Comment:
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit? 0 ❑ ❑ ❑
Is all required information readily available, complete and current? 0 ❑ ❑ ❑
Are all records maintained for 3 years (lab. reg. required 5 years)? 0 ❑ ❑ ❑
Are analytical results consistent with data reported on DMRs? 0 ❑ ❑ ❑
Is the chain-of-custody complete? 0 ❑ ❑ ❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs ❑
Are DMRs complete: do they include all permit parameters? 0 ❑ ❑ ❑
Page# 3
Permit: NCO038300 Owner-Facility: S.S. Mobile Home Park
Inspection Date: 02/26/2024 Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ ■ ❑
(If the facility is = or> 5 MGD permitted flow) Do they operate 24/7 with a certified ❑ ❑ ■ ❑
operator on each shift?
Is the ORC visitation log available and current? ■ ❑ ❑ ❑
Is the ORC certified at grade equal to or higher than the facility classification? ■ ❑ ❑ ❑
Is the backup operator certified at one grade less or greater than the facility ❑ ■ ❑ ❑
classification?
Is a copy of the current NPDES permit available on site? ■ ❑ ❑ ❑
Facility has copy of previous year's Annual Report on file for review? ❑ ❑ ■ ❑
Comment: bORC is not properly designated.. This is issue is addessed in CEI letter with
requirement for written resposne back to RRO..
Bar Screens Yes No NA NE
Type of bar screen
a.Manual ■
b.Mechanical ❑
Are the bars adequately screening debris? ■ ❑ ❑ ❑
Is the screen free of excessive debris? ■ ❑ ❑ ❑
Is disposal of screening in compliance? ■ ❑ ❑ ❑
Is the unit in good condition? ■ ❑ ❑ ❑
Comment: system (bar screen, areation basin, clairifer were rusted due to age.
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Is the basin free of dead spots? ■ ❑ ❑ ❑
Are surface aerators and mixers operational? ❑ ❑ ■ ❑
Are the diffusers operational? ■ ❑ ❑ ❑
Is the foam the proper color for the treatment process? ■ ❑ ❑ ❑
Does the foam cover less than 25% of the basin's surface? ■ ❑ ❑ ❑
Is the DO level acceptable? ❑ ❑ ❑ ■
Is the DO level acceptable?(1.0 to 3.0 mg/1) ❑ ❑ ❑ ■
Comment:
Page# 4
Permit: NC0038300 Owner-Facility: S.S. Mobile Home Park
Inspection Date: 02/26/2024 Inspection Type: Compliance Evaluation
Primary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater? 0 ❑ ❑ ❑
Is the site free of excessive buildup of solids in center well of circular clarifier? ❑ ❑ ■ ❑
Are weirs level? ❑ ❑ 0 ❑
Is the site free of weir blockage? ■ ❑ ❑ ❑
Is the site free of evidence of short-circuiting? 0 ❑ ❑ ❑
Is scum removal adequate? ■ ❑ ❑ ❑
Is the site free of excessive floating sludge? ■ ❑ ❑ ❑
Is the drive unit operational? ❑ ❑ 0 ❑
Is the sludge blanket level acceptable? 0 ❑ ❑ ❑
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth) ❑ ■ ❑ ❑
Comment: some grease/scum on surface of clairfier.
Sand Filters (Low rate) Yes No NA NE
(If pumps are used) Is an audible and visible alarm Present and operational? ■ ❑ ❑ ❑
Is the distribution box level and watertight? ❑ ❑ ❑
Is sand filter free of ponding? ■ ❑ ❑ ❑
Is the sand filter effluent re-circulated at a valid ratio? ❑ ❑ 0 ❑
# Is the sand filter surface free of algae or excessive vegetation? ■ ❑ ❑ ❑
# Is the sand filter effluent re-circulated at a valid ratio? (Approximately 3 to 1) ❑ ❑ ■ ❑
Comment:
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, ■ ❑ ❑ ❑
and sampling location)?
Comment:
Disinfection-Tablet Yes No NA NE
Are tablet chlorinators operational? 0 ❑ ❑ ❑
Are the tablets the proper size and type? ■ ❑ ❑ ❑
Number of tubes in use?
Is the level of chlorine residual acceptable? ■ ❑ ❑ ❑
Is the contact chamber free of growth, or sludge buildup? ■ ❑ ❑ ❑
Is there chlorine residual prior to de-chlorination? 0 ❑ ❑ ❑
Page# 5
Permit: NC0038300 Owner-Facility: S.S. Mobile Home Park
Inspection Date: 02/26/2024 Inspection Type: Compliance Evaluation
Disinfection-Tablet Yes No NA NE
Comment:
De-chlorination Yes No NA NE
Type of system ?
Is the feed ratio proportional to chlorine amount (1 to 1)? 0 ❑ ❑ ❑
Is storage appropriate for cylinders? ■ ❑ ❑ ❑
# Is de-chlorination substance stored away from chlorine containers? 0 ❑ ❑ ❑
Comment:
Are the tablets the proper size and type? ■ ❑ ❑ ❑
Are tablet de-chlorinators operational? ■ ❑ ❑ ❑
Number of tubes in use?
Comment:
Page# 6
E q
ROY COOPER ��s
Governor
ELIZABETH S. BISER
Secretary a�
RICHARD E. ROGERS,JR.
" QUM4
Director NORTH CAROLINA
Environmental Quality
March 11, 2024
Mr. James R. Edwards
S.S. Construction and Rental, Inc.
1808 Pinecrest St.
Burlington,NC 2715
Subject: Compliance Evaluation Inspection
S.S. Mobile Home Park-WWTP
NPDES Permit NCO038300
Chatham County
Dear Mr. Edwards:
On February 26, 2024, Danny Smith of the Raleigh Regional Office conducted a Compliance
Evaluation Inspection(CEI) of the wastewater treatment facility for S.S. Mobile Home Park, at 241
Graham Morre Road in Chatham County. The purpose of this inspection was to review facility's
compliance with the subject NPDES permit. During the inspection, the presence and cooperation of
Mr. James R. Edwards, Operator in Responsible Charge (ORC), was greatly appreciated and very
helpful to this review process.
Through NPDES permit (NC0038300), S.S. Construction and Rental Inc. is authorized to discharge treated
wastewater through outfall 001 to receiving waters designated as Brush Creek, Class C Waters, within the
Cape Fear River Basin.
Findings during inspection and file review were as follows:
1. The current NPDES permit(NC0038300) listed in DEQ's Basinwide Information Database
(BIMS) depicts the issued permit effective on August 1, 2022, and expiration September 30, 2026.
[Note: To receive automatic authorization to discharge after the expiration date, you will need to
submit a permit renewal application at least 180 days prior to the expiration of the permit.]
2. Since the implementation of EPA's NPDES Electronic Reporting Rule, S.S. Mobile Home Park
has been submitting its discharge monitoring reports (DMRs) electronically, instead of on paper.
The first DMR the Division received electronically from the permittee was December 2016.
3. The designated Operator in Responsible Charge (ORC) for S.S. Mobile Home Park is Mr. James R.
Edwards, a Grade WW II operator. No operator(s)were formally listed/designated as a back-
up Operator in Responsible Charge (bORC) for the subject facility.
D E QNorth Carolina Department of Environmental Quality I Division of Water Resources
512 North Salisbury Street 11617 Mail Service Center I Raleigh,North Carolina 27699-1617
........ a\ r 919.707.9000
S.S. Mobile Home Park—WWTP- CEI
NPDES Permit NCO038300
Page 2 of 3
Please fill out the attached designation form or you can access this form by going to the Operator
Certification website. [To find this form online you may google WPCSOCC. Then under wastewater Operator
Certification menu,on right side of page,you should click on"Downloads". The first item under the downloads is a
link to the ORC Forms:Designation and Registration.]
Once this form is completed, be sure to email the form to both: certadmin@deq.nc.gov AND
send a copy to Danny Smith by email(danny.smith@deq.nc.gov).
Please email Danny Smith a copy of the bORC designation form within 45-days of receipt of
this letter. Also, please clearly include in this written email response: 1)you have secured a
back-up Operator in Responsible Charge for the facility and 2) confirm that you have
emailed the completed bORC designation form to certadmin@deq.nc.gov.
4. For the review period of December 2021 through December 2023, the following exceedances were
identified S.S. Mobile Home Park(Permit No. NC0038300):
• Limit violations. For August 2022 and October 2023,two (2)Notice of Deficiencies (NODS) for
BOD (monthly average). One (1)Notice of Violation(NOV) for BOD, a monthly average
exceedances for November 2023.
• Monitorinsz. No monitoring violations occurred during this review period.
• Assessments. No Civil Penalty Assessments (CPAs) were issued/assessed during this
period. (The last CPA was assessed in 2016.)
5. The required Annual Administering and Compliance Monitoring Fee for the current billing period
has been paid. There are no overdue fees.
6. The inspector compared the March 2023 and August 2023 eDMR data against the bench lab data
and field data. No discrepancies were noted. The thermometers used for the self-monitoring
program is NIST certified or checked against the NIST certified thermometer.
7. The treatment component, as listed in the subject NPDES permit, includes the following:
Manual bar screen, aeration basin, clarifier, tablet chlorinator, chlorine contact chamber, one-pass
detention polishing sand-filter, tablet de-chlorinator, poly tank, and concrete tank for sludge
holding.
- All of the above listed components were observed to be present and operable during the walk
through of the plant.
- The aeration basin,bar screen, and clarifier were observed. Some grease and foam were
observed in both clarifier and the aeration basin. Components were operational with notable
rust, in-keeping with a system/wastewater treatment unit(s) of this age.
- Sand-filter was clear of debris and vegetation growth. The sand media was well maintained.
- Sludge is hauled by Clark Septic Tank Services. Sludge is taken to Siler City for disposal.
S.S. Mobile Home Park—WWTP- CEI
NPDES Permit NC0038300
Page 3 of 3
- The inspector observed the effluent discharge from the outfall 001 to the Brush Creek. The
effluent was clear with no observable solids or foam. No detrimental impacts to the receiving
waters from the effluent were observed.
The overall condition of the subject facility was compliant with the NPDES permit requirements as
observed on the day of the inspection. If you have questions or comments about the inspection, this
report or the requirements to take corrective action (if applicable), please do not hesitate to contact
Da!M.Smith(iWeq.nc.gov or call (919) 791-4248.
Sincerely,
DocuSigned by:
f.
Uaant,SSa
62916E6AB32144F...
Vanessa Manuel, Assistant Regional Supervisor
Water Quality Regional Operations Section
Raleigh Regional Office
Division of Water Resources,NCDEQ
Attachment: EPA Water Compliance Inspection Report
Cc: Laserfiche